Property |
Type |
Description |
||||||
Active Circuit[1-8] |
Binary |
Active Circuit. Each bit reflects the state of up to eight circuits |
||||||
Alarm Event Class |
Numeric |
This arrayed property specifies the event classes to which Informational Message and Service Required alarm messages are routed. The event class has a set of receivers as determined in Site Configuration that will receive the alarm messages. |
||||||
Alarm Level |
Enumerated |
Indicates the severity of the diagnostic shown in the "Diagnostic Alarm Status" property. |
||||||
Alarm Present |
Binary |
Controller property that indicates that a diagnostic condition exists within the unit. |
||||||
Alarm Reset |
Binary |
Used to directly set nviRequest, enumeration 10 (clear alarm). The alarm state of the object is cleared, but the state of the object itself may remain unchanged. Persistent alarms will be reported, as they are re-detected. '???' will be displayed because this is handled as a momentary command state, so there is no real value that can be read. The range below is more for an object like a binary output that is used to reference the Alarm Reset property. |
||||||
Alarms Locked |
Binary |
The value of this property is TRUE when clearing alarms remotely is not supported by the UCM. |
||||||
Application Mode: Tracer |
Multi-State |
Used to communicate the application mode of the unit. Valid Range: 0 = Auto |
||||||
Cabinet Style |
Multi-State |
Controller property that defines the cabinet style based on the Unit Type. |
||||||
Cluster Member Role |
Multi-State |
Indicates the current cluster configuration of a Trane controller. |
||||||
Comm5 Communication State |
Numeric |
Obsolete name as of v16SP2. Refer to LonTalk Communication State property for a description. |
||||||
Comm5 DSN |
Unsignedlongword |
Obsolete name as of v16SP2. Refer to LonTalk DSN property for a description. |
||||||
Comm5 Program ID |
Numeric |
Obsolete name as of v16SP2. Refer to LonTalk Program ID property for a description. |
||||||
Communication Channel |
Numeric |
This property provides access to the assigned communications channel value of the UCM being represented. |
||||||
Compressor Control: Loop Control |
Binary |
Building control property that is used to propagate an immediate and latched compressor disable to the controller. A Disable causes a disable to be put to Compressor Control: Tracer and sets a VM-based value to Disable. An Auto only causes the VM-based value to be set to Auto. Valid Range: 0 = Disable, 1 = Auto. |
||||||
Condenser Capacity: Active |
Numeric |
Indicates the active condenser capacity. |
||||||
Condenser Water Flow Status |
Binary |
Controller property that displays the effective, local or communicated, condenser water flow. |
||||||
Condenser Water Flow: Ref |
Property Reference |
Building control property selects system water flow state that is communicated down to the unit as the condenser water flow. |
||||||
Condenser Water Flow: Tracer |
Enumeration |
Building control property used to communicate the building condenser water flow to the controller. |
||||||
Condenser Water Pump Output |
Binary |
Controller property that displays the unit’s hardwired condenser water pump status. |
||||||
Condenser Water Temp: Active |
Numeric |
Indicates the active condenser water temperature. In an Intellipak RTU, this is the condenser sump water temperature. In an Intellipak CSC this is the entering water condenser temperature. |
||||||
Condenser Water Temp: Entering |
Numeric |
Controller property which displays the unit's local temperature of the water entering the condenser. |
||||||
Condenser Water Temp: Leaving |
Numeric |
Controller property which display the unit’s local temperature of the water leaving the condenser. |
||||||
Condenser Water Temp: Local |
Numeric |
Indicates the unit’s hardwired condenser water temperature. |
||||||
Condenser Water Temp: Ref |
Property Reference |
Building control property selects condenser water temperature that is communicated down to the unit as the condenser water temp. |
||||||
Condenser Water Temp: Tracer |
Numeric |
Building Control property that is used to communicate the building condenser water temp to the controller. |
||||||
Config: Condenser Type |
Multi-State |
Controller property that displays condenser type. |
||||||
Configuration: Unit Type Trane |
Multi-State |
Controller property that displays unit type configuration. This property only available in Trane products only. |
||||||
Control Event Class |
Numeric |
This property determines where control messages are routed when the object’s present value is controlled. |
||||||
Cool Output |
Numeric |
Status of the unit's cool capacity (if hydronic, report valve position of cool valve). |
||||||
Cool Setpoint Occupied |
Numeric |
Controller property which selects the unit’s occupied cooling space setpoint. |
||||||
Cool Setpoint Occupied Standby |
Numeric |
Controller property that selects the units occupied standby cooling space setpoint. |
||||||
Cool Setpoint Unoccupied |
Numeric |
Controller property that selects the unit’s unoccupied cooling space setpoint. |
||||||
Cool Stage Status[1-8] |
Multi-State |
Controller property that indicates the presence and state of the unit’s cool stage. |
||||||
Cool Type |
Multi-State |
Controller property that displays the unit’s cooling type configuration. |
||||||
Cooling Control: Ref |
Property Reference |
Building control property that selects the allowable cooling capacity the controller may use. |
||||||
Cooling Control: Tracer |
Numeric |
Building control property that is used to communicate the compressor enable input to the controller. |
||||||
Cooling Disable: Ref |
Property Reference |
Building control Binary property is used to enable or disable the unit’s cooling control. |
||||||
Critical Application Alarming |
Binary |
This property changes a select group of priority 2 alarms (service request) to priority 3 alarms (critical). This pre-defined group of alarm may vary for each UCM. |
||||||
Daytime Warmup Setpoint |
Numeric |
Controller property that selects the daytime warm-up initiate temperature. This applies for units that support daytime warm-up. During occupied mode and when the space temperature falls below this temperature, the unit will change into a daytime warm-up (heating) mode until the space temperature goes above the Daytime Terminate temperature. There should be a three-degree Fahrenheit temperature difference between the Daytime Warmup Setpoint and Daytime Warmup Terminate. A value of 40 deg F can be used to disable daytime warm-up. |
||||||
Daytime Warm-up Terminate |
Numeric |
Controller property that selects the daytime warm-up terminate temperature |
||||||
Defrost Status |
Enumerated |
This property is used to report when the unit is in defrost mode. |
||||||
Dehumidification Control: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate to the UCM to enable the dehumidification function. |
||||||
Dehumidification Control Status |
Multi-State |
Indicates if dehumidification is present or not and if it is on or off. Valid Range: |
||||||
Dehumidification Control: Tracer |
Multi-State |
Building control property used to communicate the enable/disable dehumidification function to the controller. Valid Range: Enable, Disable, Not Used (0xFF = Enable) |
||||||
Dehumidification Level |
Numeric |
Indicates the current level of dehumidification control. Valid Range: 0-100% |
||||||
Dehumidification Start Setpoint: Tracer |
Numeric |
Used to communicate the space dehumidification setpoint to the controller. When valid, this has priority over any other space dehumidification setpoint. |
||||||
Device Major Revision |
UnsignedByte |
This defines the major revision number for the device. The major revision of the device is updated whenever the network interface of the device changes. |
||||||
Device Minor Revision |
UnsignedByte |
This defines the minor revision number for the device. The minor revision of the device is updated whenever the software is changed for any reason. |
||||||
Diagnostic Alarm Status |
Text String |
Communicates the diagnostic of the controller as they occur. The severity of the diagnostic is indicated in the "Alarm Level" property. |
||||||
Discharge Air Cooling Setpoint: Local |
Numeric |
Controller property that displays the units locally stored default discharge air temperature cooling setpoint. |
||||||
Discharge Air Cooling Setpoint: Ref |
Property Reference |
Building control property defines the discharge air cooling setpoint that is communicated down to the unit as the discharge air temp cooling setpoint. |
||||||
Discharge Air Cooling Setpoint: Reset |
Binary |
This read-only configuration property indicates the default discharge air cooling setpoint reset control. Valid Range: |
||||||
Discharge Air Cooling Setpoint: Tracer |
Numeric |
Building control property that communicates the discharge air temp cooling setpoint to the controller. |
||||||
Discharge Air Dew Pt Setpoint: Active |
Numeric |
Controller property that displays the is effective, local or communicated, discharge air temp dew point setpoint that the unit is using in it’s control. A communicated value has priority over the local value. |
||||||
Discharge Air Dew Pt Setpoint: Local |
Numeric |
Controller property that displays the units locally stored default discharge air dew point setpoint. |
||||||
Discharge Air Dew Pt Setpoint: Ref |
Property Reference |
Building control property defines dew point setpoint that is communicated down to the unit as the discharge air temperature dew point setpoint. |
||||||
Discharge Air Dew Pt Setpoint: Tracer |
Numeric |
Building control property that communicates the discharge air temp dew point setpoint to the controller. |
||||||
Discharge Air Dew Pt: Active |
Numeric |
Controller property that displays the effective, local or communicated, discharge air temp dew point. The building controls communicated value has priority over the unit’s local value. |
||||||
Discharge Air Heating Setpoint: Local |
Numeric |
Controller property that displays the units locally stored default discharge air heating setpoint. |
||||||
Discharge Air Heating Setpoint: Ref |
Property Reference |
Building control property defines the discharge air heating setpoint that is communicated down to the unit as the discharge air temp heating setpoint. |
||||||
Discharge Air Heating Setpoint: Reset |
Binary |
This read-only configuration property indicates the default discharge air heating setpoint reset control. Valid Range: |
||||||
Discharge Air Heating Setpoint: Tracer |
Numeric |
Building control property that communicate the discharge air temp heating setpoint to the controller. |
||||||
Discharge Air Reheat Setpoint: Active |
Numeric |
Indicates the active discharge air temp reheat setpoint in the controller. |
||||||
Discharge Air Reheat Setpoint: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which discharge air temp reheat setpoint value to communicate to the UCM. |
||||||
Discharge Air Heating Setpoint Reset |
Binary |
This read-only configuration property indicates the default discharge air heating setpoint reset control. Valid Range: |
||||||
Discharge Air Reheat Setpoint: Tracer |
Numeric |
Used to communicate the discharge air temp reheat setpoint in the controller. |
||||||
Discharge Air Temp |
Numeric |
Controller property that displays the status of the hardwired sensor on the unit. |
||||||
Discharge Air Temp Setpoint: Active |
Numeric |
Controller property that displays the effective, local or communicated, discharge air temp setpoint for the active heating/cooling mode that the unit is using in it’s control. A communicated value has priority over the local value. |
||||||
Duct Pressure: Active |
Numeric |
Controller property that displays the effective, local or communicated, duct pressure that the unit is using in it’s control. A communicated value has priority over the local value. |
||||||
Duct Pressure: Local |
Numeric |
Controller property that displays the hardwired duct pressure. |
||||||
Duct Pressure Setpoint: Active |
Numeric |
Controller property that displays the effective, local or communicated, duct pressure setpoint that the unit is using in it’s control. A communicated value has priority over the local value. |
||||||
Duct Pressure Setpoint: Local |
Numeric |
Controller property that displays the unit’s default duct pressure setpoint. |
||||||
Duct Pressure Setpoint: Ref |
Property Reference |
Building control property defines the duct static pressure setpoint that is communicated down to the unit as the duct static setpoint. |
||||||
Duct Pressure Setpoint: Tracer |
Numeric |
Building control property that communicates the effective duct pressure setpoint to the controller. |
||||||
Duct Pressure: Tracer |
Numeric |
Building control property used to communicate a duct static pressure value. Valid Range: 0-7.9 I.W.C (0-1967 Pa). Invalid: 0x7FFF |
||||||
Economizer Control: Ref |
Property Reference |
Building control property defines the economizer control state that is communicated down to the unit as the Economizer Enable Input. |
||||||
Economizer Control: Tracer |
Multi-State |
Building control that communicates the auto/enable/disable economizer operation to the controller. |
||||||
Economizer Damper Position |
Numeric |
Controller property that displays the status of unit's economizer damper pos. (Not used if unit has 2-position OA damper) |
||||||
Economizer Enable: Active |
Multi-State |
Controller property that displays the displays the unit's current state of economizer control algorithm operation. |
||||||
Economizer Min Position: Ref |
Property |
Building control property defines the minimum position for the economizer that is communicated down to the unit as the Economizer Minimum Position Input. |
||||||
Economizer Min Position: Tracer |
Numeric |
Building control property that communicates the economizer minimum position to the controller. The communicated value is used over the default value when both are present. |
||||||
Economizer Minimum Position Occupied |
Numeric |
Controller property that displays the unit’s default outdoor air damper occupied minimum position. |
||||||
Economizer Minimum Position Occupied Standby |
Numeric |
Controller property that displays the unit’s default outdoor air damper occupied standby minimum position. |
||||||
Economizer/Ventilation Type |
Multi-State |
Controller property that displays the economizer/ventilation configuration. |
||||||
Emergency Override: Request |
Multi-State |
Building control property is used control the unit into emergency override mode. |
||||||
Emergency Override: Tracer |
Multi-State |
Building control property that communicates the emergency override request to the controller. If Emergency Override: Request is Normal, the communicated request will come from the Present Value. The communicated request will come from Emergency Override: Request if it is anything other than Normal. |
||||||
Energy Recovery Exhaust Air Bypass Damper Position |
Numeric |
Indicates the current Position of the Energy Recovery Exhaust Air Bypass Damper. |
||||||
Energy Recovery Leaving Exhaust Temperature |
Numeric |
Indicates the current temperature of the energy recovery wheel leaving exhaust air. Invalid 0x7FFF |
||||||
Energy Recovery Outdoor Air Bypass Damper Position |
Numeric |
Indicates the current position of the energy recovery wheel outside air bypass damper. |
||||||
Energy Recovery Wheel Frost Avoidance |
Multi-State |
Indicates the current status of the Energy Recovery Frost Avoidance function for monitoring. When the energy recovery wheel exhaust temperature falls below the frost avoidance setpoint, the controller initiates a frost avoidance sequence (modulates the outside air bypass damper to maintain setpoint, and/or energizes a pre-heater.) The Network Variable associated with this property uses two fields (a State field and a Value field) to display an answer. Valid Range: |
||||||
Energy Recovery Wheel Preheat Relay Status |
Multi-State |
Indicates the current status of the energy recovery wheel preheat relay output. Valid Range: |
||||||
Energy Recovery Wheel Relay Status |
Multi-State |
Indicates the current operational status of the energy recovery wheel. Valid Range: |
||||||
Entering Water Temperature: Active |
Numeric |
Controller property that displays the effective, local or communicated, entering water temperature. When both exist, the communicated value is sent. |
||||||
Evaporator Frost Cutout Temperature |
Numeric |
Indicates the active frost avoidance setpoint. Valid Range: 25 to 35° F (-3.9 to 1.7° C) |
||||||
Evaporator Frost Protection Status [1-8] |
Binary |
Indicates if any of the refrigeration circuits are below the evaporator frost cutout temperature. There are up to 8 circuits. |
||||||
Evaporator Refrigerant Temperature[1-8] |
Numeric |
Indicates the evaporator leaving temperature in circuits 1 through 8. |
||||||
Exhaust Damper Position |
Numeric |
Indicates the current status of the exhaust damper. Valid Range: 0-100% Invalid = 0x7FFF |
||||||
Exhaust Enable Position |
Numeric |
This read-only configuration property indicates the default exhaust enable outdoor air damper position setpoint. Valid Range: 0 to 100% |
||||||
Exhaust Fan Status |
Numeric |
Controller property that displays the unit's status of the exhaust fan output. |
||||||
Exhaust/Return Type |
Multi-State |
Controller property that displays the unit's exhaust/return configuration. |
||||||
Face And Bypass: Active |
Numeric |
Controller property that displays the unit's status of face bypass damper. |
||||||
Generic Binary Input |
Multi-State |
Controller property that displays the state of generic Binary input 1. |
||||||
Generic Binary Output |
Multi-State |
Controller property that displays the presence and state of generic Binary output 1. |
||||||
Generic Temperature |
Numeric |
Controller property that displays the status of the local generic temperature input. |
||||||
Heat Output |
Numeric |
Controller property that displays the status of the unit's primary heat capacity (if hydronic, report valve position of primary heat valve). |
||||||
Heat Output Secondary |
Numeric |
Controller property that displays the status of the unit's secondary heat capacity (if hydronic, report valve position of secondary heat valve). |
||||||
Heat Setpoint Occupied |
Numeric |
Controller property that selects the unit’s occupied heating space setpoint. |
||||||
Heat Setpoint Occupied Standby |
Numeric |
Controller property that selects the unit’s occupied standby heating space setpoint. |
||||||
Heat Setpoint Unoccupied |
Numeric |
Controller property that selects the unit’s unoccupied heating space setpoint. |
||||||
Heat Stage Status [1-8] |
Multi-State |
Controller property that indicates the presence and state of the unit’s heat stage. |
||||||
Heat/Cool Mode: Active |
Binary |
Used to display the current heat/cool mode of the DAC UCM. This is an interpretation made by the BCU based on the value shown for the ‘Mode: Heat/Cool’ property
|
||||||
Heat/Cool Mode: Ref |
Binary |
Building control property defines what mode being either heating or cooling that is communicated down to the unit as the heat/cool mode. |
||||||
Heating Control: Ref |
Numeric |
Building control property that selects the allowable heating capacity the controller may use. |
||||||
Heating Control: Tracer |
Numeric |
Building control property that is used to communicate heating capacity to the controller. |
||||||
Heating Disable: Ref |
Binary |
Building control Binary property is used to enable or disable the unit’s heating control. |
||||||
Humidification Control: Ref | Property Reference | This property indicates the value to be used by the BCU to determine which value to communicate to the UCM to enable the humidification function. | ||||||
Humidification Control: Tracer | Multi-State | Building control property used to communicate the enable/disable humidification function to the controller. Valid Range: Enable, Disable, Not Used (0xFF = Enable) | ||||||
Humidity: Active | Numeric | Indicates the unit's humidifier output. Valid Range: 0 - 100%: 0 = Off Invalid = 0x7FFF |
||||||
Language Identifier |
Multi-State |
Controller property that displays what language is being used. Alarm messages will be sent in the current language. |
||||||
Last Control Date/Time |
Numeric |
Building control property that indicates the date and time when the present value property of this object was last controlled. The date and time value is stored and manipulated in the BCU’s standard date/time format, which is a value of seconds past midnight of January 1st, 1980. |
||||||
Load: Absolute |
Numeric |
Controller property that is used by water-cooled condensing units to indicate the current heat/cool energy demand of the unit. This property is intended to be reference by a water loop control application. |
||||||
Load: Terminal |
Numeric |
Controller property that used by water-cooled condensing units to indicate the current heat/cool energy demand of the unit. |
||||||
Location Label |
Text String |
Controller property that displays unit programmed description text such as a room location. |
||||||
LonTalk Communication State | Numeric | This property indicates the status of communications between the BCU and the DAC. 0 = Down 1 = Up 2 = No neuron ID assigned 3 = Installation in progress 4 = Incomplete bindings |
||||||
LonTalk DSN | Unsignedlongword | A comma-separated value representing the domain, subnet and node ID (DSN) of the UCM. | ||||||
LonTalk Program ID | Numeric | An identifier stored in the device (in the Neuron Ship’s EEPROM) that identifies the application program running on the node. All nodes with the same program ID must have the same external interface. | ||||||
Manual Control | Binary | If the UCM supports this property, this will indicate if the source of the control parameters used by the device is local (manual). Valid Range: FALSE (0) = Device is under building management control (default). TRUE (non-0) = Device is under manual control. |
||||||
Max Heat: Active |
Binary |
Controller derived property that is used to display the current status of the "max heat" or "test" modes of the DAC UCM. |
||||||
Minimum Off Time |
Numeric |
Building control property that sets the minimum off time requirement before the present value can change to an on state. This value serves to protect the hardware from cycle times that might harm the hardware. |
||||||
Minimum On Time |
Numeric |
Building control property that sets the minimum on time requirement before the present value can change to an off state. This value serves to protect the hardware from cycle times that might harm the hardware. |
||||||
Minimum Send Time | Numeric | This defines the minimum period of time between automatic, network variable, output transmissions. Although this configuration property is optional, it must be provided if the minimum send-time function is used in the controller. Setting this property to 0.0 disables the Minimum Send Time mechanism. Valid Range: 0.0 sec to 6,553.4 sec. |
||||||
Minimum Time Remaining |
Numeric |
Building control property that displays the minimum time remaining (if any) of a minimum On/Off time control action for the UCM. PUTS are also allowed so that an operator can intervene on a Minimum On/Off control action that is in progress. |
||||||
Mixed Air Low Limit Setpoint: Local |
Numeric |
Controller property that displays the unit’s default minimum mixed air temperature. |
||||||
Mixed Air Temperature |
Numeric |
Controller property that displays the unit’s current mixed air temperature. |
||||||
Mode: Active |
Multi-State |
Controller property that displays the unit’s actual mode of the unit. |
||||||
Mode: Heat/Cool |
Multi-State |
Controller property that displays the unit’s current Heat/Cool mode of the unit. This property will show that the unit is in a "Test" mode while Mode: Active may not show unit in this mode. |
||||||
Mode: Occupancy |
Multi-State |
Controller property that displays the unit’s effective, local or communicated, occupancy status. When both exist, the communicated value has priority. Valid Range: |
||||||
Node Self Doc |
Text String |
This property displays the unit's type of UCM (i.e., ZN510, ZN520, MP580, etc.) |
||||||
Node Status | Multi-State | The current operating condition of the Neuron Microprocessor. Possible conditions are: Normal Unconfigured Unconfigured/No application Configured/Online Configured/Offline (soft) Configured/Offline (hard) Configured/Offline (bypass) Unsupported |
||||||
Object Identifier |
Object ID |
Building control property uniquely identifies a particular object. It is provided primarily to allow the embedding of the object ID in the returned data buffer. |
||||||
Object Name |
Character String |
Building control property allows the assignment of a unique printable name to the object for user identification. |
||||||
Object Type |
Multi-State |
Building control property displays the object’s type (i.e., analog input, Binary input, TCM, PCM, etc.). |
||||||
Occupancy: Active |
Binary |
Controller derived property that displays current occupancy of unit in terms of either occupied or unoccupied. |
||||||
Occupancy: Tracer |
Multi-State |
Building control property that is used to communicate the occupancy request to the controller. The communicated value used in conjunction with the local input to determine effective occupancy. |
||||||
Occupied Bypass Time |
Unsigned Word |
Controller property which sets the unit’s maximum amount of time that the unit can be in Bypass (occupancy) mode from a single Bypass request from a local (hardwired) switch. This property only applies to a local thermostat timed override request, if present. |
||||||
Occupied Bypass: Active |
Binary |
Controller property which displays whether or not the unit is a bypass mode occupancy. |
||||||
Outdoor Air Cooling Lockout: Local |
Numeric |
Controller property which is used to define the cooling lockout point, below which mechanical cooling should be disabled. |
||||||
Outdoor Air Damper Position |
Numeric |
Controller property which displays the unit’s current position of the Outdoor Air Damper. |
||||||
Outdoor Air Dew Point: Active | Numeric | This is the current value for the outdoor air dew-point temperature. Valid Range: 25 - 85 deg. F (-3.89 - 29.44 deg. C) |
||||||
Outdoor Air Enthalpy |
Numeric |
Controller property which displays the unit’s effective, local or communicated, outdoor air enthalpy, When both exist, the communicated value has priority. |
||||||
Outdoor Air Enthalpy Setpoint: Local |
Numeric |
Controller property which defines the point at which outdoor air enthalpy is appropriate for economizing. |
||||||
Outdoor Air Flow |
Numeric |
Controller property which displays the unit’s effective, local or communicated, outdoor air flow. |
||||||
Outdoor Air Humidity: Active |
Numeric |
Controller property which displays the unit’s effective, local or communicated, outdoor air relative humidity as a percentage, When both exist, the communicated value has priority. |
||||||
Outdoor Air Humidity: Input |
Numeric |
Controller property which displays the unit’s hardwired outdoor air relative humidity as a percentage, |
||||||
Outdoor Air Humidity: Ref |
Numeric |
Building control property that defines the outdoor air humidity that is communicated down to the unit. |
||||||
Outdoor Air Humidity: Tracer |
Numeric |
Building control property that is used to communicate the outdoor air humidity to the controller. Communicated value used over local value when both are present. |
||||||
Outdoor Air Min Flow Stpt: Local |
Numeric |
Controller property that is used as the unit’s default outdoor air min flow setpoint. |
||||||
Outdoor Air Min Flow Setpoint: Ref |
Numeric |
Building control property used to set the economizer’s outdoor air minimum flow setpoint that is communicated down to the unit. |
||||||
Outdoor Air Min Flow Setpoint: Tracer |
Numeric |
Building control property that is used to communicate the economizer’s outdoor air minimum flow setpoint to the controller. |
||||||
Outdoor Air Temp Setpoint: Local |
Numeric |
Controller property that is used to define the minimum outdoor air temperature suitable for economizing. |
||||||
Outdoor Air Temperature: Active |
Numeric |
Controller property that displays the effective, local or communicated, outdoor air temperature. When both exist, the communicated value has priority. |
||||||
Outdoor Air Temperature: Input |
Numeric |
Controller property that displays the unit’s local outdoor air temperature input. |
||||||
Outdoor Air Temperature: Ref |
Property Reference |
Building control property that sets an Outdoor Air Temperature that is communicated down to the unit. |
||||||
Outdoor Air Temperature: Tracer |
Numeric |
Building control property that is used to communicate the outdoor air temperature to the controller. Communicated value used over local value when both are present. |
||||||
Preheat Type | Multi-State | Controller property that displays the unit’s preheat configuration. 0 = None 1 = Modulating Hot Water 2 = Binary Hot Water 3 = Modulating Steam Water 4 = Binary Steam Water 5 = Modulating Electric 6 = 1 Stage Electric 7 = 2 Stage Electric 8 = 3 Stage Electric 9 = 4 Stage Electric 10 = Pump And Valve 11 = 1 Stage Gas 12 = 2 Stage Gas 13 = Modulating Gas 14 = 2 Pipe Changeover Modulating 15 = 2 Pipe Changeover Binary 16 = Hot Gas Bypass 17 = Modulating Air 18 = 1 Stage DX 19 = 2 Stage DX 20 = 3 Stage DX 21 = 4 Stage DX 22 = Wild Coil 23 = Face Bypass Wild Hot Water 24 = Face Bypass Wild Steam 25 = Face Bypass Modulating Hot Water 26 = Face Bypass Modulating Steam 27 = Face Bypass Binary Hot Water 28 = Face Bypass Binary Steam |
||||||
Present Value |
OP Mode |
Building control property is used to control the UCM to one of nine standard operation modes. These modes are defined as Unoccupied, Optimal Stop, Occupied, Optimal Start, Demand Limit, Duty Cycle, Priority Shutdown, Night Economize, and Night Heat Cool. |
||||||
Refrigerant Type |
Multi-State |
Controller property that displays the unit’s refrigerant configuration. |
||||||
Reheat Type |
Multi-State |
Controller property that displays the unit’s reheat configuration. |
||||||
Reset Maintenance Timer |
Binary |
Building control property that is used to reset the maintenance timer in the DAC UCM. |
||||||
Return Air Temperature | Numeric | The return air temperature. Valid Range: -40.00 to 212.00 deg. F (-40.00 to 100 deg. C.) |
||||||
Return Fan Pressure Setpoint: Local |
Numeric |
Controller property that defines the default return fan pressure setpoint. |
||||||
Return Fan Pressure: Active |
Numeric |
Controller property that displays the effective return fan pressure. |
||||||
Return Fan Status |
Numeric |
Controller property that displays the status of the unit's return fan output. |
||||||
Saturated Condenser Temperature |
Numeric |
An array of up to 8 temperatures representing the local or communicated active condenser temperatures. |
||||||
Space CO2 Concentration: Input |
Numeric |
Controller property that displays the unit’s space carbon dioxide (CO2) concentration in parts per million (ppm), if the UCM has a locally wired CO2 sensor. |
||||||
Space CO2 Concentration: Ref |
Numeric |
Building control property that is used to communicate the space CO2 concentration that is communicated down to the unit This property indicates the value used by the BCU to determine which value to communicate as the. |
||||||
Space CO2 Concentration: Tracer |
Numeric |
Building control property that is used to communicate the space CO2 levels in PPM to the controller. The unit can also have a locally wired CO2 sensor. |
||||||
Space CO2 Limit |
Numeric |
Controller property which defines a high limit CO2 setpoint configuration property for the controlled space. |
||||||
Space CO2 Low Limit | Numeric | This read-only configuration property indicates the default low limit CO2 setpoint for the controlled space. This is where the CO2 demand ventilation control begins. Typical Range: 0 - 2000 ppm | ||||||
Space Dehumidification Setpoint: Active | Numeric | The effective space high humidity limit setpoint communicated from the controller. Valid Range: 0 - 100% |
||||||
Space Dehumidification Setpoint: Local | Numeric | This configuration property indicates the default maximum humidity level for the controlled space. Valid Range: 0 - 100% | ||||||
Space Enthalpy |
Numeric |
Controller property that displays the effective, local or communicated, space enthalpy, When both exist, the communicated value has priority. |
||||||
Space Humidification Setpoint: Active | Numeric | Indicates the active space low humidity limit setpoint. Valid Range: 0 - 100% Invalid = 0x7FFF |
||||||
Space Humidification Setpoint: Local | Numeric | This configuration property indicates the default minimum humidity level for the controlled space. Valid Range: 0 - 100% |
||||||
Space Humidity: Active |
Numeric |
Controller property that displays the effective, local or communicated, space relative humidity as a percentage, When both exist, the communicated value has priority. |
||||||
Space Humidity: Ref | Property Reference | This property indicates the value to be used by the BCU to determine which space humidity value to communicate to the UCM. | ||||||
Space Humidity: Tracer | Numeric | Building control property used to communicate the space relative humidity. Valid Range: 0-100%, Invalid: 0x7FFF | ||||||
Space Pressure Setpoint: Local |
Numeric |
Controller property that displays the default space pressure setpoint. |
||||||
Space Pressure Setpoint: Ref |
Property Reference |
Building control property defines a space pressure setpoint that is communicated down to the unit. |
||||||
Space Pressure Setpoint: Tracer |
Numeric |
Building control property that is used to communicate the space pressure setpoint to the controller. Communicated value used over local value when both are present. |
||||||
Space Pressure: Active |
Numeric |
Controller property which displays the unit’s effective, local or communicated, space pressure. When both exist, the communicated value has priority. |
||||||
Space Pressure: Ref |
Property Reference |
Building control property that defines the space pressure that is communicated down to the unit. |
||||||
Space Pressure: Tracer |
Numeric |
Building control property that is used to communicate the space pressure to the controller. Communicated value used over local value when both are present |
||||||
Space Temperature: Active |
Numeric |
Controller property which displays the unit’s effective, local or communicated, space temperature. When both exist, the communicated value has priority. If neither exist, the unit uses its stored default value. |
||||||
Space Temperature: Ref |
Property Reference |
Building control property that defines the Space Temperature humidity that is communicated down to the unit. . |
||||||
Space Temperature: Tracer |
Numeric |
Building control property that is used to communicate the space temperature to the controller. Communicated value used over local value when both are present. |
||||||
Startup Setpoint |
Numeric |
Building control property defines the threshold for warm-up or pre-cool at start-up. |
||||||
Startup Time Delay |
Unsigned Word |
Controller property that represents the amount of time the controller waits (after power-up) before invoking the normal control algorithm operation. |
||||||
Supply Fan Proving Status | Enumerated | Status that indicates if the supply fan is actually on, compared to the Supply Fan Status property, which may indicate only a requested state. Example of proving actual operation is by means of a current sensing relay on the wires to the fan motor. 0 = Off 1 = On 2 = Not Present. |
||||||
Supply Fan Run Time |
Numeric |
Controller property that displays the number of fan run hours elapsed since the "maintenance required" diagnostic was initiated and cleared. |
||||||
Supply Fan Status |
Numeric |
Controller property that displays the status of unit's fan output. |
||||||
Supply Fan Type |
Multi-State |
Controller property that displays the unit’s supply fan configuration. |
||||||
Timed Override Request |
Binary |
Controller property that displays the active status of the Timed Override flag that is set when the ON button is pushed on the zone sensor. |
||||||
Timed Override Request: Cancel |
Binary |
Controller property that displays the active status of the Cancel Timed Override flag that is set when the CANCEL button is pushed on the zone sensor. |
||||||
Update Tag |
Numeric |
This property is used as the upload/download tag. Its purpose is to keep the PC Workstation and BCU copies of the object instance in synchronization. |
||||||
Water Valve Drive Closed: Ref |
Property Reference |
Building control property is used to override all of the water valves to a closed position. This property is evaluated by the Water Valve Override: Tracer property. |
||||||
Water Valve Drive Open: Ref |
Property Reference |
Building control property is used to override all of the water valves to an open position. This property is evaluated by the Water Valve Override: Tracer property. |
||||||
Water Valve Override: Tracer |
Multi-State |
Building control system’s communicated override command that overrides the unit’s water valves operation. This property relies upon states of Water Valve Drive Open: Ref and Water Valve Drive Closed: Ref properties. Water valve drive open override will have preference over a water valve drive closed override. |