Property | Type | Description | ||||||||||||||||||
Active Circuit[1-8] |
Enumerated |
This is the status of the condenser circuits reported by the controller. This indicates if each stage 1-8 is present or not, and if it is on or off: |
||||||||||||||||||
Air Flow Override: Tracer |
Multi-State |
Used to communicate override commands for air valve. In Tracer Summit version 15 and newer, this property can not be read (you’ll see ‘???’ displayed) because it only initiates an air flow override. |
||||||||||||||||||
Air Flow Stpnt: Active Min |
Float |
This property represents the active minimum flow setpoint read from the VAV. This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. |
||||||||||||||||||
Air Flow Stpnt: Active Min Source |
Enumerated |
This property indicates which minimum is enforcing the "Air Flow Stpnt: Active Min" property. This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. |
||||||||||||||||||
Air Flow Stpnt: Min Local Heat |
Float |
Defines the minimum flow through the VAV that is necessary to safely operate the reheat capability of a VAV with reheat. This value must be less than or equal to the "Heating Maximum Flow" property. |
||||||||||||||||||
Air Flow Stpnt: Min Standby Heat |
Float |
Defines the minimum flow setpoint while in the occupied standby heating mode. This value must be less than or equal to the "Heating Maximum Flow" property. |
||||||||||||||||||
Air Flow Stpnt: Tracer |
Float |
This is the measured supply airflow, typically provided by a flow sensor. |
||||||||||||||||||
Air Valve Position |
Float |
This property represents the cool output valve position (if valid) or the primary heat output valve position (if valid) of the VAV. |
||||||||||||||||||
Air Valve Drive Closed: Ref |
Property Reference |
This property only applies to sites that use a v14.XXX BCU image or older. |
||||||||||||||||||
Air Valve Drive Max: Ref |
Property Reference |
This property only applies to sites that use a v14.XXX BCU image or older. |
||||||||||||||||||
Air Valve Drive Min: Ref |
Property Reference |
This property only applies to sites that use a v14.XXX BCU image or older. |
||||||||||||||||||
Air Valve Drive Open: Ref |
Property Reference |
This property only applies to sites that use a v14.XXX BCU image or older. |
||||||||||||||||||
Airflow: Active |
Numeric |
This property indicates the active airflow, if the UCM has a local or communicated airflow value. |
||||||||||||||||||
Alarm Event Class |
Numeric |
This arrayed property specifies the event classes to which Informational Message and Service Required alarm messages are routed. The event class has a set of receivers as determined in Site Configuration that will receive the alarm messages. |
||||||||||||||||||
Alarm Level |
Enumerated |
Indicates the severity of the diagnostic shown in the "Diagnostic Alarm Status" property. |
||||||||||||||||||
Alarm Present |
Binary |
This indicates that the unit has a diagnostic |
||||||||||||||||||
Alarm Reset |
Binary |
Used to directly set nviRequest, enumeration 10 (clear alarm). The alarm state of the object is cleared, but the state of the object itself may remain unchanged. Persistent alarms will be reported, as they are re-detected. |
||||||||||||||||||
Alarms Locked |
Binary |
The value of this property is TRUE when clearing alarms remotely is not supported by the UCM. |
||||||||||||||||||
Application Mode: Tracer |
Multi-State |
Used to communicate the application mode of the unit. |
||||||||||||||||||
Autocommissioning Cmd: Tracer |
Enumerated |
This property is used by the BCU to command the VAV to execute its autocommissioning sequence. Full use of this function requires the presence of an auxiliary temperature sensor in the discharge air stream (without it the fan and reheat operation cannot be tested). This property can not be read (you’ll see ‘???’ displayed) because it only initiates the autocommissioning command. This property applies only to a Trane VAV box. |
||||||||||||||||||
Autocommissioning Air Valve Pos[1-2] |
Float |
This property is used to report the air valve positions measured during the last autocommissioning sequence. The VAV keeps the results until another autocommissioning sequence is run. This property applies only to Trane VAV boxes. |
||||||||||||||||||
Autocommissioning Disch Air Temp[1-7] |
Float |
This property is used to report the discharge air temperatures measured during the last autocommissioning sequence. The VAV keeps the results until another autocommissioning sequence is run. This property applies only to Trane VAV boxes. |
||||||||||||||||||
Autocommissioning State |
Enumerated |
This property is used to indicate the status of an auto commission sequence. This property applies only to a Trane VAV box. |
||||||||||||||||||
Autocommissioning Time Stamp |
Date/Time Numeric |
This property is used to report the date and time of the last autocommissioning sequence. The VAV stores the results until another autocommissioning sequence is run. This property applies only to Trane VAV boxes. |
||||||||||||||||||
Auxiliary Heat Control: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Auxiliary Heat Enable Input. |
||||||||||||||||||
Auxiliary Heat Control: Tracer |
Binary |
Used to enable/disable all stages of auxiliary heat in the controller. |
||||||||||||||||||
Cabinet Style |
Multi-State |
Defines the cabinet style based on the Unit Type. |
||||||||||||||||||
Cluster Member Role |
Multi-State |
Indicates the current cluster configuration of a Trane controller. |
||||||||||||||||||
Comm5 Communication State |
Numeric |
Obsolete name as of v16SP2. Refer to LonTalk Communication State property for a description. |
||||||||||||||||||
Comm5 Device NID |
Bytestring |
Obsolete name as of v16SP2. Refer to LonTalk Device NID property for a description. |
||||||||||||||||||
Comm5 DSN |
Unsignedlongword |
Obsolete name as of v16SP2. Refer to LonTalk DSN property for a description. |
||||||||||||||||||
Comm5 Program ID |
Numeric |
Obsolete name as of v16SP2. Refer to LonTalk Program ID property for a description. |
||||||||||||||||||
Communication Channel |
Numeric |
This property provides access to the assigned communications channel value of the UCM being represented. |
||||||||||||||||||
Compressor Control: Loop Control |
Binary |
Used to propagate an immediate and latched compressor disable to the controller. If its' value is "disable," this sets Compressor Control: Tracer and the VM-based value to disable. Auto only causes the VM-based value to be set to auto. (The BCU will evaluate the VM-based value along with other factors to set the Compressor Control: Tracer to auto.) |
||||||||||||||||||
Compressor Control: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Compressor Enable Input. |
||||||||||||||||||
Compressor Control: Tracer |
Binary |
Used to communicate the compressor enable input to the controller. |
||||||||||||||||||
Condenser Capacity: Active |
Numeric |
Indicates the active condenser capacity. Valid range: 0% = Off, 100% = Full |
||||||||||||||||||
Condenser Type |
Enumerated |
Condenser type. Valid range: |
||||||||||||||||||
Condenser Water Flow Status |
Boolean |
The local or communicated condenser water flow. |
||||||||||||||||||
Condenser Water Pump Output |
Boolean |
The hardwired condenser water pump status. |
||||||||||||||||||
Condenser Water Temp: Active |
Numeric |
Indicates the active condenser water temperature. In an Intellipak RTU, this is the condenser sump water temperature. In an Intellipak CSC this is the entering water condenser temperature. |
||||||||||||||||||
Condenser Water Temp Entering |
Float |
The local temperature of the water entering the condenser. |
||||||||||||||||||
Condenser Water Temp Leaving |
Float |
The local temperature of the water leaving the condenser. |
||||||||||||||||||
Condenser Water Temp: Local |
Numeric |
Indicates the unit’s hardwired condenser water temperature. |
||||||||||||||||||
Configuration: Unit Type Profile |
Multi-State |
Defines the type of unit. This property is used by all devices that meet the SCC Profile. |
||||||||||||||||||
Configuration: Unit Type Trane |
Multi-State |
Defines the type of unit. This property is used for Trane products only. |
||||||||||||||||||
Control Event Class |
Numeric |
This property determines where control messages are routed when the object’s present value is controlled. |
||||||||||||||||||
Cool Output |
Numeric |
Status of the unit's cool capacity (if hydronic) report valve position of cool valve). |
||||||||||||||||||
Cool Setpoint High Limit |
Numeric |
The local or communicated occupied cooling setpoint high limit. If both exist, the communicated value has priority. |
||||||||||||||||||
Cool Setpoint Occupied |
Numeric |
This property defines the occupied cooling setpoint. |
||||||||||||||||||
Cool Setpoint Occupied Standby |
Numeric |
This property defines the occupied standby cooling setpoint. |
||||||||||||||||||
Cool Setpoint Unoccupied |
Numeric |
This property defines the unoccupied cooling setpoint. |
||||||||||||||||||
Cool Stage Status[1-8] |
Multi-State |
Indicates if cool stage 1-8 is present or not, and if it is on or off. |
||||||||||||||||||
Cool Type |
Multi-State |
Defines the cool type of the unit. |
||||||||||||||||||
Cooling Setpoint Low Limit |
Numeric |
The local or communicated occupied cooling setpoint low limit If both exist, the communicated value has priority. |
||||||||||||||||||
Cooling Setpoint Shift: Ref |
Property Reference |
This property indicates the value to be used by the BCU to shift the occupied and occupied standby cooling setpoints. |
||||||||||||||||||
Cooling Setpoint Shift: Tracer |
Numeric |
Used to shift the occupied and occupied standby cooling setpoints. Unoccupied cooling setpoints are not shifted. |
||||||||||||||||||
Critical Application Alarming |
Binary |
This property changes a select group of priority 2 alarms (service request) to priority 3 alarms (critical). This pre-defined group of alarms may vary for each UCM. |
||||||||||||||||||
Default Cooling Fan Cycling |
Binary |
Defines the default fan cycling operation of the unit in cooling modes. |
||||||||||||||||||
Default Cooling Fan Speed |
Multi-State |
Defines the default fan speed operation of the unit in cooling modes. |
||||||||||||||||||
Default Heating Fan Cycling |
Binary |
Defines the default fan cycling operation of the unit in heating modes. |
||||||||||||||||||
Default Heating Fan Speed |
Multi-State |
Defines the default fan speed operation of the unit in heating modes. |
||||||||||||||||||
Defrost Status |
Enumerated |
This property is used to report when the unit is in defrost mode. |
||||||||||||||||||
Dehumidification Control Status |
Multi-State |
Indicates if dehumidification (for 1 state only – the 1st stage) is present or not present, and if it is on or off. Valid Range: |
||||||||||||||||||
Dehumidification Control: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate to the UCM to enable the dehumidification function. |
||||||||||||||||||
Dehumidification Control: Tracer |
Multi-State |
Building control property used to communicate the enable/disable dehumidification function to the controller. Valid Range: Enable, Disable, Not Used (0xFF = Enable) |
||||||||||||||||||
Dehumidification Level |
Numeric |
Indicates the current level of dehumidification control. Valid Range: 0-100% |
||||||||||||||||||
Device Major Revision |
UnsignedByte |
This defines the major revision number for the device. The major revision of the device is updated whenever the network interface of the device changes |
||||||||||||||||||
Device Minor Revision |
UnsignedByte |
This defines the minor revision number for the device. The minor revision of the device is updated whenever the software is changed for any reason. |
||||||||||||||||||
Diagnostic Alarm Status |
Text String |
Communicates the diagnostic of the controller as it occurs. The severity of the diagnostic is indicated in the "Alarm Level" property. |
||||||||||||||||||
Discharge Air Reheat Setpoint: Active |
Numeric |
Indicates the active discharge air temp reheat setpoint in the controller. |
||||||||||||||||||
Discharge Air Reheat Setpoint: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which discharge air temp reheat setpoint value to communicate to the UCM. |
||||||||||||||||||
Discharge Air Reheat Setpoint: Tracer |
Numeric |
Used to communicate the discharge air temp reheat setpoint in the controller. Valid Range: 48.0 to 120.0° F (8.89 to 48.89° C) |
||||||||||||||||||
Discharge Air Temp |
Numeric |
Status of the hardwired sensor on the unit. |
||||||||||||||||||
Display Active Setpoint |
Binary |
Allows the active space temperature setpoint in the UCM to be displayed at the zone sensor. This property only applies to Trane controllers (e.g., the ZN523). |
||||||||||||||||||
Display Active Space Temp |
Binary |
Allows the active space temperature in the UCM to be displayed at the zone sensor. This property only applies to Trane controllers (e.g., the ZN523). |
||||||||||||||||||
Economizer Control: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Economizer Enable Input. |
||||||||||||||||||
Economizer Control: Tracer |
Multi-State |
This property indicates the value that will be communicated by the system to the UCM and used enable and disable the economizer control. |
||||||||||||||||||
Economizer Damper Position |
Numeric |
Status of unit’s economizer damper position. (Not used if unit has 2-position OA damper) |
||||||||||||||||||
Economizer Enable: Active |
Multi-State |
This property reports whether it is even possible for the unit to economize, if one is present. (See ‘Economizer Status’ property for its on/off status when present). |
||||||||||||||||||
Economizer Min Position: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Economizer Minimum Position Input. |
||||||||||||||||||
Economizer Min Position: Tracer |
Numeric |
This property indicates the value that will be communicated by the system to the UCM and used as the minimum position of the outdoor air damper. |
||||||||||||||||||
Economizer Minimum Position Occupied |
Numeric |
Indicates the outdoor air damper occupied minimum position: |
||||||||||||||||||
Economizer Minimum Position Occupied Standby |
Numeric |
Indicates the outdoor air damper occupied standby minimum position. |
||||||||||||||||||
Economizer Status |
Multi-State |
Used to display the status of the economizer, if present. The state of this property is dependent upon the state of the ‘Economizer Enable: Active’ property. |
||||||||||||||||||
Economizer/Ventilation Type |
Multi-State |
Defines the economizer/ventilation type of the unit. |
||||||||||||||||||
Electric Heat Run Hours |
Numeric |
Number of electric heat run hours elapsed since the "Electric Heat Counter" has been cleared. This property only applies to Trane controllers. |
||||||||||||||||||
Emergency Override: Request |
Multi-State |
This property is used to override the UCM’s Present Value, when an emergency signal dictates the need for the following functions. |
||||||||||||||||||
Emergency Override: Tracer |
Multi-State |
Used to communicate the emergency override request to the controller. Note: If Emergency Override: Request is Normal, the communicated request will come from the Present Value. The communicated request will come from Emergency Override: Request if it is anything other than Normal 0 = Normal |
||||||||||||||||||
Energy Hold Off: Active |
Binary |
Used to report the status of the energy hold off in the controller. |
||||||||||||||||||
Energy Recovery Exhaust Air Bypass Damper Position |
Numeric |
Indicates the current Position of the Energy Recovery Exhaust Air Bypass Damper. Valid Range: 0-100%. Invalid: 0x7FFF |
||||||||||||||||||
Energy Recovery Leaving Exhaust Temperature |
Numeric |
Indicates the current temperature of the energy recovery wheel leaving exhaust air. Invalid 0x7FFF |
||||||||||||||||||
Energy Recovery Outdoor Air Bypass Damper Position |
Numeric |
Indicates the current position of the energy recovery wheel outside air bypass damper. Valid Range: 0-100%. Invalid: 0x7FFF |
||||||||||||||||||
Energy Recovery Wheel Frost Avoidance |
Multi-State |
Indicates the current status of the Energy Recovery Frost Avoidance function for monitoring. When the energy recovery wheel exhaust temperature falls below the frost avoidance setpoint, the controller initiates a frost avoidance sequence (modulates the outside air bypass damper to maintain setpoint, and/or energizes a pre-heater.) The Network Variable associated with this property uses two fields (a State field and a Value field) to display an answer. Valid Range: |
||||||||||||||||||
Energy Recovery Wheel Preheat Relay Status |
Multi-State |
Indicates the current status of the energy recovery wheel preheat relay output. Valid Range: |
||||||||||||||||||
Energy Recovery Wheel Relay Status |
Multi-State |
Indicates the current operational status of the energy recovery wheel. Valid Range: |
||||||||||||||||||
Entering Water Temperature: Active |
Numeric |
The local or communicated entering water temperature. When both exist, the communicated value has priority. |
||||||||||||||||||
Evaporator Frost Cutout Temperature |
Numeric |
Indicates the active frost avoidance setpoint. Valid Range: 25 to 35° F (-3.9 to 1.7° C) |
||||||||||||||||||
Evaporator Frost Protection Status [1-8] |
Binary |
Indicates if any of the refrigeration circuits are below the evaporator frost cutout temperature. There are up to 8 circuits. |
||||||||||||||||||
Evaporator Refrigerant Temperature[1-8] |
Numeric |
Indicates the evaporator leaving temperature in circuits 1 through 8. |
||||||||||||||||||
Exhaust Damper Position |
Numeric |
Indicates the current status of the exhaust damper. Valid Range: 0-100% Invalid = 0x7FFF |
||||||||||||||||||
Exhaust Enable Position |
Numeric |
This read-only configuration property indicates the default exhaust enable outdoor air damper position setpoint. Valid Range: 0 to 100% |
||||||||||||||||||
Exhaust Status |
Real |
This property indicates active status of the binary output controlling the exhaust fan. |
||||||||||||||||||
Exhaust/Return Type |
Multi-State |
Defines the exhaust/return type of the unit. |
||||||||||||||||||
External Interface File (XIF) |
Text |
The logical interface to a device, which contains the Program Interface. A device's external interface specifies the number and types of LonMark objects; the number, types, directions and connection attributes of network variables; and the number of message tags. The program ID field is used as the key to identify each external interface. |
||||||||||||||||||
Face And Bypass: Active |
Numeric |
Status of the unit's face and bypass damper. Range: 0 to 100% 0% = Full Bypass |
||||||||||||||||||
Fan Speed: Ref |
Numeric |
This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the fan speed. The fan being controlled may be a 1, 2, 3, or variable speed fan. This property is valid for non-VAV devices only. |
||||||||||||||||||
Fan Speed: Tracer |
Numeric |
Used to communicate the fan speed to the UCM. The fan being controlled may be a 1, 2, 3, or variable speed fan. This property is valid for non-VAV devices only. |
||||||||||||||||||
Flow Gain |
Numeric |
Indicates the air flow measurement gain. |
||||||||||||||||||
Flow Setpoint: Active |
Numeric |
This property indicates the active flow setpoint, if the UCM has a local or communicated flow setpoint value. |
||||||||||||||||||
Generic Analog Input |
Numeric |
The state of generic analog input. This property only applies to Trane controllers. |
||||||||||||||||||
Generic Binary Input |
Multi-State |
The state of generic binary input 1. |
||||||||||||||||||
Generic Binary Output |
Multi-State |
The state of generic binary output 1. |
||||||||||||||||||
Generic Binary Output: Tracer |
Binary |
Used to control the generic binary output (when present). |
||||||||||||||||||
Generic Temperature |
Numeric |
Status of the local generic temperature input. |
||||||||||||||||||
Heat Output |
Numeric |
Status of the unit’s primary heat capacity (if hydronic, reports valve position of primary heat valve). |
||||||||||||||||||
Heat Output Secondary |
Numeric |
Status of the unit’s secondary heat capacity (if hydronic, report valve position of secondary heat valve). |
||||||||||||||||||
Heat Setpoint High Limit |
Numeric |
The local or communicated occupied heating setpoint high limit If both exist, the communicated value has priority |
||||||||||||||||||
Heat Setpoint Low Limit |
Numeric |
The local or communicated occupied heating setpoint low limit If both exist, the communicated value has priority |
||||||||||||||||||
Heat Setpoint Occupied |
Numeric |
This property defines the occupied heating setpoint. |
||||||||||||||||||
Heat Setpoint Occupied Standby |
Numeric |
This property defines the occupied standby heating setpoint. |
||||||||||||||||||
Heat Setpoint Unoccupied |
Numeric |
This property defines the unoccupied heating setpoint. |
||||||||||||||||||
Heat Stage Status[1-8] |
Multi-State |
Indicates if heat stage 1-8 is present or not, and if it is on or off. |
||||||||||||||||||
Heat/Cool Mode: Active |
Binary |
Used to display the current heat/cool mode of the SCC UCM. This is an interpretation made by the BCU based on the value shown for the ‘Mode: Heat/Cool’ property |
||||||||||||||||||
Heat/Cool Mode: Ref
|
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the heat/cool mode. |
||||||||||||||||||
Heating Maximum Flow |
Numeric |
Indicates the heating maximum air flow. |
||||||||||||||||||
Heating Minimum Flow |
Numeric |
Indicates the heating minimum air flow. |
||||||||||||||||||
Heating Setpoint Shift: Ref |
Property Reference |
This property indicates the value to be used by the BCU to shift the occupied and occupied standby heating setpoints. Unoccupied heating setpoints are not shifted. |
||||||||||||||||||
Heating Setpoint Shift: Tracer |
Numeric |
Used to shift the occupied and occupied standby heating setpoints. Unoccupied heating setpoints are not shifted. |
||||||||||||||||||
Humidification Control: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate to the UCM to enable the humidification function. |
||||||||||||||||||
Humidification Control: Tracer |
Multi-State |
Building control property used to communicate the enable/disable humidification function to the controller. Valid Range: Enable, Disable, Not Used (0xFF = Enable) |
||||||||||||||||||
Humidifier: Active |
Numeric |
Status of unit’s humidifier output. |
||||||||||||||||||
Language Identifier |
Multi-State |
Defines which language is currently being used. It defines for the UCM what language to present alarm messages in. |
||||||||||||||||||
Last Control Date Time |
Date/Time Numeric |
This indicates the date and time when the present value property of this object was last controlled. The date and time value is stored and manipulated in the BCU's standard date/time format, which is a value of seconds past midnight of January 1st, 1980. |
||||||||||||||||||
Leaving Water Temperature: Active |
Numeric |
The local leaving water temperature. |
||||||||||||||||||
Light 1 Command: Local |
Binary |
Reports how light circuit #1 is being commanded from the zone sensor. This property only applies to Trane controllers (e.g., the ZN523). |
||||||||||||||||||
Light 1 Command: Tracer |
Binary |
Used to communicate override commands to light circuit #1. This property can not be read, it only controls an override for light #1. This property only applies to Trane controllers (e.g., the ZN523) |
||||||||||||||||||
Light 1 Status |
Binary |
Reports the status of light circuit #1. This property only applies to Trane controllers (e.g., the ZN523). |
||||||||||||||||||
Light 2 Command: Local |
Binary |
Reports how light circuit #2 is being commanded from the zone sensor. This property only applies to Trane controllers (e.g., the ZN523). |
||||||||||||||||||
Light 2 Command: Tracer |
Binary |
Used to communicate override commands to light circuit #2. This property can not be read, it only controls an override for light #2. This property only applies to Trane controllers (e.g., the ZN523) |
||||||||||||||||||
Light 2 Status |
Binary |
Reports the status of light circuit #2. This property only applies to Trane controllers (e.g., the ZN523). |
||||||||||||||||||
Load: Absolute |
Numeric |
Used by heat pumps to indicate the current energy consumed by the unit. |
||||||||||||||||||
Load: Terminal |
Numeric |
Used by Heat Pumps to indicate the current heat/cool energy demand of the unit. |
||||||||||||||||||
Location Label |
Text String |
Used to provide descriptive location information. |
||||||||||||||||||
LonTalk Communication State |
Numeric |
This property indicates the status of communications between the BCU and the SCC. |
||||||||||||||||||
LonTalk Device NID |
Bytestring |
The Neuron ID (NID) of the UCM. This is a unique, 12 digit, non-adjustable serial number found on every Neuron chip. |
||||||||||||||||||
LonTalk DSN |
Unsignedlongword |
A comma-separated value representing the domain, subnet, and node ID (DSN) of the UCM. |
||||||||||||||||||
LonTalk Program ID |
Numeric |
An identifier stored in the device (in the Neuron Chip's EEPROM) that identifies the application program running on the node. All nodes with the same program ID must have the same external interface. |
||||||||||||||||||
Maintenance Requested |
Multi-State |
This property is used to report whether a service ping has been received by the UCM (e.g a zone sensor initiated a service ping on a ZN523). This property only applies to Trane controllers. |
||||||||||||||||||
Manual Control |
Binary |
If the UCM supports this property this will indicate if the source of the control parameters used by the device is local (manual). |
||||||||||||||||||
Maximum Flow |
Numeric |
Indicates the maximum air flow. |
||||||||||||||||||
Minimum Flow |
Numeric |
Indicates the minimum air flow. |
||||||||||||||||||
Minimum Off Time |
Numeric |
This property provides access to the minimum off time assigned to the UCM being represented. This value serves to protect the hardware from cycle times that might harm the hardware. |
||||||||||||||||||
Minimum On Time |
Numeric |
This property provides access to the minimum on time assigned to the UCM being represented. This value serves to protect the hardware from cycle times that might harm the hardware. |
||||||||||||||||||
Minimum Send Time |
Numeric |
This defines the minimum period of time between automatic network variable output transmissions. Although this configuration property is optional, it must be provided if the minimum send time function is used in the controller. Setting this property to 0.0 disables the Minimum Send Time mechanism. |
||||||||||||||||||
Minimum Time Remaining |
Numeric |
This property provides access to the minimum time remaining (if any) of a minimum On/Off time control action for the represented UCM device. PUTS are also allowed so that an operator can intervene on a Minimum On/Off control action that is in progress. |
||||||||||||||||||
Mixed Air Temperature |
NUMERIC |
Controller property that displays the unit’s current mixed air temperature. |
||||||||||||||||||
Mode: Active |
Multi-State |
Actual mode of the unit. |
||||||||||||||||||
Mode: Heat/Cool |
Multi-State |
Actual heat/cool mode of the unit. |
||||||||||||||||||
Mode: Occupancy |
Multi-State |
The local or communicated occupancy status When both exist, the communicated value. has priority |
||||||||||||||||||
Node Self Doc |
Text String |
This property displays the unit's type of UCM (i.e., ZN510, MP580, VV550, etc.). |
||||||||||||||||||
Node State |
Multi-State |
The current operating condition of the Neuron Microprocessor. Possible conditions are: |
||||||||||||||||||
Nominal Flow |
Numeric |
Indicates the nominal air flow. |
||||||||||||||||||
Object Identifier |
Object ID |
This property allows the assignment of a unique printable name to the object for user identification. It is provided primarily to allow the embedding of the object ID in the returned data buffer. |
||||||||||||||||||
Object Name |
Text String |
This property allows the assignment of a unique printable name to the object for user identification. |
||||||||||||||||||
Object Type |
Multi-State |
This property Designates the object’s type (i.e., analog input, binary input, TCM, PCM, etc). |
||||||||||||||||||
Occupancy: Active |
Binary |
Used to display the current occupancy of the SCC UCM, based on the multi-state values of the ‘Mode: Occupancy’ property (nvoEffectOccup from the UCM). |
||||||||||||||||||
Occupancy: Tracer |
Enumerated |
This property indicates the value that is communicated by the system to the UCM and used to determine occupancy. |
||||||||||||||||||
Occupant Call: Local |
Multi-State |
This property is used to report whether an occupant call has been received at the UCM (e.g. a ZN523) from a zone sensor. This property only applies to Trane controllers. |
||||||||||||||||||
Occupied Bypass Time |
Numeric |
Defines the maximum amount of time that the unit can be in Bypass (occupancy) mode from a single Bypass request from a local (hardwired) switch. This property only applies to a local input, if present. |
||||||||||||||||||
Occupied Bypass: Active
|
Binary |
Used to display the current occupied status of the SCC UCM, based on the multi-state values of the 'Mode: Occupancy' property (nvoEffectOccup from the UCM). |
||||||||||||||||||
Outdoor Air Cooling Lockout: Local |
Numeric |
This read-only configuration property indicates the cooling lockout point below which mechanical cooling is disabled. Typical Range: 14.00 to 68.00° F (-10.00 to 20.00° C) |
||||||||||||||||||
Outdoor Air Damper Position |
Numeric |
This property indicates the active position of the outdoor air damper (if the unit is configured for one). If the outdoor air damper is a modulating air damper, the valid range is between 0 and 100%. If it is a 2-position outdoor air damper, the value that appears will be either 0 or 100% (closed or open). |
||||||||||||||||||
Outdoor Air Enthalpy |
Numeric |
The local or communicated outdoor air enthalpy. When both exist, the communicated value has priority. |
||||||||||||||||||
Outdoor Air Enthalpy Setpoint: Local |
Numeric |
This read-only configuration property indicates the point at which outdoor air enthalpy is appropriate for economizing. Typical Range: 10.0 to 99.9 BTU/lb (23.26 to 232.37 KJoules/Kg) |
||||||||||||||||||
Outdoor Air Humidity: Input |
Numeric |
This property indicates the outdoor air relative humidity in a percentage, if the UCM has a locally wired humidity sensor. Range: 0% to 100% |
||||||||||||||||||
Outdoor Air Humidity: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Outdoor Air Humidity Input. |
||||||||||||||||||
Outdoor Air Humidity: Tracer |
Numeric |
Used to communicate outdoor air humidity to the controller. Communicated value used over local value when both are present. |
||||||||||||||||||
Outdoor Air Min Flow Setpoint: Local |
Numeric |
This read-only configuration property indicates the unit's default outdoor air min flow setpoint. Range: 0 to 137727 cfm (0 to 65,000 I/sec.) |
||||||||||||||||||
Outdoor Air Temperature Setpoint: Local |
Numeric |
Defines the outside air temperature at which the device is allowed to economize. This is the absolute temperature, not a differential temp or enthalpy value. |
||||||||||||||||||
Outdoor Air Temperature: Active |
Float |
The local or communicated outdoor air temperature. When both exist, the communicated value has priority. |
||||||||||||||||||
Outdoor Air Temperature: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the Outdoor Air Temperature. |
||||||||||||||||||
Outdoor Air Temperature: Tracer |
Numeric |
This property indicates the value that is communicated by the system to the UCM and used as the Outdoor Air Temperature. |
||||||||||||||||||
Preheat Type |
Multi-State |
Defines the preheat type of the unit. |
||||||||||||||||||
Present Value |
Op Mode |
This property is used to control the unit to one of nine standard operation modes. These modes are defined as UNOCCUPIED, OPTIMAL START, OCCUPIED, OPTIMAL STOP, DEMAND LIMIT, DUTY CYCLE, PRIORITY SHUTDOWN, NIGHT ECONOMIZE, and NIGHT HEAT-COOL. A translation (within the BCU) may take place to map these modes into a simpler mode set. |
||||||||||||||||||
Reheat Type |
Multi-State |
Defines the reheat type of the unit. |
||||||||||||||||||
Release Overrides: |
Multi-State |
Used to release one or more overrides. This property can not be read, it only controls an override for clearing the zone sensor requests. This property only applies to Trane controllers (e.g., the ZN523). |
||||||||||||||||||
Reset Electric Run Hours |
Binary |
Used to reset the electric heat |
||||||||||||||||||
Reset Maintenance Timer |
Binary |
Used to reset the maintenance timer in the SCC UCM. |
||||||||||||||||||
Return Air Temperature |
Numeric |
The return air temperature. |
||||||||||||||||||
Return Fan Pressure: Active |
Numeric |
Indicates the effective return fan pressure. |
||||||||||||||||||
Return Fan Pressure Setpoint: Local |
Numeric |
Controller property that defines the default return fan pressure setpoint. Typical Range: -0.10 to 0.40 I.W.C. (-25 to 100 Pa). |
||||||||||||||||||
Return Fan Status |
Numeric |
Indicates the status of the unit's return fan output. |
||||||||||||||||||
Reversing Valve |
Binary |
This property indicates the active status of the reversing valve (applies to Water Source Heat Pumps only). |
||||||||||||||||||
Saturated Condenser Temperature |
Float |
The active condenser temperature reported from the UCM. |
||||||||||||||||||
Setpoint Offset: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Setpoint Offset. |
||||||||||||||||||
Setpoint Offset: Tracer |
Numeric |
Used to shift the occupied and standby temperature setpoint. All setpoints will be shifted up or down by this value. |
||||||||||||||||||
Source Temperature: Ref (Formerly called ‘Entering Water Temperature: Ref’)
|
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Entering Water Temperature Input for a non-VAV controller or as the Supply Air Temperature Input for a VAV controller. Valid Range: 32.00 to 212.00 deg. F (0.00 to 100.00 deg. C). |
||||||||||||||||||
Source Temperature: Tracer (Formerly called ‘Entering Water Temperature: Tracer’)
|
Numeric |
Used to communicate the entering water temperature to a non-VAV controller or the supply air temperature to a VAV controller. The communicated value is used over the local value when both are present. |
||||||||||||||||||
Space CO2 Concentration: Input |
Numeric |
This property indicates the space carbon dioxide (CO2) concentration in parts per million (ppm), if the UCM has a locally wired CO2 sensor. |
||||||||||||||||||
Space CO2 Concentration: Ref |
Numeric |
This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the Space CO2 reading. The communicated value will take precedence over a locally hard-wired sensor. |
||||||||||||||||||
Space CO2 Concentration: Tracer |
Numeric |
If used, this is the value that will be communicated down to the UCM and used as its Space CO2 reading. The communicated value will take precedence over a locally hard-wired sensor. |
||||||||||||||||||
Space CO2 Limit |
Numeric |
This defines a high limit CO2 setpoint for the controlled space. |
||||||||||||||||||
Space CO2 Low Limit |
Numeric |
This defines a high limit CO2 setpoint for the controlled space. |
||||||||||||||||||
Space Dehumidification Setpoint: Active |
Numeric |
Indicates the effective space high humidity limit setpoint communicated from the controller. |
||||||||||||||||||
Space Dehumidification Setpoint: Local |
Numeric |
This defines a high limit humidity setpoint for the controlled space. |
||||||||||||||||||
Space Enthalpy |
Numeric |
Indicates the effective space enthalpy, |
||||||||||||||||||
Space Humidification Setpoint: Active |
Numeric |
Indicates the active space low humidity limit setpoint. |
||||||||||||||||||
Space Humidification Setpoint: Local |
Numeric |
This configuration property indicates the default minimum humidity level for the controlled space. Valid Range: 0 - 100% |
||||||||||||||||||
Space Humidity: Input |
Numeric |
This property indicates the space relative humidity in a percentage, if the UCM has a locally wired humidity sensor. |
||||||||||||||||||
Space Humidity: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which space humidity value to communicate to the UCM. |
||||||||||||||||||
Space Humidity: Tracer |
Numeric |
Building control property used to communicate the space relative humidity. Valid Range: 0-100%, Invalid: 0x7FFF |
||||||||||||||||||
Space Pressure: Active |
Float |
The local or communicated effective space pressure. When both exist, the communicated value has priority. |
||||||||||||||||||
Space Pressure Setpoint: Tracer |
Numeric |
Building control property that is used to communicate the space pressure setpoint to the controller. Valid Range: -1.00 to 1.00 I.W.C. (-250 to 250 Pa). 32,767 = Invalid or Property Not Supported. |
||||||||||||||||||
Space Setpoint User |
Numeric |
This is a graphical setpoint field that applies during the occupied and occupied standby mode. It is the space setpoint that the user intends to send down to the UCM as the active setpoint. An algorithm uses the heat/cool mode and occupancy mode of the UCM to determine the necessary ‘Space Temperature Setpoint: Ref’ value that will equate the users entered value to the ‘Space Temperature Setpoint: Active’ property in the UCM. The algorithm is based on the asymmetrical method for determining the active setpoint relative to the communicated space setpoint value. The valid range entered in this field will vary depending on the default heating/cooling setpoints, setpoint offset, and setpoint shift parameters, but is such that it will not cause the ‘Space Temperature Setpoint: Ref’ value to go out of range. |
||||||||||||||||||
Space Temperature: Active |
Numeric |
The local or communicated effective space temperature. When both exist, the communicated value has priority. If neither exist, the unit uses its stored default. |
||||||||||||||||||
Space Temperature: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Space Temperature. |
||||||||||||||||||
Space Temperature: Tracer |
Numeric |
Used to communicate a space temperature to the controller. Communicated value used over local value when both are present. |
||||||||||||||||||
Space Temperature Setpoint Control: Local |
Binary |
Defines whether the local hardwired setpoint input is enabled or disabled. |
||||||||||||||||||
Space Temperature Setpoint: Active |
Numeric |
The local or communicated effective space temperature setpoint. When both exist, the communicated value has priority. If neither exists, the unit uses its stored default value. |
||||||||||||||||||
Space Temperature Setpoint: Local |
Numeric |
Reflects the local setpoint input. |
||||||||||||||||||
Space Temperature Setpoint: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Space Temperature Setpoint. |
||||||||||||||||||
Space Temperature Setpoint: Tracer |
Numeric |
Used to communicate a space temperature setpoint to the controller. Communicated value used over local value when both are present. |
||||||||||||||||||
Standby Minimum Flow |
Numeric |
Indicates the standby minimum air flow. |
||||||||||||||||||
Startup Setpoint |
Numeric |
This property defines the threshold for warm-up or pre-cool at start-up. |
||||||||||||||||||
Startup Time Delay |
Unsigned Word |
Represents the amount of time the controller waits (after power-up) before invoking the normal control algorithm operation. |
||||||||||||||||||
Sunblind 1 Command: Local |
Binary |
Reports how sunblind circuit #1 is being commanded from the zone sensor. This property only applies to Trane controllers (e.g. the ZN523). |
||||||||||||||||||
Sunblind 1 Command: Tracer |
Binary |
Used to communicate override commands to sunblind circuit #1. This property can not be read, it only controls an override for sunblind #1. This property only applies to Trane controllers (e.g., the ZN523). |
||||||||||||||||||
Sunblind 1 Status |
Binary |
Reports the status of sunblind circuit #1. This property only applies to Trane controllers (e.g., the ZN523). |
||||||||||||||||||
Sunblind 2 Command: Local |
Binary |
Reports how sunblind circuit #2 is being commanded from the zone sensor. This property only applies to Trane controllers (e.g. the ZN523). |
||||||||||||||||||
Sunblind 2 Command: Tracer |
Binary |
Used to communicate override commands to sunblind circuit #2. This property can not be read, it only controls an override for sunblind #2. This property only applies to Trane controllers (e.g., the ZN523). |
||||||||||||||||||
Sunblind 2 Status |
Binary |
Reports the status of sunblind circuit #2. This property only applies to Trane controllers (e.g., the ZN523). |
||||||||||||||||||
Supply Fan Proving Status |
Enumerated |
Status that indicates if the supply fan is actually on, compared to the Supply Fan Status property, which may indicate only a requested state. Example of proving actual operation is by means of a current sensing relay on the wires to the fan motor. |
||||||||||||||||||
Supply Fan Run Time |
Numeric |
Number of fan run hours elapsed since the "maintenance required" diagnostic was initiated and cleared. |
||||||||||||||||||
Supply Fan Speed |
Enumerated |
Status of unit's fan output as an enumeration.
|
||||||||||||||||||
Supply Fan Status |
Numeric |
Status of unit’s fans output. |
||||||||||||||||||
Supply Fan Switch Control: Local |
Binary |
Defines whether the local hardwired setpoint input is enabled or disabled. |
||||||||||||||||||
Supply Fan Type |
Multi-State |
Defines the supply fan type of the unit |
||||||||||||||||||
Timed Override Request |
Binary |
This property indicates the active status of the Timed Override Flag, which is set, when the Timed Override button is pushed on the zone sensor. |
||||||||||||||||||
Timed Override Request: Cancel |
Binary |
This property indicates the active status of the Cancel Timed Override Flag that is set when the cancel button is pushed on the zone sensor. |
||||||||||||||||||
Update Tag |
Numeric |
This property is used as the upload/download tag. Its purpose is to keep the PC Workstation and BCU copies of the object instance in synchronization. |
||||||||||||||||||
VAV Drive Max Heat: Ref |
Property Reference |
This property indicates the value to be used by the BCU to communicate Max Heat override commands for the Application Mode. |
||||||||||||||||||
Ventilation Ratio Calc | Float | This status property is the ratio between the "Ventilation Setpoint: Active" property and the "Airflow: Active" property. This value is limited by the "Ventilation Ratio Limit: Tracer" property. This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 0 – 100% |
||||||||||||||||||
Ventilation Ratio Limit: Tracer | Float | This property is communicated to the VAV as the limit to request outdoor air in the primary air (VAV system). This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 1 – 100% |
||||||||||||||||||
Ventilation Setpoint: Active | Float | This property is the amount of outdoor air the VAV is requesting. The VAV will typically use this in determining the "Ventilation Ratio Calc" property. This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 0 – 65,534 L/s |
||||||||||||||||||
Ventilation Setpoint: Max | Float | This property is the maximum flow of outdoor air the space should ever require for ventilation purposes. This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 0 – 10,000 L/s (0 – 21,189 cfm) |
||||||||||||||||||
Ventilation Setpoint: Min | Float | This property is the minimum flow of outdoor air required to ventilate the space during periods of zero occupancy. This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 0 – 10,000 L/s (0 – 21,189 cfm) |
||||||||||||||||||
Ventilation Setpoint: Ref | Float | This property is communicated to the VAV as the ventilation setpoint (the outdoor air requirement) for the expected number of people occupying the space. This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 0 – 10,000 L/s (0 – 21,189 cfm) |
||||||||||||||||||
Ventilation Setpoint: Tracer | Float | This property is communicated to the VAV as the ventilation setpoint (the outdoor air requirement) for the expected number of people occupying the space. This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 0 – 10,000 L/s (0 – 21,189 cfm) |
||||||||||||||||||
Water Valve Drive Closed: Ref |
Property Reference |
This property only applies to sites that use a v14.XXX BCU image or older. |
||||||||||||||||||
Water Valve Drive Open: Ref |
Property Reference |
This property only applies to sites that use |
||||||||||||||||||
Water Valve Override: Tracer |
Multi-State |
Used to communicate override commands for the Water Valve(s). In Tracer Summit version 15 and newer, this property can not be read, it only initiates a water valve override. If the controller is a Trane VAV box, this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 0 = Normal 4 = Open all valves 5 = Close all valves All other values = Not Used |