VariTrac Systems: View
VariTrac Central Control Panles (CCPs) are seen as air systems in Tracer Ensemble.
- VariTrac I Comfort Managers are typically used with EMTK Trackers, which are not supported by Tracer Ensemble. To be used with Tracer Ensemble, these panels must be ugraded to BMTK trackers with VariTrac III CCPs.
- VariTrac II Central Control Panels are supported by Tracer Summit BCUs and Tracer Ensemble. VariTrac II Central Control Panel (CCP) has one type of system configuration: changeover bypass. CCP has two types of bypass damper control methods: static pressure and velocity.
- VariTrac III Central Control Panels are supported only by BMTK Tracker systems, not Tracer Summit BCUs. The VariTrac determines this configuration automatically based on the HVAC unit type. If the HVAC unit type is a variable air volume Voyager, VariTrac III automatically sets the system configuration to delivered VAV. All other HVAC unit types are configured as changeover bypass. VariTrac III does not support velocity bypass damper control; only static pressure bypass damper control is supported in the changeover bypass configuration.
To view VariTrac Systems:
- Go to Home | building name | Systems| Air Systems. A table appears with an air system in each row and basic status data in each column.
- Click on the name of the VariTrac system you want to view. The individual air system status page appears.
- VeriTrac II status ppoint definitions: VariTrac II Central Control Panel, VariTrac II Central Control Panel Groups, VariTrac II Central Control Panel VAV Boxes.