Property | Type | Description |
Alarm Event Class |
Numeric |
This arrayed property specifies the event classes to which Informational Message and Service Required alarm messages are routed. The event class has a set of receivers as determined in Site Configuration that will receive the alarm messages. |
Analog Out Control Source [1-30] |
Multi-State |
Unit controller arrayed property that contains the name of the device or software that has control of each analog output. |
Analog Out Name [1-30] |
Character String |
A unit configuration arrayed property that contains the name assigned to each analog output. |
Analog Out Request: Tracer [1-30] |
Numeric |
An arrayed property used to request an override for each of the analog outputs. Tracer Summit has the lowest priority. |
Analog Out [1-30] |
Numeric |
A unit controller arrayed property that contains the controlled value as a percentage for each analog output. |
Analog Var Local Name [1-120] |
Character String |
A unit configuration arrayed property that contains the name for each local analog variable. |
Analog Var Local Units [1-120] |
Multi-State |
A unit controller arrayed property that contains units of measurement for each local analog variable. |
Analog Var Local [1-120] |
Numeric |
A unit controller arrayed property that contains the current value for each local analog variable. |
Analog Var Summit Name [1-30] |
Character String |
A unit configuration arrayed property that contains the name for each Tracer Summit analog variable. |
Analog Var Summit Units [1-30] |
Multi-State |
A unit configuration arrayed property that contains the units of measurement for each Tracer Summit analog variable. |
Analog Var Summit: Ref [1-30] |
Property Reference |
An arrayed property used to program in Tracer Summit a value or property reference for each Summit analog variable. |
Analog Var Summit: Tracer [1-30] |
Numeric |
An arrayed property that communicates a value down to the controller for each of the Tracer Summit analog variables. |
Application Mode: Tracer |
Multi-State |
A property used to communicate an application mode down to the controller if it has DAC or SCC configuration and supporting TGP. |
Binary Out Control Source [1-30] |
Multi-State |
Unit controller arrayed property that contains the name of the device or software that has control of each binary output. |
Binary Out Name [1-30] |
Character String |
A unit configuration arrayed property that contains the name assigned to each binary output. |
Binary Out Request: Tracer [1-30] |
Binary |
An arrayed property used to request an override control for each of the binary outputs. Tracer Summit has the lowest priority. |
Binary Out [1-30] |
Binary |
A unit controller arrayed property that contains the control state of each binary output. |
Binary Var Local Name [1-120] |
Character String |
A unit configuration arrayed property that contains the name for each local binary variable. |
Binary Var Local [1-120] |
Binary |
A unit controller arrayed property that contains the current state of each local binary variable. |
Binary Var Summit Name [1-30] |
Character String |
A unit configuration arrayed property that contains the name for each Tracer Summit binary variable. |
Binary Var Summit: Ref [1-30], #12940 |
Property Reference |
An arrayed property used to program in Tracer Summit a state or property reference for each Tracer Summit binary variable. |
Binary Var Summit: Tracer [1-30] |
Binary |
An arrayed property that communicates to the controller a value for each of the Tracer Summit binary variables. |
Calc Current Periods Starts [1-6] |
Numeric |
A unit controller arrayed property that contains start totals for the current billing period for each MP580/581 calculation. Only valid for "Run Hours/Starts" calculation types. |
Calc Current Periods Value [1-6] |
Numeric |
A unit controller arrayed property that contains the calculated total value for the current billing period for each MP580/581 calculation. |
Calc Last Periods Starts [1-6] |
Numeric |
A unit controller arrayed property that contains start totals for the last billing period for each MP580/581 calculation. Only valid for "Run Hours/Starts" calculation types. |
Calc Last Periods Value [1-6] |
Numeric |
A unit controller arrayed property that contains the calculated total value for the last billing period for each MP580/581 calculation. |
Calc Name [1-6] |
Character String |
A unit configuration arrayed property that contains the name assigned to each calculation. |
Calc Pulse Rate [1-6] |
Numeric |
A unit controller arrayed property that contains the calculated pulse rate for a pulse meter application for each MP580/581 calculation. |
Calc Todays Starts [1-6] |
Numeric |
A unit controller arrayed property that contains start totals for Today for each MP580/581 calculation. Only valid for "Run Hours/Starts" calculation types. |
Calc Todays Value [1-6] |
Numeric |
A unit controller arrayed property that contains the calculated total value for today for each MP580/581 calculation. |
Calc Type [1-6] |
Multi-State |
A unit configuration arrayed property that contains the selected mathematical function the calculation is to perform for each calculation. |
Calc Yesterday Starts [1-6] |
Numeric |
A unit controller arrayed property that contains start totals for Yesterday for each MP580/581 calculation. Only valid for "Run Hours/Starts" calculation types. |
Calc Yesterdays Value [1-6] |
Numeric |
A unit controller arrayed property that contains the calculated total value for yesterday for each MP580/581 calculation. |
Comm5 Communication State |
Multi-State |
Obsolete name as of v16SP2. Refer to LonTalk Communication State property for a description. |
Comm5 Device NID |
Bytestring |
Obsolete name as of v16SP2. Refer to LonTalk Device NID property for a description. |
Comm5 DSN |
Unsigned Long Word |
Obsolete name as of v16SP2. Refer to LonTalk DSN property for a description. |
Comm5 Program ID |
Bytestring |
Obsolete name as of v16SP2. Refer to LonTalk Program ID property for a description. |
Communication Channel |
Numeric |
The number of the link on which the unit is setup to communicate. Range: 1 to 4 |
Configuration: Unit Type Profile |
Multi-State |
The type of profile for the unit. This property is used for Trane products only. |
Control Event Class |
Numeric |
This property determines where control messages are routed when the object's present value is controlled. |
Cool Output |
Numeric |
A unit controller property that contains the status of the unit's cool capacity (if hydronic, reports valve position of cool valve). This property only has a value if the MP580/581 uses the DAC or SCC profile and has TGP to support it. |
Cool Setpoint Occupied |
Numeric |
A unit configuration property that contains the occupied cooling setpoint programmed into the unit. Valid for a SCC or DAC configuration with supporting TGP. |
Cool Setpoint Occupied Standby |
Numeric |
A unit configuration property that contains the occupied standby cooling setpoint programmed into the unit. Valid for a SCC or DAC configuration with supporting TGP. |
Cool Setpoint Unoccupied |
Numeric |
A unit configuration property that contains the unoccupied cooling setpoint programmed into the unit. Valid for a SCC or DAC configuration with supporting TGP. |
Diagnostic Alarm Status |
Character String |
Unit controller property that contains the most recent diagnostic that changed to active. When the controller has an alarm condition, the status message displays the alarm diagnostic condition (indicates both severity and message). "Normal" will display when the last alarm clears. |
Discharge Air Cooling Setpoint: Ref |
Property Reference |
A property used to program in Tracer Summit a value or property reference for the discharge air temperature cooling setpoint. Only DAC configured MP580/581 controllers can use this property and TGP will determine its use. |
Discharge Air Cooling Setpoint: Tracer |
Numeric |
A property that communicates a discharge air temperature-cooling setpoint to the controller if it has a DAC configuration and supporting TGP. |
Discharge Air Heating Setpoint: Ref |
Property Reference |
A property used to program in Tracer Summit a value or property reference for the discharge air temperature heating setpoint. Only DAC configured MP580/581 controllers can use this property and TGP will determine its use. |
Discharge Air Heating Setpoint: Tracer |
Numeric |
A property that communicates a discharge air temperature heating setpoint down to the controller if it has a DAC configuration and supporting TGP. |
Discharge Air Temp |
Numeric |
A unit controller property that contains the value of the active discharge air temperature for the unit. This property only has a value if the MP580/581 uses the DAC or SCC profile and has TGP to support it. |
Discharge Air Temp Setpoint: Active |
Numeric |
A unit controller property that contains the value of the active discharge air temperature for the unit. This property only has a value if the MP580/581 uses the DAC or SCC profile and has TGP to support it." |
Duct Pressure Setpoint: Active |
Numeric |
A unit controller property that contains the effective, local or communicated, duct pressure setpoint that the unit is using in its control. This property only has a value if the MP580/581 uses the DAC profile and has TGP to support it. |
Duct Pressure Setpoint: Ref |
Property Reference |
A property used to program in Tracer Summit a value or property reference for the duct static setpoint. Only DAC configured MP580/581 controllers can use this property and TGP will determine its use. |
Duct Pressure Setpoint: Tracer |
Numeric |
A property that communicates a duct pressure setpoint down to the controller if it has a DAC configuration and supporting TGP. |
Duct Pressure: Active |
Numeric |
A unit controller property that contains the effective, local or communicated duct static pressure that the unit is using in its control. This property only has a value if the MP580/581 uses the DAC profile and has TGP to support it. |
Economizer Damper Position |
Numeric |
A unit controller property that contains the status of the economizer damper position if configured as a SCC or DAC and supported by TGP. |
Economizer Min Position: Ref
|
Property Reference |
A property used to program in Tracer Summit a value or property reference for the economizer minimum position. Only DAC configured MP580/581 controllers can use this property and TGP will determine its use. |
Economizer Min Position: Tracer
|
Numeric |
A property that communicates an economizer minimum position down to the controller if it has a DAC configuration and supporting TGP. |
Economizer Minimum Position Occupied |
Numeric |
A unit configuration property that contains the occupied minimum open position setting programmed into the unit for the outdoor air damper. Valid for a SCC configuration with supporting TGP. |
Emergency Override: Request |
Multi-State |
A property used to request an emergency override operation from the controller. Only SCC or DAC configured MP580/581 controllers can use this property and TGP will determine its use. |
Emergency Override: Tracer |
Multi-State |
A property that communicates an emergency override request down to the controller if it has supporting TGP and a DAC or SCC configuration. |
Exhaust Fan Status |
Heat Output, |
A property that contains the unit's status of the exhaust fan output if configured as a DAC and supported by TGP. |
Heat Output |
Numeric |
A unit controller property that contains the unit's primary heat capacity status if configured as an SCC or DAC and supported by TGP (if hydronic, reports valve position of primary heat valve). |
Heat Output Secondary |
Numeric |
A unit controller property that contains the unit's secondary heat capacity if configured as an SCC or DAC and supported by TGP (if hydronic, reports valve position of secondary heat valve). |
Heat Setpoint Occupied |
Numeric |
A unit configuration property that contains the occupied heating setpoint programmed into the unit. Valid for an SCC or DAC configuration with supporting TGP. |
Heat Setpoint Occupied Standby |
Numeric |
A unit configuration property that contains the occupied standby heating setpoint programmed into the unit. Valid for an SCC or DAC configuration with supporting TGP. |
Heat Setpoint Unoccupied |
Numeric |
A unit configuration property that contains the unoccupied heating setpoint programmed into the unit. Valid for a SCC or DAC configuration with supporting TGP. |
Heat/Cool Mode: Ref |
Property Reference |
A property used to program in Tracer Summit a mode or property reference for the heating/cooling mode selection. This selection at times determines the Application Mode: Tracer property. Only SCC or DAC configured MP580/581 controllers can use the Application Mode: Tracer property and TGP will determine its use. |
Last Control Date Time |
Date/Time Numeric |
The time and date of the last "Present Value" mode change. |
Location Label |
Character String |
A unit configuration property that contains text based information about the unit. Typically, the text would describe a physical location where the unit has been installed. |
LonTalk Communication State |
Multi-State |
This property indicates the status of communications between the BCU and the MP580/581. |
LonTalk Device NID |
Bytestring |
The serial number assigned to the neuron chip. The serial number is usually referred to as the Neuron Identification (NID) number, a unique, six-byte, non-changeable number. |
LonTalk DSN |
Unsigned Long Word |
A comma-separated value representing the domain, subnet and node ID (DSN) of the UCM. |
LonTalk Program ID |
Bytestring |
An identifier stored in the device (in the Neuron Chip's EEPROM) that identifies the application program running on the node. All nodes with the same program ID must have the same external interface. |
Minimum Off Time |
Numeric |
The time duration during which the Present Value must remain in an "Off" state before the "Present Value" is allowed to change to a "On" state. This serves to protect the hardware from cycle times that might harm it. Protection applies to priorities below Minimum On/Off control priority. |
Minimum On Time |
Numeric |
The time duration during which the Present Value must remain in an "On" state before the "Present Value" is allowed to change to a "Off" state. This serves to protect the hardware from cycle times that might harm it. Protection applies to priorities below Minimum On/Off control priority. |
Minimum Time Remaining |
Numeric |
The time remaining of a Minimum On Time or a Minimum Off Time control action. |
Mixed Air Temperature |
Numeric |
A unit controller property that contains the unit’s mixed air temperature. Valid only for an SCC or DAC configuration with supporting TGP. |
Mode: Active |
Multi-State |
A unit controller property that contains the unit’s actual mode. Valid for an SCC or DAC configuration with supporting TGP. |
Mode: Occupancy |
Multi-State |
A unit controller property that contains the MP580/581 unit’s effective, local or communicated occupancy status. Programming in TGP determines which one takes precedence. |
Node Self Doc |
Text String |
This property displays the unit's type of UCM |
Object Identifier |
Object ID |
The object’s type followed by its instance number.It is provided primarily to allow the embedding of the object ID in the returned data buffer. |
Object Name |
Character String |
A property that assigns a recognizable name to the controller. This name will be used within Tracer Summit to associate this controller with other programs or applications. |
Object Type |
Object Type |
The type of object for this controller. |
Occupancy: Active |
Binary |
A unit controller property that contains the effective unit occupancy. |
Occupancy: Tracer |
Multi-State |
A property that communicates an occupancy request down to the controller. |
Occupied Bypass: Active |
Binary |
Used to display the current occupied status of the unit. |
Outdoor Air Flow |
Numeric |
A unit controller property that contains the unit’s effective, local or communicated outdoor air flow. Valid only for a DAC configuration with supporting TGP. A value of -1 indicates an invalid value. |
Outdoor Air Temperature: Ref |
Property Reference |
A property used to program in Tracer Summit a value or property reference for the outdoor air temperature. Only SCC or DAC configured MP580/581 controllers can use this property and TGP will determine its use. |
Outdoor Air Temperature: Tracer |
Numeric |
A property that communicates an outdoor air temperature down to the controller if it has a SCC or DAC configuration and supporting TGP. |
Present Value |
Multi-State |
The occupancy mode sent to the controller from the BCU. The nine standard operation modes include Unoccupied, Optimal Stop, Occupied, Optimal Start, Demand Limit, Duty Cycle, Priority Shutdown, Night Economize, and Night Heat Cool. These modes will get sent down to the controller as either an occupied mode or an unoccupied mode. |
Pressure: Input |
Numeric |
A unit controller property that contains the current pressure reading from the pressure transducer input. |
Relinquish Default |
Multi-State |
The occupancy mode to which the unit controller is controlled when modes at all other priority levels (1..16) are not in effect. |
Return Fan Status |
Numeric |
A unit controller property that contains the status of the unit's return fan output. Valid for a DAC configuration with supporting TGP. |
Space CO2 Concentration: Input |
Numeric |
A unit controller property that contains the current space carbon dioxide (CO2) concentration in parts per million (ppm). Valid only for SCC configured controllers that have a locally wired CO2 sensor and have TGP programming to support it. |
Space Humidity: Active |
Numeric |
A unit controller property that contains the effective, local or communicated, space relative humidity as a percentage for the unit. Valid only for a SCC or DAC configuration with supporting TGP. |
Space Pressure Setpoint: Ref |
Property Reference |
A property used to program in Tracer Summit a value or property reference for the space pressure setpoint. Only DAC configured MP580/581 controllers can use this property and TGP will determine its use. |
Space Pressure Setpoint: Tracer |
Numeric |
A property that communicates a space pressure setpoint down to the controller if it has supporting TGP and a DAC configuration. |
Space Pressure: Active |
Numeric |
A unit controller property that contains the effective, local or communicated space pressure. Valid only for a DAC configuration with supporting TGP. |
Space Pressure: Ref |
Property Reference |
A property used to program in Tracer Summit a value or property reference for the space pressure. Only DAC configured MP580/581 controllers can use this property and TGP will determine its use. |
Space Pressure: Tracer |
Numeric |
A property that communicates a space pressure down to the controller if it has supporting TGP and a DAC configuration. |
Space Temperature Setpoint: Active |
Numeric |
A unit controller property that contains the effective, local or communicated space temperature setpoint. Valid only for an SCC configuration with supporting TGP. |
Space Temperature Setpoint: Ref |
Property Reference |
A property used to program in Tracer Summit a value or property reference for the space temperature setpoint. Only SCC configured MP580/581 controllers can use this property and TGP will determine its use. |
Space Temperature Setpoint: Tracer |
Numeric |
A property that communicates a space temperature setpoint down to the controller if it has supporting TGP and an SCC configuration. |
Space Temperature: Active |
Numeric |
A unit controller property that contains the effective, local or communicated space temperature for the unit. Valid only for an SCC or DAC configuration with supporting TGP. |
Space Temperature: Ref |
Property Reference |
A property used to program in Tracer Summit a value or property reference for the space temperature. Only SCC or DAC configured MP580/581 controllers can use this property and TGP will determine its use. |
Space Temperature: Tracer |
Numeric |
A property that communicates a space temperature down to the controller if it has supporting TGP and a DAC or SCC configuration. |
Startup Setpoint |
Numeric |
A constant entered by the user that the BCU uses to determine warm-up or pre-cool modes at start-up. Only DAC and SCC configured controllers need this value. |
Supply Fan Status |
Numeric |
A unit controller property that contains the status of the unit's fan output. Valid only for an SCC or DAC configuration with supporting TGP. |
Universal Input Name [1-36] |
Character String |
A unit configuration arrayed property that contains the name assigned to each universal input. |
Universal Input TOV Cancel [1-36] |
Binary |
A unit controller arrayed property that contains the status of a thermostat's local cancel timed override request input for all universal inputs. |
Universal Input TOV Request [1-36] |
Binary |
A unit controller arrayed property that contains the status of a thermostat's local timed override request input for all universal inputs. |
Universal Input Units [1-36] |
Multi-State |
A unit configuration arrayed property that contains the selected units of measurement for each universal input. |
Universal Input [1-36] |
Numeric |
A unit controller arrayed property that contains the value for all universal inputs. |
Update Tag |
Numeric |
This property is used as the upload/download tag. Its purpose is to keep the PC Workstation and BCU copies of the object instance in synchronization. |
Water Valve Drive Closed: Ref |
Property Reference |
A property used to program in Tracer Summit a control action or property reference for the water valve closed override command. This request applies to all hydronic valves on DAC and SCC configured controllers if programmed in TGP to |
Water Valve Drive Open: Ref |
Property Reference |
A property used to program in Tracer Summit a control action or property reference for the water valve open override command. This request applies to all hydronic valves on DAC and SCC configured controllers if programmed in TGP to |
Water Valve Override: Tracer |
Multi-State |
A property that communicates an override command for the Water Valve(s) down to the controller if it has supporting TGP and a DAC or SCC configuration. |