Trane Europe Chiller (TEC)

Property Type Description

Active Setpoint

Numeric

This is the current value of the temperature setpoint used to control the leaving chilled water temperature or the leaving hot water temperature. Based on the operating mode of the chiller, this setpoint will be the value of either the "Chilled Water Setpoint: Tracer" property or the "Hot Water Setpoint: Tracer" property.Range: -31.0 to 177.8 °F (-35.0 to 81.0 °C)

Alarm Event Class [1-3]

Numeric

This is a three element array containing entries for alarm classes: Informational Diagnostics, Auto Reset Diagnostics, and Manual Reset Diagnostics. Each entry contains an index into the event action table. The event action table contains both a set of instructions for alarm routing, and a stretchy list of referencer objects (the potential receivers).

Capacity Control: Active

Binary

This is the capacity control status. Capacity control will be reduced only when "Capacity Control: Tracer" is "Reduced" and "Unit Control Source" is "Tracer".0 = Normal, 1 = Reduced

Capacity Control: Ref

Referencer

This is the value used by the BCU to determine which value to communicate to the chiller UCM as the normal or reduced capacity request. (This property feeds the "Capacity Control: Tracer" property.)0 = Normal, 1 = Reduced

Capacity Control: Tracer

Binary

This is the value communicated by the system to the chiller UCM and used to request normal or reduced capacity operation. Reduced capacity is implemented by disabling circuit 2.0 = Normal, 1 = ReducedDefault: Normal

Chilled Water Flow Status

Binary

This is the status of chilled water flow.0 = No Flow, 1 = Flow

Chilled Water Pump Output

Binary

This is the current state of the evaporator pump output.0 = Off, 1 = On

Chilled Water Setpoint: Source

Binary

This is the source of the chiller setpoints.0 = Local, 1 = Tracer

Chilled Water Setpoint: Ref

Referencer

This is the value used by the BCU to determine which value to communicate to the chiller UCM as the chilled water setpoint. (This property feeds the "Chilled Water Setpoint: Tracer" property.)Range: -14.8 to 86.0 °F (-26.0 to 30.0 °C)

Chilled Water Setpoint: Tracer

Numeric

This is the value communicated by the system to the chiller UCM and used as the leaving chilled water temperature setpoint. (This setpoint is the primary control value for the chiller in the cool mode.)Range: -14.8 to 86.0 °F (-26.0 to 30.0 °C)Default: 42.8 °F (6.0 °C)

Chilled Water Temp: Entering

Numeric

This is the temperature of the water entering the chiller.Range: -31.0 to 177.8 °F (-35.0 to 81.0 °C)

Chilled Water Temp: Leaving

Numeric

This is the temperature of the water leaving the evaporator. Maintaining this temperature is the primary control objective of the chiller. For single circuit chillers, this property will represent the actual temperature of the water leaving the evaporator. For dual circuit chillers, this property will represent the average temperature of the water leaving both evaporators.Range: -31.0 to 177.8 °F (-35.0 to 81.0 °C)

Chilled Wtr Pump Request: Ref

Referencer

This is the value used by the BCU to determine which value to communicate to the chiller UCM as the chilled water pump request. (This property feeds the "Chilled Wtr Pump Request: Tracer" property.)0 = Auto, 1 = On

Chilled Wtr Pump Request: Tracer

Binary

This is the value communicated by the system to the chiller UCM and used to request chilled water pump control.0 = Auto, 1 = OnDefault: Auto

Chiller Enable/Disable: Tracer

Binary

This is the value communicated by the system to the chiller UCM and used to disable the chiller or put it into an auto mode.0 = Disable, 1 = AutoDefault: (priority arbitrated by "Present Value")

Ckt Limited / Not Ready: CKT1

Binary

This is whether circuit 1 is either limited or not ready.0 = No, 1 = Yes

Ckt Limited / Not Ready: CKT2

Binary

This is whether circuit 2 is either limited or not ready.0 = No, 1 = Yes

Communication Address

Numeric

This is the assigned communication address of the UCM.

Communication Bad Message Count

Numeric

This is the number of message errors that occur when attempting to communicate with the UCM.

Communication Channel

Numeric

This is the assigned communication channel of the UCM.

Communication Error Count

Numeric

This is the number of communications errors that occur when attempting to communicate with the UCM.

Communication No Answer Count

Numeric

This is the number of unanswered communications with the UCM.

Communication State

Binary

This is the chiller’s communication state.0 = Down, 1 = Up

Compressor A Output

Binary

This is the current state of the compressor A1 output.0 = Off, 1 = On

Compressor A Run Time

Numeric

This is the number of hours compressor A1 has run. Once it has reached its maximum value, this hours counter will automatically be reset back to 0.Range: 0 to 1,048,576 hours

Compressor A Starts

Numeric

This is the number of starts compressor A1 has had. Once it has reached its maximum value, this starts counter will automatically be reset back to 0.Range: 0 to 1,048,575 starts

Compressor B Output

Binary

This is the current state of the compressor B1 output.0 = Off, 1 = On

Compressor B Run Time

Numeric

This is the number of hours compressor B1 has run. Once it has reached its maximum value, this hours counter will automatically be reset back to 0.Range: 0 to 1,048,576 hours

Compressor B Starts

Numeric

This is the number of starts compressor B1 has had. Once it has reached its maximum value, this starts counter will automatically be reset back to 0.Range: 0 to 1,048,575 starts

Compressor C Output

Binary

This is the current state of the compressor A2 output.0 = Off, 1 = On

Compressor C Run Time

Numeric

This is the number of hours compressor A2 has run. Once it has reached its maximum value, this hours counter will automatically be reset back to 0.Range: 0 to 1,048,576 hours

Compressor C Starts

Numeric

This is the number of starts compressor A2 has had. Once it has reached its maximum value, this starts counter will automatically be reset back to 0.Range: 0 to 1,048,575 starts

Compressor D Output

Binary

This is the current state of the compressor B2 output.0 = Off, 1 = On

Compressor D Run Time

Numeric

This is the number of hours compressor B2 has run. Once it has reached its maximum value, this hours counter will automatically be reset back to 0.Range: 0 to 1,048,576 hours

Compressor D Starts

Numeric

This is the number of starts compressor B2 has had. Once it has reached its maximum value, this starts counter will automatically be reset back to 0.Range: 0 to 1,048,575 starts

Compressor In Anti-Recycle

Binary

This is whether one or more of the compressors is in an anti-recycle state.0 = No, 1 = Yes

Compressor Running

Binary

This is the current status of the chiller, and indicates when one or more compressors is running.0 = No, 1 = Yes

Cond Saturated Refrig Press CKT1

Numeric

This is the value of the condenser saturated refrigerant pressure input from circuit 1 on the chiller.Range: -14 to 507 PSI (-96.5 to 3495.6 kPa)

Cond Saturated Refrig Press CKT2

Numeric

This is the value of the condenser saturated refrigerant pressure input from circuit 2 on the chiller.Range: -14 to 507 PSI (-96.5 to 3495.6 kPa)

Cond Saturated Refrig Temp: CKT1

Numeric

This is the value of the condenser saturated refrigerant temperature from circuit 1, and is used to monitor the condition of the condenser on circuit 1.Range: -31.0 to 177.8 °F (-35.0 to 81.0 °C)

Cond Saturated Refrig Temp: CKT2

Numeric

This is the value of the condenser saturated refrigerant temperature from circuit 2, and is used to monitor the condition of the condenser on circuit 2.Range: -31.0 to 177.8 °F (-35.0 to 81.0 °C)

Condenser Fan Status

Binary

This is the status of line fan 1.0 = Off, 1 = On

Condenser Water Temp: Entering

Numeric

This is the temperature of the water entering the condenser, and is used for monitoring the condition of the condenser.Range: -31.0 to 177.8 °F (-35.0 to 81.0 °C)

Condenser Water Temp: Leaving

Numeric

This is the temperature of the water leaving the condenser, and is used for monitoring the condition of the condenser.Range: -31.0 to 177.8 °F (-35.0 to 81.0 °C)

Config: Unit Type

Multi-State

This is the unit configuration, and is edited by the operator. 0 = CGAH/RAUH 1 = CGWH/CCUH 2 = CGCH/RACH 3 = CXAH 4 = Other Trane Europe ChillerDefault: CGAH / RAUH

Control Event Class

Numeric

This determines where control messages are routed when the object’s present value is controlled.

Diag: Automatic Reset

Binary

This indicates that an automatic reset diagnostic exists.0 = No, 1 = Yes

Diag: Automatic Reset CKT1

Binary

This indicates that an automatic reset diagnostic exists on circuit 1.0 = No, 1 = Yes

Diag: Automatic Reset CKT2

Binary

This property indicates an automatic reset diagnostic exists on circuit 2.0 = No, 1 = Yes

Diag: Information Warning

Binary

This indicates an informational warning diagnostic exists. It is calculated based on the last diagnostic enumeration. Since the last diagnostic is prioritized such that the informational warning diagnostics are of the lowest priority, this property will not indicate any potential informational warning diagnostic exists when nearly any of the automatic reset diagnostics exist or any of the manual reset required diagnostics exist.0 = No, 1 = Yes

Diag: Last

Multi-State

This is the last diagnostic to occur on the chiller. The diagnostics are ordered here from lowest priority (first) to highest priority (last). When a diagnostic occurs, the UCM will place it in the last diagnostic only if it is of higher priority than any existing last diagnostic.
0 = None
1 = Service Demand
2 = EEPROM Parameter Change
3 = External RAM Parameter Change
4 = EEPROM Parameters Programmed
5 = User Circuit 1 Stop
6 = User Circuit 2 Stop
7 = External Circuit 1 Stop
8 = External Circuit 2 Stop
9 = Remote Circuit 1 Stop
10 = Remote Circuit 2 Stop
11 = User Unit Stop
12 = External Unit Stop
13 = Remote Unit Stop
14 = Operator Stop
15 = EEPROM Fault
16 = Circuit 1 Limiting
17 = Circuit 2 Limiting
18 = Circuit 1 HP Limit
19 = Circuit 2 HP Limit
20 = Low Ambient
21 = Circuit 1 Defrost
22 = Circuit 2 Defrost
23 = Evap Water Flow
24 = Sensor 4 Main
25 = Sensor 1 I/O 2
26 = Sensor 1 I/O 3
27 = Sensor 1 I/O 4
28 = Sensor 1 Main
29 = Sensor 2 Main
30 = Sensor 3 Main
31 = Sensor 1 I/O 1
32 = Sensor 2 I/O 1
33 = Sensor 3 I/O 1
34 = Communication I/O 1
35 = Communication I/O 2
36 = Communication I/O 3

Diag: Last (continued)

Multi-State

37 = Communication I/O 4
38 = Fan Inverter 1
39 = Fan Inverter 2
40 = Fan Protection
41 = Low Refrigerant Circuit 1
42 = Low Refrigerant Circuit 2
43 = Low Water Circuit 1
44 = Low Water Circuit 2
45 = Pressure Circuit 1
46 = Pressure Circuit 2
47 = Discharge Circuit 1
48 = Discharge Circuit 2
49 = Bypass Circuit 1
50 = Bypass Circuit 2
51 = Compressor A1 Fault
52 = Compressor B1 Fault
53 = Compressor A2 Fault
54 = Compressor B2 Fault
55 = Circuit 1 Fault
56 = Circuit 2 Fault
57 = Unit Fault
58 = Unit Locked

Diag: Man Reset Reqd: CKT1

Binary

This indicates a manual reset required diagnostic exists on circuit 1.0 = No, 1 = Yes

Diag: Man Reset Reqd: CKT2

Binary

This indicates a manual reset required diagnostic exists on circuit 2.0 = No, 1 = Yes

Diag: Manual ResetRequired

Binary

This indicates a manual reset required diagnostic exists.0 = No, 1 = Yes

Evap Leaving Water Temp: CKT1

Numeric

This is the temperature of the water leaving the evaporator on circuit 1.Range: -31.0 to 177.8 °F (-35.0 to 81.0 °C)

Evap Leaving Water Temp: CKT2

Numeric

This is the temperature of the water leaving the evaporator on circuit 2.Range: -31.0 to 177.8 °F (-35.0 to 81.0 °C)

Evap Saturated Refrig Press CKT1

Numeric

This is the value of the evaporator saturated refrigerant pressure input from circuit 1 on the chiller.Range: -14 to 507 PSI (-96.5 to 3495.6 kPa)

Evap Saturated Refrig Press CKT2

Numeric

This is the value of the evaporator saturated refrigerant pressure input from circuit 2 on the chiller.Range: -14 to 507 PSI (-96.5 to 3495.6 kPa)

Evap Saturated Refrig Temp: CKT1

Numeric

This is used to monitor the condition of the evaporator on circuit 1.Range: -31.0 to 177.8 °F (-35.0 to 81.0 °C)

Evap Saturated Refrig Temp: CKT2

Numeric

This is used to monitor the condition of the evaporator on circuit 2.Range: -31.0 to 177.8 °F (-35.0 to 81.0 °C)

Evaporator Heater Output

Binary

This is the status of the evaporator heater output .0 = Off, 1 = On

Heat/Cool Mode: Ref

Referencer

This is the value used by the BCU to determine which value to communicate to the chiller UCM to request heating or cooling. (This property feeds the "Heat/Cool Mode: Tracer" property.)0 = Cooling, 1 = Heating

Heat/Cool Mode: Tracer

Binary

This is the value communicated by the system to the chiller UCM and used to request the heat or cool mode.0 = Cooling, 1 = HeatingDefault: Cooling

Hot Water Setpoint: Ref

Referencer

This is the value used by the BCU to determine which value to communicate to the chiller UCM as the hot water setpoint. (This property feeds the "Hot Water Setpoint: Tracer" property.)Range: 68.0 to 140.0 °F (20.0 to 60.0 °C)

Hot Water Setpoint: Tracer

Numeric

This is the value communicated by the system to the chiller UCM and used as the leaving hot water temperature setpoint. (This setpoint is the primary control value for the chiller in the heat mode.)Range: 68.0 to 140.0 °F (20.0 to 60.0 °C)Default: 113.0 °F (45.0 °C)

Last Control Date Time

Date/Time Numeric

This is the date and time recorded at the last control of the present value. Its value is updated when an attempt to control occurs and 1] a priority change occurs (up or down), OR 2] a change in the commandable property value occurs (e.g., OCCUPIED to UNOCCUPIED), OR, 3] a change in the priority owner occurs and the priority level stays the same.

Low Noise Control: Ref

Referencer

This is the value used by the BCU to determine which value to communicate to the chiller UCM to request normal or low noise control. (This property feeds the "Low Noise Control: Tracer" property.)0 = Normal, 1 = Low

Low Noise Control: Tracer

Binary

This is the value communicated by the system to the chiller UCM and used to select normal or low noise control.0 = Normal, 1 = LowDefault: Normal

Minimum Off Time

Numeric

This is the minimum off time assigned to the UCM. This value serves to protect the hardware from cycle times that might harm it. Range: 0 to 120 minutes

Minimum On Time

Numeric

This is the minimum on time assigned to the UCM. This value serves to protect the hardware from cycle times that might harm it.

Range: 0 to 120 minutes

 

 

Minimum Time Remaining

Numeric

This is the minimum time remaining (if any) of a minimum On/Off time control action for the UCM. Range: 0 to 120 minutes

Mode: Heat/Cool

Binary

This is the heat / cool mode of the chiller. 0 = Cooling, 1 = Heating

Object Identifier

Object ID

This property uniquely identifies a particular object.

Object Name

Character

This property allows the assignment of a unique printable name to the object for user identification.

Object Type

Object Type

This is the object’s type (i.e., analog input, binary input, TCM, PCM, etc.).

Operating Capacity

Numeric

This is the current operating capacity of the chiller.Range: 0 to 100 %

Outdoor Air Temperature: Input

Numeric

This is the value of the outdoor air temperature input from the chiller.Range: -31.0 to 177.8 °F (-35.0 to 81.0 °C)

Present Value

Multi-State

This is used to control the chiller to one of nine standard operation modes. These modes are defined as Unoccupied, Optimal Start, Occupied, Optimal Stop, Demand Limit, Duty Cycle, Priority Shutdown, Night Economize, and Night Heat Cool. A translation (within the BCU) takes place to map these modes into a simpler mode set.

Unit Control Source

Binary

This is the control source of the chiller.0 = Local, 1 = Tracer

Unit Control Source: Setup

Binary

This is the value used by the BCU to determine which value to communicate to the chiller UCM to request local or Tracer chiller control. (This property feeds the "Unit Control Source: Tracer" property.)0 = Local, 1 = Tracer

Unit Control Source: Tracer

Binary

This is the value communicated by the system to the chiller UCM and used to select Local or Tracer control. This property must be set to ‘Tracer’ for Tracer Summit control; otherwise, the chiller will be under local control.0 = Local, 1 = Tracer Default: Tracer

Unit Stop: External Input

Binary

This is whether the chiller has been placed in the stop mode by an external input.0 = Stop, 1 = Auto

Unit Stop: ICS

Binary

This is whether Tracer has placed the chiller in the stop mode.0 = Stop, 1 = Auto

Unit Stop: Low Ambient

Binary

This is whether the chiller has been placed in the stop mode by a low ambient condition.0 = Stop, 1 = Auto

Unit Stop: Menu

Binary

This is whether the chiller has been placed in the stop mode by the menu. The chiller will be placed in the stop mode when both refrigerant circuits are disabled.0 = Stop, 1 = Auto

Unit Stop: Operator

Binary

This is whether the chiller has been placed in the stop mode by an operator. The chiller will be placed in the stop mode when "0" is selected on the SMM front panel or Auto when "1" is selected on the SMM front panel.0 = Stop, 1 = Auto

Update Tag

Numeric

Its purpose is to keep the PC Workstation and BCU copies of the object instance in synchronization.