Property | Type | Description |
Compressor Control: Active |
Binary |
This property indicates the current value that is being communicated by the system to the heat pump members and used to disable their compressors. 0=DISABLE COMPRESSOR, 1=AUTO |
Compressor Control: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate to the heat pump members to enable or disable their compressor(s). |
Continuous Operation: Setup |
Binary |
This property is used to assign the Heat Pump Loop Control into the continuous operation mode. |
Load: Cooling |
Numeric |
This is the sum of the cooling loads from all heat pump members. |
Load: Heating |
Numeric |
This is the sum of the heating loads from all heat pump members. |
Loop Controller Mode |
Op Mode |
This property is the mode to which the application is controlling the loop controller. The possible modes are UNOCCUPIED, OPTIMAL START, OCCUPIED and NIGHT HEAT-COOL. |
Loop Controller: Ref |
Object Reference |
This referencer specifies the object which serves as the loop controller, such as the UPCM, PCM or TLC. |
Member List |
Object Reference |
This is the list of the heat pumps which are assigned as members of this application. |
Object Identifier |
Object ID |
Unique hexadecimal ID of this object. This ID is used internally to identify the object. |
Object Name |
Character |
This is the name assigned to the object. Range: Up to 32 characters. |
Object Type |
Multi-State |
Designates object’s type (i.e., analog input, binary output, TCM, PCM, etc.). |
Requests To Run: Active |
Numeric |
This property is the total number of heat pump members whose terminal load is greater than or equal to 30% or less than or equal to -30%. |
Requests To Run: Threshold |
Numeric |
When the system is in the Unoccupied Mode and the value of the "Requests to Run: Active" property reaches this threshold, the system will transition into the Night Heat-Cool Mode. |
Security Class |
Bit String |
This property contains the security class setup information for the Heat Pump Loop Control object. |
Startup Enable: Ref |
Property Reference |
When the system is in the Unoccupied Mode, this referencer determines if the system should transition into the Optimal Start Mode. |
Update Tag |
Numeric |
This property indicates the last edit change of this object. |