Scroll Chiller (CGA/CGW)

Property Type Description

Alarm Event Class[1-3]

Numeric

This is a three element array containing entries for alarm classes Manual Reset, Auto Reset, & Informational diagnostics. Each entry contains an index into the event action table. The event action table contains both a set of instructions for alarm routing, and a stretchy list of referencer objects (the potential receivers).

Alarm Output

Binary

This property indicates the state of the alarm relay output on the CYCLONE UCM. The UCM provides an isolated SPDT output suitable for customer connection for remote alarm indication. The output is energized for all manually resettable diagnostics (MMR’s and CMR’s) when detected and deenergized when the UCM is manually reset. This remote alarm function does not apply to faults that reset automatically (MAR’s and IAR’s). 0=OFF, 1=ON

Capacity Control: External

Binary

The UCM accepts an isolated contact closure input that is suitable for customer connection to be used to inhibit compressor operation because of high ambient temperatures or to provided KW demand limiting. When open, the UCM does not operate the lag compressor for either refrigerant circuit. If both compressors on a circuit are operating when the contact transitions from closed to open, the lag compressor will stop. When closed, the UCM operates both compressors normally. When used for high ambient operation inhibit, a separate remote ambient sensing thermostat is required. Note: The capacity control function must not be used in the ice building mode. 0=NORMAL, 1=REDUCED

Capacity Control: Ref

Referencer

Feeds the "Capacity Control: Tracer" property. 0=NORMAL, 1=REDUCED

Capacity Control: Tracer

Binary

When Reduced, the UCM does not operate the lag compressor for either refrigerant circuit. If both compressors on a circuit are operating when reduced, the lag compressor will stop. When Normal, the UCM operates both compressors normally. Note: The capacity control feature must not be used in the ice building mode. 0=NORMAL, 1=REDUCED

Chilled Water Flow Status

Binary

The UCM will accept an isolated contact closure input suitable for customer connection for interlocking with a customer-installed evaporator chilled water flow switch and customer provided pump starter auxiliary contact. This input must be closed to start compressors. Loss of chilled water flow results in an automatically resettable diagnostic (MAR). Momentary (six seconds) opening of the flow switch due to turbulent water flow, etc, is allowed. 0=NO, 1=YES

Chilled Water Reset Type

Multi-State

For the following, start, gain, and max are defined by the "FP Start Reset", "FP Reset Ratio", and "FP Max Reset", respectively. When Outdoor Air Based Reset is enabled, any chilled water setpoint (local or Tracer) will be modified by the following equations:

sp = (start - oa temp) *gain + input sp,
and 0 =(sp - input sp) =max..

where: sp is the modified or active setpoint.
input sp is the commanded chilled water
setpoint. oa temp is the outdoor air temp.

When Zone Based Reset is enabled, any chilled water setpoint (local or Tracer) will be modified by the following equations:

sp = (start - zone temp) *gain + input sp,
and 0 =(sp - input sp) =max..

where: sp is the modified or active setpoint.
input sp is the commanded chilled water
setpoint. zone temp is the zone air temp.

When Return Based Reset is enabled, any chilled water setpoint (local or Tracer) will be modified by the following equations:

sp=(start-(return temp-supply temp)) *gain +
input sp, and 0 =(sp - input sp) =max..

where: sp is the modified or active setpoint.
input sp is the commanded chilled water
setpoint. return temp is the chilled water
temp: entering. supply temp is the chilled
water temp: leaving.

0=DISABLED, 1=OUTDOOR AIR BASED RESET ENABLED, 2=ZONE BASED RESET ENABLED, 3=RETURN BASED RESET

Chilled Water Setpoint: Active

Numeric

This property indicates the active value of the chilled water setpoint. This value may be limited on the low end by the leaving water temperature cutout setpoint. Valid only when not in Ice Mode (Ice Making Status=Normal). Range: 0 to 65° F

Chilled Water Setpoint: Ref

Referencer

Feeds the Chilled Water Setpoint: Tracer. Range: 0 to 65°F

Chilled Water Setpoint: Tracer

Numeric

This setpoint is the primary control value for the chiller in non-Ice Making mode. Range: 0 to 65°F

Chilled Water Temp: Entering

Numeric

The UCM continuously senses and compares entering and leaving chilled water temperatures to detect loss of chilled water flow. If the entering water temp drops below the leaving water temp by more than 2 F°, a manually resettable diagnostic is generated in 100 F° seconds. This feature is active only if one compressor, or more, is operating. Range: -40 to 142° F

Chilled Water Temp: Leaving

Numeric

Leaving refers to leaving the chiller’s evaporator. Maintaining this temperature is the primary control objective of the chiller. Range: -40 to 142° F

Chiller Enable/Disable: External

Binary

Also known as external auto/stop. The UCM accepts an isolated contact closure input suitable for customer connection to put the unit in either Auto or Stop from a remote device. This input overrides the Chiller switch on the UCM when the Chiller switch is in Auto (auto/local or auto/remote). It does not override the Chiller switch when the switch is in Stop. The input contacts are closed for external Auto operation and open to put the unit in external Stop. 0=STOP, 1=AUTO

Chiller Enable/Disable: Tracer

Binary

This property is the Tracer’s request to enable or disable the chiller. 0=STOP, 1=AUTO.

Comm Loss Mode: Request

Multi-State

This property defines what value the UCM should use for a unit disable: comm loss. Off means Stop, and when Last state is selected, the Unit Disable: Tracer value is used. 0=OFF, 1=AUTO, 2=LAST STATE.

Comm Loss Mode: Tracer

Binary

This property defines the value last communicated to the UCM before communication was lost. 0=OFF, 1=AUTO.

Communication Address

Numeric

This is the communications address of the UCM being represented.

Communication Channel

Numeric

This is the communications channel of the UCM being represented.

Communication Retry

Binary

Provides access to the communications retry indicator. This property is used to signal the control server that it needs to force control data output to the device when it is awakened for maintenance operations. The communications retry indicator is set (TRUE) when an attempt to send control data fails, and cleared (FALSE) when communications are successful.

Communication State

Binary

This property indicates the status of communications between the BCU and the UCM.  0=Down, 1=Up.

Comp Number Enabled: Tracer

Numeric

Value used to enforce mechanical cooling lockout. 0=0, 1=1, 2=2, 3=3, 4=4 COMPRESSORS ENABLED.

Comp: Number Of

Numeric

20, 25, and 30 Ton chillers have 2 compressors, 40, 50, and 60 Ton chillers have 4 compressors. 2=2 COMPRESSORS, 4=4 COMPRESSORS.

Compressor A Output

Binary

This property indicates the state of the Compressor A output relay. 0=OFF, 1=ON

Compressor A Run Time

Numeric

This property indicates the number of hours compressor A has run since the last clearing of this counter. Integer counter will clamp at 255 until reset to 0. Range: 0 to 255 hours

Compressor A Starts

Numeric

This property indicates the number of starts compressor A has had since the last clearing of this counter. Integer counter will clamp at 255 until reset to 0. Range: 0 to 255 starts

Compressor B Output

Binary

This property indicates the state of the Compressor B output relay. 0=OFF, 1=ON

Compressor B Run Time

Numeric

This property indicates the number of hours compressor B has run since the last clearing of this counter. Integer counter will clamp at 255 until reset to 0. Range: 0 to 255 hours

Compressor B Starts

Numeric

This property indicates the number of starts compressor B has had since the last clearing of this counter. Integer counter will clamp at 255 until reset to 0. Range: 0 to 255 starts

Compressor C Output

Binary

This property indicates the state of the Compressor C output relay. 0=OFF, 1=ON

Compressor C Run Time

Numeric

This property indicates the number of hours compressor C has run since the last clearing of this counter. Integer counter will clamp at 255 until reset to 0. Range: 0 to 255 hours

Compressor C Starts

Numeric

This property indicates the number of starts compressor C has had since the last clearing of this counter. Integer counter will clamp at 255 until reset to 0. Range: 0 to 255 starts

Compressor D Output

Binary

This property indicates the state of the Compressor D output relay. 0=OFF, 1=ON

Compressor D Run Time

Numeric

This property indicates the number of hours compressor D has run since the last clearing of this counter. Integer counter will clamp at 255 until reset to 0. Range: 0 to 255 hours

Compressor D Starts

Numeric

This property indicates the number of starts compressor D has had since the last clearing of this counter. Integer counter will clamp at 255 until reset to 0. Range: 0 to 255 starts

Compressor Running

Binary

The UCM provides an isolated SPDT output suitable for customer connection for remote "compressors running" indication. This output is energized when any compressor is operating (or commanded to run) and deenergized when no compressors are operating (or "no compressor operating" command is in effect). 0=ALL COMPRESSORS OFF, 1=AT LEAST ONE COMPRESSOR IS RUNNING

Cond Saturated Refrig Temp: CKT1

Numeric

This property is used for monitoring the condition of the condenser on circuit 1. Only valid with A/C condenser. Range: -40 to 158° F

Cond Saturated Refrig Temp: CKT2

Numeric

This property is used for monitoring the condition of the condenser on circuit 2. Only valid with A/C condenser and there are 4 compressors. Range: -40 to 158° F

Condenser Fan Contactor: CKT1[1-2]

Binary

This property indicates the active status of fans on the condenser on circuit 1. The 20 and 40 Ton units have 2 condenser fans controlled by the 2 outputs on circuit 1. 25, 30, 50, 60 Ton units have 3 condenser fans controlled by the 2 outputs on circuit 1. UCM condenser fan control logic is dependent on the number of compressors operating per circuit and on ambient temperature. Fan logic is not initiated until LPC closure when outdoor air temperature is below 50° F. Only valid with A/C condenser.

Condenser Fan Contactor: CKT2[1-2]

Binary

This property indicates the active status of fans on the condenser on circuit 2. The 40 Ton units have 2 condenser fans controlled by the 2 outputs on circuit 2. 50 and 60 Ton units have 3 condenser fans controlled by the 2 outputs on circuit 2. UCM condenser fan control logic is dependent on the number of compressors operating per circuit and on ambient temperature. Fan logic is not initiated until LPC closure when outdoor air temperature is below 50° F. Only valid with A/C condenser and there are 4 compressors.

Condenser Water Pump Output

Binary

The UCM provides a single isolated contract closure output suitable for customer connection to control the condenser water pump. Only valid with W/C condenser. 0=OFF, 1=ON.

Condenser Water Temp: Entering

Numeric

This property is used for monitoring the condition of the water entering the condenser. Only valid with W/C condenser. Range: -40 to 158° F.

Condenser Water Temp: Leaving

Numeric

This property is used for monitoring the condition of the water leaving the condenser. Only valid with W/C condenser. Range: -40 to 158° F integer.

Config: Communications

Binary

If communications are disabled, the CYCLONE will answer scan requests with garbage data. 0=DISABLE, 1=ENABLE

Config: External Setpoint

Binary

When Enabled, the local chilled water setpoint (0 to 65° F) is read in from a 2 to 10V analog input on the CSR module. 0=DISABLED, 1=ENABLED.

Config: Head Pressure Control

Binary

Enables the condenser temperature sensor diagnostic function. Only valid with W/C condenser. 0=DISABLED, 1=ENABLED

Config: Ice Machine Control

Binary

This feature must be Enabled for either the shorted zone temp sensor or the Tracer to put the unit into Ice Making. When the zone temp sensor is shorted, the ice termination setpoint is entered in the external setpoint input . When the Tracer puts the unit into Ice Making, the "Ice Termination Setpoint: Tracer" is used. 0=DISABLED, 1=ENABLED

Config: Reset Option

Binary

This property is a reflection of the software lock that enables the three chilled water reset functions. 0=DISABLED, 1=ENABLED

Configuration: Pumpdown

Binary

Pumpdown enabled means that before the last compressor on a circuit is turned off, a liquid line soleniod valve is closed, forcing all of the refrigerant from the evaporator to the condenser. Termination of pumpdown is via a detected low pressure cutout or 30 seconds, whichever comes first. 0=DISABLED, 1=ENABLED

Control Event Class

Numeric

This property identifies the control event class to be used for controlling the given commandable object.

Diag: Last

Multi-State

00 = none
82 = MMR: CKT 1 Soleniod Valve
83 = MMR: CKT 2 Soleniod Valve
87 = IFW: External Chilled Water Setpoint
8A = MMR: Chilled Water Flow
8C = IFW: CKT 1 Pumpdown Timeout
8D = IFW: CKT 2 Pumpdown Timeout
8E = MMR: Evap Entering Water Temp Sensor
9A = IFW: Cond Entering Water Temp Sensor
9B = IFW: Cond Leaving Water Temp Sensor
A0 = IFW: Zone Temperature Sensor
A1 = IFW: Outdoor Air Sensor
AB = MMR: Evap Leaving Water Temp Sensor
B5 = MMR: Low Evap Refrigerant Pressure
B6 = MMR: Low Evap Refrigerant Pressure CKT 2
BA = MMR: Overload Trip Compressor A
BB = MMR: Overload Trip Compressor B
BC = MMR: Overload Trip Compressor C
BD = MMR: Overload Trip Compressor D
C1 = MMR: Compressor A High Motor Winding Temp
C2 = MMR: Compressor B High Motor Winding Temp
C3 = MMR: Compressor C High Motor Winding Temp
C4 = MMR: Compressor D High Motor Winding Temp
C5 = IFW: Low Chilled Water Temp Unit Off
C6 = MAR: Low Chilled Water Temp Unit On
CA = MMR: Starter Contactor Interrupt Failure
CB = MMR: Starter Contactor Fail Compressor B
CC = MMR: Starter Contactor Fail Compressor C
CD = MMR: Starter Contactor Fail Compressor D
D7 = MAR: Over Voltage
D8 = MAR: Under Voltage
DF = IFW: Unit Communications Fail
E4 = MMR: Phase Loss
E5 = Phase Reversal / Phase Loss
ED = MAR: Chilled Water Flow Lost
F5 = MMR: High Pressure Cutout
F6 = MMR: High Pressure Cutout Compressor B
FD = MMR: Emergency Stop Input
FF = MMR: Unit Control Module

External Interlock Input

Binary

The UCM accepts an isolated contact closure input that is suitable for interlocking with either a customer specified or provided device. The input contact is closed for normal operation. Opening the contacts will cause a Machine Shutdown/Manual Reset (MMR) diagnostic. 0=NORMAL, 1=TRIP

FP Chilled Water Setpoint

Numeric

Set by a pot on the front panel of the UCM. This value may be limited on the low end by the following equation:

If HGBP is not enabled:
  cws - lwtc = 2 + (delta t/# of stages)
If HGBP is Enabled:
  cws - lwtc = 4 + (delta t/# of stages)

Where: the cws is the chilled water setpoint.
HGBP is the "Hot Gas Bypass Option"
lwtc is the leaving water temp cutout
setpoint which is adjustable on the
UCM front panel
delta t is the "Design Delta Temp
Setpoint" the # of stages is defined by
"Compressor Number of".

Range: 0 to 65° F.

FP Control Response Setpoint

Numeric

It is recommended that this value remain at the factory setting. If the temperature control appears to be too responsive or reactive, or if compressor cycle rate is too high, reduce the control response setpoint. Conversely, if temperature control is too sluggish, increase the control response setpoint. Range: 1 to 128. 25 is nominal.

FP Design Delta Temp Setpoint

Numeric

This number is used to define the separation between the chilled water setpoint and the leaving water temp cutout setpoint. See "FP Chilled Water Setpoint" for details of this relationship. Range: 4 to 20° F. 10° F is nominal.

Front Panel: Max Reset

Numeric

This index sets the maximum amount of setpoint reset allowed during any of the three reset types: zone based, outdoor air based and return based. The index is interpreted differently for each reset type. Range: 0 to 7.

Front Panel: Reset Ratio

Numeric

This index sets the rate of which the setpoint reset approaches its maximum reset amount with respect to the input parameter during any of the three reset types: zone based, outdoor air based and return based. The index is interpreted differently for each reset type. Range: 0 to 7.

Front Panel: Start Reset

Numeric

This index sets the starting point for setpoint reset allowed during any of the three reset types: zone based, outdoor air based and return based. The index is interpreted differently for each reset type. Range: 0 to 15.

Hot Gas Bypass Hours History

Numeric

This property indicates the number of hours the chiller has done hot gas bypass since the last clearing of this counter. Integer counter will clamp at 255 until reset to 0. Range: 0 to 255 hours

Hot Gas Bypass Option

Binary

BCU bit polarity is the inverse of UCM bit polarity. Hot Gas Bypass is not allowed when this property is disabled. Refer to the Hot Gas Bypass Status property for more information on Hot Gas Bypass. 0=DISABLED, 1=ENABLED

Hot Gas Bypass Starts

Numeric

This property indicates the number of times the chiller has been in hot gas bypass mode since the last clearing of this counter. Integer counter will clamp at 255 until reset to 0. Range: 0 to 255 starts

Hot Gas Bypass Status

Binary

Hot Gas Bypass (HGBP) is only available when compressor A alone is running. HGBP is a mechanism to reduce the capacity of the system so that very light loads (less than 1 compressor) can be better matched without rapid cycling of the compressor. This output can remain on for up to 30 minutes before either turning off the compressor or going back to full compressor load. There is no minimum off time before a restart after the HGBP is turned off. 0=HGBP INACTIVE, 1=HGBP ACTIVE

Ice Making Request: Ref

Referencer

Feeds the Ice Making Request: Tracer. 0=OFF (normal, non-ice making), 1=ON - ICE MAKING.

Ice Making Request: Tracer

Binary

Should only be used on systems that have ice making capabilities. 0=OFF (normal, non-ice making), 1=ON-ICE MAKING

Ice Making Status

Binary

Ice mode is a way of storing cold in large vats of Ice (or other freezing liquid). Ice mode is typically entered at night when energy costs are lower. Ice mode usually means running the chiller at full capacity until the Ice storage tanks are completely frozen and then shutting off the chiller for the duration of Ice mode (ice complete). This ice can then be used throughout the day to cool the load. Normal mode is trying to maintain chilled water temp by cycling on and off compressors to meet the load. 0=NORMAL MODE, 1=ICE MODE.

Ice Termination Setpoint: Ref

Referencer

Feeds the Ice Termination Setpoint: Tracer. Range: 20 to 31°F

Ice Termination Setpoint: Tracer

Numeric

This setpoint is the primary control value for the chiller in Ice Making mode. Once the chilled water temp reaches the Ice termination setpoint, all compressors are shut off and held off until ice making is turned off. Range: 20 to 31°F.

Last Control Date Time

Date/Time Numeric

This indicates the date and time when the present value property of this object was last controlled.

Lead Lag Selection

Binary

If Ckt 1 lead is selected, the UCM will prefer to start compressors on circuit 1. If Auto, the UCM will try to balance compressor operation by alternating which circuit starts first. This property is ignored when Hot Gas Bypass is enabled. 0=CKT 1 LEAD, 1=AUTO.

Maximum Capacity

Binary

Max capacity means that the chiller is running all the compressors are enabled (or not locked out due to diagnostic). 0=NOT AT MAX CAPACITY, 1=CHILLER RUNNING AT MAX CAPACITY.

Mech Cooling Control: Ref

Referencer

Feeds the Comp Number Enabled: Tracer. (Auto=4, Disable=0). 0=DISABLE, 1=AUTO.

Minimum Off Time

Numeric

This property is the minimum off time assigned to the UCM being represented. This value serves to protect the hardware from cycle times which might harm the hardware.

Minimum On Time

Numeric

This property is the minimum on time assigned to the UCM being represented. This value serves to protect the hardware from cycle times which might harm the hardware.

Minimum Time Remaining

Numeric

This property is the minimum time remaining (if any) of a minimum On/Off time control action for the represented UCM device.

Mode: System Status

Binary

Auto means that the UCM is not inhibited from running by the front panel. 0=STOP/RESET, 1=AUTO.

Object Identifier

Object ID

This property allows the assignment of a unique printable name to the object for user identification.

Object Type

Multi-State

This property designates the object’s type (i.e., analog input, binary input, TCM, PCM, etc.).

Operating Mode: Unit

Multi-State

0=Stop
1=Auto/Local
2=Auto//Remote
11=Pumpdown Level 1
12=Pumpdown Level 2
20=Hot Gas Bypass
21=Cooling Level 1
22=Cooling Level 2
23=Cooling Level 3
24=Cooling Level 4
70=Restart Inhibit
100=External Stop
101=Ice Complete.
121=Ice Cooling Level 1
122=Ice Cooling Level 2
123=Ice Cooling Level 3
124=Ice Cooling Level 4
88=Reset

Outdoor Air Temperature: Input

Numeric

This property is used for condenser fan control on CGA units or for outdoor air based reset. Range: -40 to 170° F.

Over Under Volt Protect Select

Binary

High and low voltage protections are enabled in this property. High voltage is activated (must trip) at line voltage+15 percent of nominal unit voltage. "Must hold" is +10 percent of nominal unit voltage. Low voltage is activated at line voltage-15 percent. "Must hold" is +10 percent of nominal unit voltage. 0=DISABLED, 1=ENABLED.

Present Value

Multi-State

This property is used to control the unit to one of nine standard operation modes. These modes are defined as UNOCCUPIED, OPTIMAL START, OCCUPIED, OPTIMAL STOP, DEMAND LIMIT, DUTY CYCLE, PRIORITY SHUTDOWN, NIGHT ECONOMIZE, and NIGHT HEAT-COOL. A translation (within the BCU) may take place to map these modes into a simpler mode set.

UCM Command

Multi-State

Password Protected Features.
UCM counters are:
  Compressor A Run Time
  Compressor A Starts
  Compressor B Run Time
  Compressor B Starts
  Compressor C Run Time
  Compressor C Starts
  Compressor D Run Time
  Compressor D Starts
  Hot Gas Bypass Hours History
  Hot Gas Bypass Starts
Password Protected Features are communications and chilled water reset. 0=NONE, 1=CLEAR UCM COUNTERS, 2=UNLOCK UCM

UCM Nonvolatile Memory Failure

Binary

This property indicates the active error status of the UCM NOVRAM/BBRAM data. When present, this diagnostic indicates the UCM has been unable to recall its remote setpoints from non-volatile storage, and requires a download of control information. This diagnostic is an auto reset diagnostic. 0=DATA OK, 1=DATA ERROR.

Unit Configuration

Multi-State

CGW means interlocked Water-Cooled (WC). CGA means Fan controlled air-cooled. 20 to 30 ton models have 2 compressors, 40 to 60 ton models have 4 compressors.0=CGWD 20 to 30 Ton1=CGWD 40 to 60 Ton2=CGAD 20 to 30 Ton3=CGAD 40 to 60 Ton

Unit Control Source

Multi-State

Stop means that the unit is not able to run. Local means that only front panel values are in use. Remote means that a Tracer is in control with either "Tracer" or "Comm Loss" values. 0=STOP, 1=LOCAL, 2=REMOTE

Update Tag

Numeric

Object instance update tag. This tag is used to indicate that the nonvolatile memory resident data within the particular instance has changed. The workstation is the primary user of this property.

Zone Temperature

Numeric

Used only for zone based reset. This value will probably not be present when zone based reset is not enabled. Range: 55 to 85° F.