VAV I

Property Type Description

Active Cool Setpoint

Numeric

The cooling setpoint presently in effect.

Active Heat Setpoint

Numeric

The heating setpoint presently in effect.

Air Valve Drive Closed: Local

Binary

State of drive closed override resident at the UCM.

Air Valve Drive Closed: Ref

Binary

This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the state of the drive closed override.

Air Valve Drive Max: Local

Binary

State of drive max flow override resident at the UCM.

Air Valve Drive Max: Ref

Binary

This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the state of the drive max flow override.

Air Valve Drive Min: Local

Binary

State of drive min flow override resident at the UCM.

Air Valve Drive Min: Ref

Binary

This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the state of the drive min flow override.

Air Valve Drive Open: Local

Binary

State of drive open override resident at the UCM.

Air Valve Drive Open: Ref

Binary

This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the state of the drive open override.

Air Valve Flow

Numeric

Current air flow in CFM.

Air Valve Flow Constant

Numeric

Scaling factor for air valve flow based on valve size and type.

Air Valve Flow Rate

Numeric

Current air flow in percent of VAV unit nominal rating.

Air Valve Flow Rate (Heat)

Numeric

Not applicable.

Air Valve Max Flow Stpnt: Local

Numeric

Value of the max flow setpoint resident at the UCM.

Air Valve Min Flow Release: Loc

Binary

State of min flow setpoint release resident at the UCM.

Air Valve Min Flow Stpnt: Local

Numeric

Value of the min flow setpoint resident at the UCM.

Air Valve Override Status

Multi-State

Flow control override may be open, close, minimum, or maximum.

Air Valve Position

Numeric

Current position in percent of stroke (0–100%) of air valve.

Air Valve Position (Heat)

Numeric

Not applicable.

Air Valve Size Index

Numeric

Nominal CFM rating of air valve.

Air Vlv Min Heat Flow Stpnt: Loc

Numeric

Value of the min heat flow setpoint resident at the UCM.

Alarm Event Class

Numeric

Contains the Alarm and Message Routing Class number (1–20) that is used to route messages when this object is in alarm.

Algorithm Output

Numeric

Not applicable.

Algorithm Output (Heat)

Numeric

Not applicable.

Auxiliary Sensor Exist

Binary

Indicates if the auxiliary temperature sensor is installed.

Auxiliary Temperature

Numeric

Current temperature measured at the auxiliary temperature sensor.

Calibrate Initiate: Local

Binary

State of calibrate initiate resident at the UCM.

Calibrate Initiate: Ref

Binary

This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the state of calibrate initiate.

Calibration in Effect

Binary

UCM is recalibrating the air valve flow sensor.

Calibration Start

Binary

Not applicable.

Calibration Stop

Binary

Not applicable.

Communication Address

Numeric

Indicates the assigned communications address value of the VAV I.

Communication Bad Message Count

Numeric

Keeps track of the number of message errors that occur when attempting to communicate with the VAV I.

Communication Channel

Numeric

Indicates the assigned communications channel value of the VAV I.

Communication Error Count

Numeric

Keeps track of the number of communications errors that occur when attempting to communicate with the VAV I.

Communication No Answer Count

Numeric

Keeps track of the number of unanswered communications with the VAV I.

Communication State

Binary

This property indicates the status of communications between the BCU and the UCM.  0=Down, 1=Up.

Control Event Class

Numeric

Contains the Alarm and Message Routing Class number (1–20) that is used to route messages when this object is controlled.

Control Mode

Multistate

This property indicates the control mode (occupy, unoccupy, etc.) of the UCM.

Control Offset in Effect

Binary

Indicates if setpoints are adjusted by the control offset value.

Diag: Cool Setpoint Fail

Binary

Not applicable.

Diag: Fan Control Setpoint Fail

Binary

Not applicable.

Diag: Flow Sensor Fail

Binary

Indicates if air valve flow sensor signal is out of normal range.

Diag: Heat Flow Sensor Fail

Binary

Not applicable.

Diag: Heat Stpt Fail

Binary

Not applicable.

Diag: Max Flow Setpoint Fail

Binary

Not applicable.

Diag: Min Flow Setpoint Fail

Binary

Not applicable.

Diag: Min Heat Setpoint Fail

Binary

Not applicable.

Diag: Thumbwheel Setpoint Fail

Binary

Indicates if the thumbwheel setpoint signal is out of normal range.

Diag: Unocc Cool Setpoint Fail

Binary

Not applicable.

Diag: Unocc Heat Setpoint Fail

Binary

Not applicable.

Diag: Zone Sensor Fail

Binary

Indicates if the zone temperature sensor is out of normal range.

Dual Duct

Binary

Not applicable.

Fan Control Method: Local

Binary

This property indicates whether the UCM will control the (parallel) fan based on a flow setpoint or a degrees setpoint.

Fan Control Offset

Numeric

This value will determine when a parallel fan will be turned on or off. This may be specified as a temperature offset above the zone heating setpoint (2-10 degrees), or as a percentage of unit nominal airflow (0-100%) This property is valid for parallel fan powered VAV only.

Fan Control Setpoint: Local

Numeric

This property indicates when the (parallel) fan will be energized when the fan control method is flow.

Fan Disable: Local

Binary

State of fan disable override resident at the UCM.

Fan Disable: Ref

Binary

This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the state of the fan disable override.

Fan Exists

Binary

Indicates if the UCM is configured to control a local fan.

Fan Output

Binary

Indicates if parallel fan output is On or Off.

Fan Type

Binary

Specifies type of fan the UCM is configured to control: series = On, Parallel = Off.

Heat Active

Binary

Indicates if heat output is On or Off.

Heat Control FPWM

Binary

Specifies control of electric heat. UCM configuration: Fast pulse width modulation = On, Slow pulse width modulation = False.

Heat Control Staged Electric

Binary

Specifies control of electric heat. UCM configuration: Staged electric = On, No staged electric = Off.

Heat Disable: Local

Binary

State of heat disable override resident at the UCM.

Heat Disable: Ref

Binary

This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the state of the heat disable override.

Heat Exists

Binary

Specifies if UCM is configured to control local heat.

Hot Water Control Type

Binary

Specifies type of hot water heat the UCM is configured to control: Proportional = On, On/Off = Off.

Last Control Date Time

Date/Time Numeric

This indicates the date and time when the present value property of this object was last controlled.

Mode: Heat/Cool

Binary

Indicates mode of heating control action (On), or cooling control action (Off).

Object Identifier

Object ID

Unique hexadecimal ID of this object. This ID is used internally to identify the object.

Object Type

Multi-State

Designates object’s type (i.e., analog input, binary output, TCM, PCM, etc.).

Occupied Cool Setpoint: Local

Numeric

Value of the occupied cool setpoint resident at the UCM.

Occupied Cool Setpoint: Ref

Numeric

This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the occupied cool setpoint.

Occupied Heat Setpoint: Local

Numeric

Value of the occupied heat setpoint resident at the UCM.

Occupied Heat Setpoint: Ref

Numeric

This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the occupied heat setpoint.

Present Value

Multi-State

Current value of the VAV I.

Thumbwheel Setpoint Enable

Binary

State of thumbwheel setpoint enable resident at the UCM.

Timed Override Request

Binary

A timed override request has been initiated and will be reset to Off after 2 minutes.

Unit Type

Binary

Indicates if VAV unit is VariTrac (On) or VariTrane (Off).

Unoccupied Cool Setpoint: Local

Numeric

Value of the unoccupied cool setpoint resident at the UCM.

Unoccupied Cool Setpoint: Ref

Numeric

This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the unoccupied cool setpoint.

Unoccupied Heat Setpoint: Local

Numeric

Value of the unoccupied heat setpoint resident at the UCM.

Unoccupied Heat Setpoint: Ref

Numeric

This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the unoccupied heat setpoint.

Update Tag

Numeric

Value indicating last edit change of this object.

VAV Air System Identification

Object Ref

Specifies the VAV air system to which this UCM is assigned.

VAV Control Offset Enable: Ref

Binary

This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the state of the control offset override.

Zone Temperature

Numeric

Current temperature measured at the zone temperature sensor.