Presentation Name | Type | Description |
A/C Unit Type: Input |
Binary |
The type of unit the CCP is configured to control. Determined by the state of setting seven on DIP switch three (S3). |
Alarm Event Class [1-3] |
Numeric |
This is a three element array containing entries for alarm classes Informational, Auto Reset, and Manual Reset diagnostics. Each entry contains an index into the event action table. The event action table contains both a set of instructions for alarm routing and a list of referencer objects (the potential receivers). |
Auxiliary Heat Control: Ref |
Property Reference |
Specifies the property or constant used to determine the value of the "Auxiliary Heat Control: Tracer" property. |
Auxiliary Heat Control: Tracer |
Binary |
The value that is communicated by Tracer Summit to the VariTrac II Central Control Panel and is used to disable auxiliary heat on units configured as heat pumps. This property is not valid when the CCP System property "Unit Control Source: Tracer" is set to Local. |
Binary Out [1-6] |
Binary |
This arrayed property indicates the current state of each of the six binary outputs. |
Bypass Control Method: Input |
Binary |
Reflects the state of setting six on DIP switch two (S2) and indicates if the Central Control Panel’s bypass control is based on velocity pressure or static pressure. |
Bypass Damper Position |
Numeric |
The current position of the system bypass damper. Range: 0 to 100% |
Callers: Cool |
Numeric |
Indicates the number of UCMs that are cool callers. Range: 0 to 16 |
Callers: Heat |
Numeric |
Indicates the number of UCMs that are heat callers. Range: 0 to 16 |
Callers: Strong Cool |
Numeric |
Indicates the number of UCMs that are strong cool callers. Range: 0 to 16 |
Callers: Strong Heat |
Numeric |
Indicates the number of UCMs that are strong heat callers. Range: 0 to 16 |
Changeover Timer |
Numeric |
The number of minutes remaining before the VariTrac II Central Control Panel system is allowed to change its heat/cool mode. Range: 0 to 60 minutes |
Communication Address |
Numeric |
The UCM’s communications address. |
Communication Bad Message Count |
Numeric |
The number of message errors that have occurred while attempting to communicate with the UCM. |
Communication Channel |
Numeric |
The number of the BCU channel to which the UCM has been assigned. |
Communication Error Count |
Numeric |
The number of communication errors that have occurred while attempting to communicate with the UCM. |
Communication No Answer Count |
Numeric |
The number of unanswered communication attempts with the UCM. |
Communication Retry |
Binary |
This property is True when an attempt to send control data fails and False when communications are successful. |
Communication State |
Binary |
The communication status between the BCU and the UCM. |
Compressor 1 Status |
Binary |
The active status of compressor number 1. Note: This is a Voyager property. |
Compressor 2 Exists |
Binary |
Indicates if compressor 2 exists on the unit. Note: This is a Voyager property. |
Compressor 2 Status |
Binary |
The active status of compressor 2. Note: This is a Voyager property. |
Compressor Control: Ref |
Property Reference |
Specifies the property or constant used to determine the value of the "Compressor Control: Tracer" property. |
Compressor Control: Tracer |
Binary |
The value communicated by Tracer Summit to the VariTrac II Central Control Panel and used to disable compressor operation. Note: This disables all compressor operation, whether the unit is 2 heat/2 cool or heat pump. This property is not valid when the CCP System property "Unit Control Source: Tracer" is set to Local. |
Compressor Lockout: Input |
Binary |
Indicates if setting eight on DIP switch three (S3) is set to lockout (disable) all compressors. |
Condenser Fan A Contactor |
Binary |
The active status of condenser fan A. Note: This is a Voyager property. |
Condenser Fan B Contactor |
Binary |
The active status of condenser fan B. Note: This is a Voyager property. |
Config: Unit Type |
Multi-State |
The unit type of Voyager Rooftop. Note: This is a Voyager property. |
Configuration: Economizer |
Binary |
Indicates if the unit is configured with an optional economizer. Note: This is a Voyager property. |
Control Mode: Active |
Binary |
The current control mode of the Central Control Panel. |
Control Mode: Input |
Binary |
Reflects the state of binary input #1 on the CCP and will determine the CCP’s control mode if "Unit Control Source: Tracer" is Local or if the CCP loses communication with the BCU. |
Cooling Stages Enabled: Ref |
Property Reference |
Specifies the property or constant used to determine the value of the "Cooling Stages Enabled: Tracer" property. Range: 0 to 2 |
Cooling Stages Enabled: Tracer |
Numeric |
The value communicated by Tracer Summit to the VariTrac II Central Control Panel limiting the actual number of cooling stages allowed. Range: 0 to 2 This property is not valid when the CCP System property "Unit Control Source: Tracer" is set to Local. |
Diag: Automatic Reset |
Binary |
Indicates if an automatic reset diagnostic has occurred. This diagnostic type is cleared when the diagnostic condition no longer exists. |
Diag: CCP SA Temp Sensor Fail |
Binary |
Indicates if the VariTrac II Central Control Panel is receiving a valid input from its supply air temperature sensor. |
Diag: Comp 1 High Press Cutout |
Binary |
Indicates if any of the following apply to compressor 1: a high pressure condition exists, the winding temperature limit switch is open, or the compressor circuit breaker has tripped. Note: This is a Voyager property. |
Diag: Comp 1 Locked Out |
Binary |
Indicates if compressor 1 is locked out due to a device in the compressor’s contactor coil circuit being open or low pressure control being open four consecutive times without more than three continuous minutes of compressor operation. This is a manual reset diagnostic. Note: This is a Voyager property. |
Diag: Comp 1 LPC Input Open |
Binary |
Indicates if the low pressure control has opened in the compressor 1 disable input circuit, or if a field-installed device has opened. This is an auto reset diagnostic. Note: This is a Voyager property. |
Diag: Comp 2 High Press Cutout |
Binary |
Indicates if any of the following apply to compressor 2: a high pressure condition exists, the winding temperature limit switch is open, or the compressor circuit breaker has tripped. Note: This is a Voyager property. |
Diag: Comp 2 Locked Out |
Binary |
Indicates if compressor 2 is locked out due to a device in the compressor’s contactor coil circuit being open or low pressure control being open four consecutive times without more than three continuous minutes of compressor operation. This is a manual reset diagnostic. Note: This is a Voyager property. |
Diag: Comp 2 LPC Input Open |
Binary |
Indicates if the low pressure control has opened in the compressor 2 disable input circuit, or if a field-installed device has opened. This is an auto reset diagnostic. Note: This is a Voyager property. |
Diag: Control Request |
Binary |
Indicates if the CCP is requesting the BCU to send the latest control data. This property is "Yes" if power has been cycled on the CCP or if communications with the CCP are reestablished after they had been down for over 15 minutes. |
Diag: Dirty Filter |
Binary |
Indicates if the Voyager has determined that a dirty filter condition exists. Note: This is a Voyager property. |
Diag: Econ Min Position Fail |
Binary |
Indicates if the minimum position setpoint input on the economizer module is reading an open or short condition. This is valid only on units with economizers. This is an auto reset diagnostic. Note: This is a Voyager property. |
Diag: Flow Sensor Fail |
Binary |
Indicates if the VariTrac II Central Control Panel is receiving a valid input from its velocity/pressure sensor. |
Diag: Heat Fail |
Binary |
Indicates if either of the high temperature limit switches on a gas heat unit are open. When these limit switches open, a high temperature condition exists. This input is valid on all units with gas heat. This is an auto reset diagnostic. Note: This is a Voyager property. |
Diag: High Temp Input |
Binary |
Indicates if an open circuit on the TCI high temp input (TB2) exists. A field-installed device is normally wired to this input. This is an auto reset diagnostic. Note: This is a Voyager property. |
Diag: Information Warning |
Binary |
Indicates if an information only diagnostic has occurred. An information only diagnostic does not inhibit any unit operation. |
Diag: Manual Reset Required |
Binary |
Indicates if a manual reset diagnostic has occurred. The manual reset diagnostic requires that the unit be reset either from the Tracer or the unit (by cycling the Voyager’s power). |
Diag: OA Rel Humid Fail |
Binary |
Indicates if the outdoor air relative humidity sensor input on the economizer board is reading an open or short condition. This diagnostic is valid only on units with economizers. This is an auto reset diagnostic. Note: This is a Voyager property. |
Diag: OA Temp Sensor Fail |
Binary |
Indicates if the outdoor air temperature sensor input on the Voyager is reading an open or short condition. This diagnostic is valid on all Voyager units. This is an auto reset diagnostic. Note: This is a Voyager property. |
Diag: RA Rel Humid Fail |
Binary |
Indicates if the return air relative humidity sensor input on the economizer board is reading an open or short condition. This diagnostic is valid only on units with economizers. This is an auto reset diagnostic. Note: This is a Voyager property. |
Diag: RA Temp Sensor Fail |
Binary |
Indicates if the return air temperature sensor input on the economizer board is reading an open or short condition. This diagnostic is valid only on units with economizers. This is an auto reset diagnostic. Note: This is a Voyager property. |
Diag: Reference Enthalpy Fail |
Binary |
Indicates if the reference enthalpy setpoint input on the economizer board is reading an invalid value. This diagnostic is valid only on units with economizers which are also set up for reference enthalpy control. This is an auto reset diagnostic. Note: This is a Voyager property. |
Diag: Supply Fan Fail |
Binary |
Indicates if the supply air flow cooling input on the Voyager has been open for five seconds while the supply fan output was on. This is a manual reset diagnostic. Note: This is a Voyager property. |
Diag: Voyager Comm Fail |
Binary |
The communication statu between the CCP and the Voyager. Note: This property is Normal if a Voyager is communicating or if a Voyager has not communicated with the CCP since power was cycled to the CCP. |
Diag: Voyager SA Temp Sens Fail |
Binary |
Indicates if the supply air temperature sensor input on the unit is reading an out-of-range value. This diagnostic is valid on all units with supply air temperature sensors. This is an auto reset diagnostic. Note: This is a Voyager property. |
Econ Calibration in Process |
Binary |
Indicates if the economizer is currently being calibrated. This occurs at initial power up and when the economizer exits the economizing mode. This property is valid only for units with economizers. Note: This is a Voyager property. |
Econ Min Pos Mult Enable: Setup |
Binary |
Determines if the "Econ Min Pos Multiplier: Ref" property is enabled. If the referencer is not enabled, the "Econ Min Pos Multiplier: Tracer " property is set equal to 1.0. |
Econ Min Pos Multiplier: Ref |
Property Reference |
Specifies the property or constant used to determine the value of the "Econ Min Pos Multiplier: Tracer" property. Range: 0.0 to 10.0This referencer has no effect on the "Econ Min Pos Multiplier: Tracer" property if the "Econ Min Pos Mult Enable: Setup" property is "Auto". |
Econ Min Pos Multiplier: Tracer |
Numeric |
The value communicated by Tracer Summit to the VariTrac II Central Control Panel and iused to adjust the Voyager’s active economizer minimum position. Range: 0.0 to 10.0This property is not valid when the CCP System property "Unit Control Source: Tracer" is set to Local or when a communicating Voyager is not present. |
Economizer Damper Position |
Numeric |
The current position of the outdoor air damper. This property is valid only for units with economizers. Range: 0 to 100% Note: This is a Voyager property. |
Economizer Min Position |
Numeric |
The minimum position that the outdoor air damper is controlled to if outside air conditions are not OK to economize. This property is valid only for units with economizers. Range: 0 to 50% Note: This is a Voyager property. |
Economizer Min Position: Input |
Numeric |
The minimum position set via the economizer damper minimum position potentiometer on the economizer module. This property is valid only on units with economizers. Range: 0 to 50 % Note: This is a Voyager property. |
Economizer Min Position: Local |
Numeric |
This property indicates the edited economizer minimum damper position. This value can be edited at the VariTrac II Central Control Panel or on the Tracer Summit system. Range: 0 to 50% Note: This value does not show the effect of the minimum position multiplier. |
Economizer: OK to Economize? |
Binary |
Indicates if the outdoor air can be used for free cooling. Note: This is a Voyager property. |
Economizer: Use Local Min Pos |
Binary |
This value determines if the Voyager’s local minimum position potentiometer (i.e., "Economizer Min Position: Input") is used to determine the economizer minimum position. If this property is "No", the economizer minimum position is determined using the "Economizer Min Position: Local" property. |
Exhaust Fan Status |
Binary |
The status of the exhaust fan output. Note: This is a Voyager property. |
Groups[1-4] |
Object ID |
An array consisting of the VariTrac II CCP Group object ID’s associated with this CCP. |
Heat Stage 1 Status |
Binary |
The status of heating stage 1. Note: This is a Voyager property. |
Heat Stage 2 Status |
Binary |
The status of heating stage 2. Note: This is a Voyager property. |
Heat/Cool Changeover: Input |
Binary |
Reflects the state of binary input #3 on the CCP and determines the CCP’s heat/cool changeover mode if "Unit Control Source: Tracer" is Local or if the CCP loses communication with the BCU. |
Heat/Cool Changeover: Setup |
Binary |
Determines the value of the "Heat/Cool Changeover: Tracer" property. |
Heat/Cool Changeover: Tracer |
Binary |
If this property is "Auto", the CCP automatically determines the heat/cool mode. If this property is set to "Tracer", the "Heat/Cool Mode: Tracer" property determines the actual heat/cool mode. This property is not valid when the CCP System property "Unit Control Source: Tracer" is set to Local. |
Heat/Cool Mode: Active |
Binary |
The current heat/cool mode of the of the VariTrac II Central Panel. |
Heat/Cool Mode: Input |
Binary |
Reflects the state of binary input #2 on the CCP and determines the heat/cool mode of the CCP when the "Heat/Cool Changeover: Input" is being used to determine the changeover mode and is in the manual state. |
Heat/Cool Mode: Ref |
Property Reference |
Specifies the property or constant used to determine the value of the "Heat/Cool Mode: Tracer" property. |
Heat/Cool Mode: Tracer |
Binary |
The value, which is communicated by Tracer Summit to the VariTrac II Central Control Panel, that determines the heat cool mode when the "Heat/Cool Changeover: Tracer" property is set to Tracer. This property is not valid when the CCP System property "Unit Control Source: Tracer" is set to Local. |
Heating Stages Enabled: Ref |
Property Reference |
Specifies the property or constant used to determine the value of the "Heating Stages Enabled: Tracer" property. Range: 0 to 2 |
Heating Stages Enabled: Tracer |
Numeric |
The value, communicated by Tracer Summit to the VariTrac II Central Control Panel, limiting the actual number of heating stages that are allowed. Range: 0 to 2 This property is not valid when the CCP System property "Unit Control Source: Tracer" is set to Local. |
Min Calls to Changeover |
Numeric |
This property indicates the edited minimum opposite calls to changeover. This value can be edited at the VariTrac II Central Control Panel or on the Tracer Summit system. Range: 1 to 4 |
Min Strong Calls to Changeover |
Numeric |
This property indicates the edited minimum opposite strong calls to changeover. This value can be edited at the VariTrac II Central Control Panel or on the Tracer Summit system. Range: 1 to 4 |
Min Time to Changeover |
Numeric |
This property indicates the edited minimum time to changeover. This value can be edited at the VariTrac II Central Control Panel or on the Tracer Summit system. Range: 10 to 60 minutes |
Minimum Supply Flow |
Numeric |
This is the CCP’s velocity pressure setpoint. It is expressed as a percentage of the air flow measurement taken during calibration. Range is 10% to 95% Note: This property only applies if "Bypass Control Method: Input" is "Velocity." |
Mode: Calibration Active |
Binary |
Indicates if the CCP is in the process of calibrating its bypass damper and its air flow sensor. |
Mode: Morning Warmup |
Binary |
This property indicates if the VariTrac II Central Control Panel is in the morning warmup mode. |
Mode: Priority Shutdown |
Binary |
Indicates if the VariTrac II Central Control Panel is in priority shutdown. Note: This property is Yes if: shutdown is sent from the BCU, the Voyager’s high temp input has tripped, the CCP SA Temp input is shorted, or the CCP SA Temp input is open and there’s no Voyager SA temp available. |
Mode: Test Mode Active |
Binary |
This property indicates whether setting eight on DIP switch two (S2) is set to test. |
Object Identifier |
Object ID |
Unique hexadecimal identifier of this particular object. This ID is used internally to identify an object. |
Object Name |
Character |
Allows the assignment of a unique printable name to the object for user identification. |
Object Type |
Object Type |
This property designates the object’s type (e.g., VariTrac II CCP System). |
Outdoor Air Humidity: Input |
Numeric |
The value reported by the outdoor air relative humidity input on the economizer module. This property is valid only on units with economizers. Range: 0 to 100% RH Note: This is a Voyager property. |
Outdoor Air Temperature: Input |
Numeric |
The value reported by the outdoor air temperature sensor on the unit. Range: -40.0 to 150.0°F Note: This is a Voyager property. |
Priority Shutdown: Tracer |
Binary |
This property indicates the value communicated by Tracer Summit to the VariTrac II Central Control Panel and used to shut down the system. Auto allows the CCP to operate normally. Shutdown instructs the CCP to shut down all mechanical operation immediately. This property is not valid when the CCP System property "Unit Control Source: Tracer" is set to Local. |
Reference Enthalpy |
Numeric |
Set by dip switches on the economizer controller and may be used to determine if it is OK to Economize. This property is valid only on units with economizers. Possible values: 19, 22, 25, 28 BTU/lbm Note: This is a Voyager property. |
Return Air Humidity: Input |
Numeric |
The value reported by the return air relative humidity input on the economizer. This property is valid only on units with economizers. Range: 0 to 100% RH Note: This is a Voyager property. |
Return Air Temperature: Input |
Numeric |
The value reported by the return air temperature input on the economizer module. This property is valid only on units with economizers. Range: -40.0 to 150.0°F Note: This is a Voyager property. |
SA Flow: Input |
Numeric |
This property indicates the flow (velocity pressure) measured by the velocity sensor. Range: 0 to 100% of system capacity Note: This property only applies if "Bypass Control Method: Input" is "Velocity." |
SA Pressure Control Band: Local |
Numeric |
This property indicates the control band the CCP uses when controlling static pressure. Range: 5 to 100% of the system design pressure Note: This property only applies if "Bypass Control Method: Input" is "Static". |
SA Pressure Setpoint: Active |
Numeric |
This property indicates the actual static pressure setpoint the CCP is using during operation. Units are Inches of Water Column and are determined by multiplying "SA Pressure: Design" by "SA Pressure Setpoint: Local." Range: 90 to 250% of design pressure Note: This property only applies if "Bypass Control Method: Input" is "Static". |
SA Pressure Setpoint: Local |
Numeric |
This property indicates the locally edited Static Pressure Setpoint and is given in a percentage of design air flow. Range: 90 to 250%The CCP multiplies this number by the design supply air pressure measured during calibration to determine the active supply air pressure setpoint. Note: This property only applies if "Bypass Control Method: Input" is "Static". |
SA Pressure: Design |
Numeric |
This property indicates the supply air pressure measured during system calibration. Units: Inches of Water Column. Design pressure represents system static pressure with all VAV dampers at Max. Note: This property only applies if "Bypass Control Method: Input" is "Static". |
SA Pressure: Input |
Numeric |
This property indicates the static pressure measured by the static pressure sensor.Units: Inches of Water Column. Note: This property only applies if "Bypass Control Method: Input" is "Static". |
SA Temperature: Active |
Numeric |
The supply air temperature currently in use. It is equal to the "SA Temperature: CCP Input" if it has not failed. If this input has failed, it is equal to "SA Temperature: Voyager Input". If both the CCP and Voyager supply air temp inputs have failed, the active supply air temperature is 0. |
SA Temperature: CCP Input |
Numeric |
The temperature being measured by the supply air temperature sensor connected to the CCP. |
SA Temperature: Voyager Input |
Numeric |
The value reported by the supply air temperature sensor connected to the Voyager unit. This sensor value is only available on units with an economizer. Range: -40.0 to 150.0°F Note: This is a Voyager property. |
Security Class |
Numeric |
Identifies the security class used for access privileges to the given object. |
Slave State |
Multi-State |
The state to which the CCP is controlling the Voyager. The slave states allow the CCP to make the heat/cool and staging decisions for the Voyager unit. The possible slave states are: |
Software Revision |
Numeric |
This is the version of the VariTrac II Central Control Panel software. |
Spare Output: Tracer |
Binary |
The state to which the Tracer is controlling the spare binary output. Note: This property only influences the state of the spare output if the "Spare Output Control" parameter has been set to ICS at the Central Control Panel. This property is not valid when the CCP System property "Unit Control Source: Tracer" is set to Local. |
Supply Fan Status |
Binary |
If a Voyager is communicating with the CCP, this property indicates the state of the Voyager’s fan. If the Voyager is not communicating, this property indicates the state of binary output 1 on the CCP. |
UCMs[1-16] |
Object ID |
An array consisting of the VariTrac II CCP VAV UCM object ID’s that are associated with this CCP. |
Unit Control Source: Setup |
Binary |
Determines the value of the "Unit Control Source: Tracer" property. |
Unit Control Source: Tracer |
Binary |
The value communicated by Tracer Summit to the VariTrac II Central Control Panel that determines whether the Central Control Panel is being controlled locally or by the Tracer Summit system. |
Update Tag |
Numeric |
Used to indicate that the nonvolatile memory resident data within the particular instance has changed. |
Voyager Exists |
Binary |
Indicates if a Voyager has communicated with the CCP since power was last cycled on the CCP. |