Property | Type | Description |
Alarm Event Class |
Numeric |
Contains the Alarm and Message Routing Class number (1–20) that is used to route messages when this object is in alarm. |
Analog In Failure[1-6] |
Binary |
This property indicates the active status of the analog input [Array of 6]. |
Analog In Name[1-6] |
Character |
Array of the descriptions for analog inputs 1–6. |
Analog In Offset[1-6] |
Numeric |
Value used to offset the actual input value to the displayed input value for analog inputs 1–6. |
Analog In Range[1-6] |
Numeric |
Value indicating the sensor range of analog inputs 1–6. |
Analog In Timed Override[1-6] |
Binary |
Indicates whether analog inputs 1–6 are in Timed Override mode or not. |
Analog In Type[1-6] |
Multi-State |
This array Indicates the type of device supplying analog inputs 1–6 (i.e., thermistor, linear, resistance, balco, or platinum). |
Analog In[1-6] |
Numeric |
Array of the values for analog inputs 1–6. |
Analog Out Name[1-4] |
Character |
Array of the descriptions for analog outputs 1–4. |
Analog Out Offset[1-4] |
Numeric |
Value used to offset the actual output value to the output value received by the external equipment for analog outputs 1–4. |
Analog Out Range[1-4] |
Numeric |
Value indicating the output range of analog outputs 1–4. |
Analog Out[1-4] |
Numeric |
Array of the values for analog outputs 1–4. |
Analog Parameter Name[1-8] |
Character |
Array of the descriptions for analog parameters 1–8. |
Analog Parameter Value[1-8] |
Numeric |
Array of the values for analog parameters 1–8. |
Analog Setpoint Default Value[1-8] |
Numeric |
Communication loss values for analog setpoints 1–8. |
Analog Setpoint Name[1-8] |
Character |
Array of descriptions for analog setpoints 1–8. |
Analog Setpoint: Ref[1-8] |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the analog setpoint. |
Analog Variable Name[01-16] |
Character |
Array of descriptions for analog variables 1–16. |
Analog Variable[01-16] |
Numeric |
Array of the values for analog variables 1–16. |
Binary In Name[1-4] |
Character |
Array of descriptions for binary inputs 1–4. |
Binary In Polarity[1-4] |
Binary |
Indicates normally open/normally closed polarity of the contacts for binary inputs 1–4. |
Binary In[1-4] |
Binary |
Array of binary inputs 1–4 and their status: On=1, Off=0. |
Binary Out Min Off Time[1-6] |
Numeric |
Array containing the minimum off time values for binary outputs 1–6. These values define the minimum time the binary output must be in the Off state before it can be turned On. |
Binary Out Min On Time[1-6] |
Numeric |
Array containing the minimum on time values for binary outputs 1–6. These values define the minimum time the binary output must be in the On state before it can be turned Off. |
Binary Out Name[1-6] |
Character |
Array of descriptions for binary outputs 1–6. |
Binary Out Polarity[1-6] |
Binary |
Indicates whether normally open or normally closed contacts are used for binary outputs 1–6. |
Binary Out[1-6] |
Binary |
Active status of binary outputs 1–6. On=1, Off=0. |
Binary Parameter Name[1-8] |
Character |
Array of descriptions for binary parameters 1–8. |
Binary Parameter Value[1-8] |
Binary |
Array of the values for binary parameters 1–8. |
Binary Setpoint Default Value[01-24] |
Binary |
Communication loss values for binary setpoints 1–24. |
Binary Setpoint Name[01-24] |
Character |
Array of descriptions for binary setpoints 1–24. |
Binary Setpoint: Ref[1-8] |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the binary setpoint. |
Binary Variable Name[01-16] |
Character |
Array of descriptions for binary variables 1–16. |
Binary Variable[01-16] |
Binary |
Array of values for binary variables 1–16. |
Communication Address |
Numeric |
Indicates the assigned communications address value of the PCM. |
Communication Bad Message Count |
Numeric |
Keeps track of the number of message errors that occur when attempting to communicate with the PCM. |
Communication Channel |
Numeric |
Indicates the assigned communications channel value of the PCM. |
Communication Error Count |
Numeric |
Keeps track of the number of communications errors that occur when attempting to communicate with the PCM. |
Communication No Answer Count |
Numeric |
Keeps track of the number of unanswered communications with the PCM. |
Communication State |
Binary |
This property indicates the status of communications between the BCU and the UCM. 0=Down, 1=Up. |
Control Event Class |
Numeric |
Contains the Alarm and Message Routing Class number (1–20) that is used to route messages when this object is controlled. |
DDC Data Version |
Numeric |
This property is a random value that always changes when the DDC data changes. Seeing a change in this property indicates the DDC data in the PCM has changed. |
DDC Derivative Gain[1-6] |
Numeric |
Value indicating the derivative gain assigned to DDC loops 1–6. |
DDC Error Deadband[1-6] |
Numeric |
Value indicating the error deadband assigned to DDC loops 1–6. |
DDC Integral Gain[1-6] |
Numeric |
Value indicating the integral gain assigned to DDC loops 1–6. |
DDC Loop Behavior[1-6] |
Binary |
Value indicating whether DDC loops 1–6 are direct or reverse acting. |
DDC Output High Limit[1-6] |
Numeric |
Value indicating the high limit assigned to DDC loops 1–6. |
DDC Output Low Limit[1-6] |
Numeric |
Value indicating the low limit assigned to DDC loops 1–6. |
DDC Proportional Bias[1-6] |
Numeric |
Value indicating the proportional bias assigned to DDC loops 1–6. |
DDC Proportional Gain[1-6] |
Numeric |
Value indicating the proportional gain assigned to DDC loops 1–6. |
Desired Binary Out[1-7] |
Binary |
Array of values for binary setpoints 18–24. |
Desired PCM Op Mode |
Multi-State |
Indicates whether the PCM is using Local, Remote (Tracer Summit), or manual operating values. |
Firmware Revision |
Numeric |
Contains the firmware revision. |
Last Control Date Time |
Date/Time Numeric |
This indicates the date and time when the present value property of this object was last controlled. |
LCD Data Version |
Numeric |
Not Applicable. |
Manual Override Analog Out [1-4] |
Numeric |
Value assigned to analog outputs 1–4 when the PCM operating mode is Manual. |
Manual Override Binary Out[1-8] |
Binary |
State (On/Off) assigned to binary outputs 1–6 (7 and 8 are not used) when the PCM operating mode is Manual. |
Minimum Off Time |
Numeric |
Value assigned to the UCM which serves to protect the hardware from cycle times which might harm the hardware. This value defines the minimum time the PCM must be in the Off state before it can be turned On. |
Minimum On Time |
Numeric |
Value assigned to the UCM which serves to protect the hardware from cycle times which might harm the hardware. This value defines the minimum time the PCM must be in the On state before it can be turned Off. |
Minimum Time Remaining |
Numeric |
Indicates the minimum time remaining (if any) of a minimum On/Off time control action for the represented PCM. |
Momentary Binary In[1-4] |
Binary |
Status (On/Off) of binary inputs 1–4 when a momentary set of contacts are used. |
Object Identifier |
Object ID |
Unique hexadecimal ID of this object. This ID is used internally to identify the object. |
Object Type |
Multi-State |
Designates object’s type (i.e., analog input, binary output, TCM, PCM, etc.). |
PCL Data Version |
Numeric |
This property is a random value that always changes when the PCL data changes. Seeing a change in this property indicates the PCL data in the PCM has changed. |
PCL Routine Control[1-15] |
Binary |
Indicates whether PCL routines 1–15 are Enabled or Disabled. |
PCL Routine Status[1-15] |
Binary |
Indicates whether PCL routines 1–15 have detected an error. |
PCL Schedule[1-15] |
Numeric |
Value of the execution frequency assigned to PCL routines 1–15. |
Present Value |
Multi-State |
Current value (operating mode) of the PCM. |
Pulse Accumulator[1-2] |
Numeric |
Array of pulse accumulator values of binary inputs 1–2 (if used). |
Pulse Accumulator Name[1-2] |
Character |
Array of pulse accumulator descriptions. |
Pulse Weight[1-2] |
Numeric |
Value assigned for the pulse weight of pulse accumulators 1–2. |
UCM Date Time Status |
Binary |
This property indicates whether the PCM needs the current date and time updated (usually after the PCM has gone through a power cycle). |
UCM Line Status |
Binary |
This property indicates the active status of communications between the PCM and the Summit system. UP or Down. |
UCM Nonvolatile Memory Failure |
Binary |
This property indicates that the nonvolatile memory in the UCM has failed. |
UCM PCL Error |
Binary |
This property indicates whether an illegal statement in one of the PCL routines has been detected. |
UCM Test Mode Status |
Binary |
Indicates that the PCM is in either a normal operating state, or set for testing. |
Unit Name |
Character |
Eight character name assigned to the PCM in the PCM edit software. |
Update Tag |
Numeric |
Value indicating last edit change of this object. |