Device

Property

Type

Description

 

Analog Input 1[1]

 

Numeric

 

Value of linear input (0–10 VDC, 0–20 mA, or 100 to 100,000 ohms) connected to Universal Input 1 on the BCU.

 

Analog Input 1[2]

 

Numeric

 

Value of Thermistor sensor (-20 F to 250 F) connected to Universal Input 1 on the BCU.

 

Analog Input 1[3]

 

Numeric

 

Value of Platinum RTD sensor (-90 F to 250 F) connected to Universal Input 1 on the BCU.

 

Analog Input 1[4]

 

Numeric

 

Value of Balco RTD sensor (-64 F to 250 F) connected to Universal Input 1 on the BCU.

 

Analog Input 2[1]

 

Numeric

 

Value of linear input (0–10 VDC, 0–20 mA, or 100 to 100,000 ohms) connected to Universal Input 2 on the BCU.

 

Analog Input 2[2]

 

Numeric

 

Value of Thermistor sensor (-20 F to 250 F) connected to Universal Input 2 on the BCU.

 

Analog Input 2[3]

 

Numeric

 

Value of Platinum RTD sensor (-90 F to 250 F) connected to Universal Input 2 on the BCU.

 

Analog Input 2[4]

 

Numeric

 

Value of Balco RTD sensor (-64 F to 250 F) connected to Universal Input 2 on the BCU.

 

APDU Segment Timeout

 

Binary

 

Application Layer Protocol Data Units (APDUs) represent requests and results of applications communicating over BACnet. Some APDUs are so large they must be broken into multiple "segments." This property indicates the status of the timeout.

 

APDU Timeout

 

Numeric

 

This property indicates the number of milliseconds for an APDU timeout. A timed out APDU is a failed APDU and is retried by the number of times defined by the "Number of APDU Retries" property.

 

Application Software Revision

 

Character

 

Not applicable.

 

BACnet Vendor ID

 

Numeric

 

This property indicates the vendor ID assigned by ASHRAE (used in BACnet communications).

 

BCU Database Status

 

Multi-State

 

Indicates whether BCU’s database is Normal, Under Construction, or Cleared.

 

BCU System Diagnostics[01]

 

Numeric

 

Indicates the number of BCU restarts.

 

BCU System Diagnostics[02]

 

Numeric

 

Indicates the number of interrupted Power Critical Regions.

 

BCU System Diagnostics[03]

 

Numeric

 

Indicates the number of ARCNET reconfigurations. A high or increasing number may indicate cable problems, or two nodes at the same address.

 

BCU System Diagnostics[04]

 

Numeric

 

Indicates the number of ARCNET aborted transmissions (timeouts).

 

BCU System Diagnostics[05]

 

Numeric

 

Indicates the number of ARCNET receive disables (out of buffers).

 

BCU System Diagnostics[06]

 

Numeric

 

Indicates the number of ARCNET messages retransmitted.

 

BCU System Diagnostics[07]

 

Numeric

 

Indicates the remainder of ARCNET good transmissions after being dividing by 65536.

 

BCU System Diagnostics[08]

 

Numeric

 

Indicates the number of ARCNET good transmissions divided by 65536

 

BCU System Diagnostics[09]

 

Numeric

 

Indicates the remainder of ARCNET good receives after being divided by 65536.

 

BCU System Diagnostics[10]

 

Numeric

 

Indicates the number of ARCNET good receives divided by 65536.

 

BCU System Diagnostics[11]

 

Numeric

 

Indicates the number of EEPROM re-tried writes. A non-zero value may indicate a bad or failing EEPROM.

 

BCU System Diagnostics[12]

 

Numeric

 

Indicates the number of unexpected BACnet replies. A high or increasing value may indicate problems with a remote BACnet device.

 

BCU System Diagnostics[13]

 

Numeric

 

Indicates the number of BACnet Reject PDUs sent. A high or increasing value may indicate problems with a remote BACnet device.

 

BCU System Diagnostics[14]

 

Numeric

 

Indicates the number of UCM channel 1 reinits. A high or increasing value may indicate problems with a UCM plugin card.

 

BCU System Diagnostics[15]

 

Numeric

 

Indicates the number of UCM channel 2 reinits. A high or increasing value may indicate problems with a UCM plugin card.

 

BCU System Diagnostics[16]

 

Numeric

 

Indicates the number of UCM channel 3 reinits. A high or increasing value may indicate problems with a UCM plugin card.

 

BCU System Diagnostics[17]

 

Numeric

 

Indicates the number of memory blocks outstanding.

 

BCU System Diagnostics[18]

 

Numeric

 

Indicates the paragraphs of memory remaining.

 

BCU System Diagnostics[19]

 

Numeric

 

Indicates the minimum paragraphs of memory encountered.

 

BCU System Diagnostics[20]

 

Numeric

 

Indicates the number of failing memory requests. A non-zero value is a warning of pool problems.

 

BCU System Diagnostics[21]

 

Numeric

 

Indicates the maximum number of paragraphs.

 

BCU System Diagnostics[22]

 

Numeric

 

Indicates the number of SV memory blocks outstanding.

 

BCU System Diagnostics[23]

 

Numeric

 

Indicates the paragraphs of SV memory remaining.

 

BCU System Diagnostics[24]

 

Numeric

 

Indicates the minimum paragraphs of SV memory encountered.

 

BCU System Diagnostics[25]

 

Numeric

 

Indicates the number of failing SV memory requests. A non-zero value is a warning of pool problems.

 

BCU System Diagnostics[26]

 

Numeric

 

Indicates the maximum number of SV paragraphs.

 

BCU System Diagnostics[27]

 

Numeric

 

Indicates the raw value of analog channel 0 (universal input 1).

 

BCU System Diagnostics[28]

 

Numeric

 

Indicates the raw value of analog channel 1 (universal input 2).

 

BCU System Diagnostics[29]

 

Numeric

 

Indicates the raw value of analog channel 2 (+5 ANAVCC, nominally 2784 counts).

 

BCU System Diagnostics[30]

 

Numeric

 

Indicates the raw value of analog channel 3 (+5 VCC, nominally 2784 counts).

 

BCU System Diagnostics[31]

 

Numeric

 

Indicates the raw value of analog channel 4 (Vunreg+, nominally 2784 counts).

 

BCU System Diagnostics[32]

 

Numeric

 

Indicates the raw value of analog channel 5 (GND, nominally 0 counts).

 

BCU System Diagnostics[33]

 

Numeric

 

Indicates the raw value of analog channel 6 ((-5, nominally 3892 counts).

 

BCU System Diagnostics[34]

 

Numeric

 

Indicates the raw value of analog channel 7 (-12, nominally 3532 counts).

 

BCU System Diagnostics[35]

 

Numeric

 

Indicates the raw value of analog channel 8 (Vunreg-, nominally 3341 counts).

 

BCU System Diagnostics[36]

 

Numeric

 

Indicates the raw value of analog channel 9 (+12, nominally 3265 counts).

 

BCU System Diagnostics[37]

 

Numeric

 

Indicates the raw value of analog channel 10 (VPP, nominally 136 or 3265 counts).

 

BCU System Diagnostics[38]

 

Numeric

 

Indicates the raw value of analog channel 11 ref/2, nominally 2048 counts).

 

BCU System Diagnostics[39]

 

Numeric

 

Number of UCM channel 1 NAKs. A high or increasing value may indicate problems with a UCM plugin card.

 

BCU System Diagnostics[40]

 

Numeric

 

Number of UCM channel 2 NAKs. A high or increasing value may indicate problems with a UCM plugin card.

 

BCU System Diagnostics[41]

 

Numeric

 

Number of UCM channel 3 NAKS. A high or increasing value may indicate problems with a UCM plugin card.

 

BCU System Diagnostics[42]

 

Numeric

 

Number of COM1 false interrupts. A high value may indicate a faulty IBM-bus serial card or modem.

 

BCU System Diagnostics[43]

 

Numeric

 

Number of COM1 receive bytes in FIFO.

 

BCU System Diagnostics[44]

 

Numeric

 

Number of DCD transitions. A high or increasing value may indicate an incorrect serial cable.

 

BCU System Diagnostics[45]

 

Numeric

 

Number of NO DCD transistions. A high or increasing value may indicate an incorrect serial cable.

 

BCU System Diagnostics[46]

 

Numeric

 

Any other Asynce related errors fro Rx handler. A high or increasing value may indicate an incorrect serial cable.

 

BCU System Diagnostics[43–50]

 

Numeric

 

Not applicable

 

Binary Input 1[1]

 

Binary

 

Status of analog timed override switch if an analog input is connected to Universal Input 1 on the BCU.

 

Binary Input 1[2]

 

Binary

 

Status of analog input failure if an analog input is connected to Universal Input 1 on the BCU.

 

Binary Input 1[3]

 

Binary

 

Status of a normally open momentary binary input connected to Universal Input 1 on the BCU.

 

Binary Input 1[4]

 

Binary

 

Status of a continuous binary input connected to Universal Input 1 on the BCU.

 

Binary Input 2[1]

 

Binary

 

Status of analog timed override switch if an analog input is connected to Universal Input 2 on the BCU.

 

Binary Input 2[2]

 

Binary

 

Status of analog input failure if an analog input is connected to Universal Input 2 on the BCU.

 

Binary Input 2[3]

 

Binary

 

Status of a normally open momentary binary input connected to Universal Input 2 on the BCU.

 

Binary Input 2[4]

 

Binary

 

Status of a continuous binary input connected to Universal Input 2 on the BCU.

 

Firmware Revision

 

Character

 

Version number and date of factory software in the BCU.

 

Local Date

 

Date/Time Numeric

 

Current Date in the BCU.

 

Local Time

 

Date/Time Numeric

 

Current Time in the BCU.

 

Max Message Length Supported

 

Numeric

 

Longest message the BCU can transmit or receive over the ARCNET LAN.

 

Mode: System Status

 

Character

 

This property indicates the BACnet defined device status. OPERATIONAL, OPERATIONAL READ ONLY, DOWNLOAD REQUIRED, DOWNLOAD IN PROGRESS, NON OPERATIONAL.

 

Model Name

 

Character

 

Tracer Building Control Unit.

 

Network Number

 

Numeric

 

The property indicates the unique numeric value of the comfort system (for example, network) or grouping to which the current BCU is connected.

 

Number of APDU Retries

 

Numeric

 

This property indicates the number of times an APDU segment communication attempt will be made.

 

Object Identifier

 

Object ID

 

Unique hexadecimal ID of this object. This ID is used internally to identify the object.

 

Object List [1]

 

Character

 

Not Applicable.

 

Object Type

 

Multi-State

 

Designates object’s type (i.e., analog input, binary output, TCM, PCM, etc.).

 

Percent BCU NVM Available

 

Numeric

 

This property indicates the percent of nonvolatile memory storage left for database use.

 

Percent BCU VM Available

 

Numeric

 

This property indicates the percent of volatile memory storage left for database use.

 

Percent Processor Idle Time

 

Numeric

 

Indicates the average idle time (%) of the processor for the first 5 minutes.

 

Protocol Conformance Class

 

Numeric

 

Protocol class to which the BCU conforms.

 

Protocol Version

 

Character

 

Protocol version the BCU is using.

 

Segmentation Supported

 

Binary

 

Some APDUs are so large they must be broken into multiple "segments." This property indicates the whether segmentation is supported.

 

Update Tag

 

Numeric

 

Value indicating last edit change of this object.

 

Vendor Name

 

Character

 

Trane Global Controls and Contracting.

 

Window Size

 

Numeric

 

Not applicable.

 

 

 

Device — BMTS and BMTW

 

BMTS — Model Building Control Unit (BCU)

Property Type Description

 

Analog Input 1[1]

 

Numeric

 

Value of linear input (0–10 VDC, 0–20 mA, or 100 to 100,000 ohms) connected to Universal Input 1 on the BCU.

 

Analog Input 1[2]

 

Numeric

 

Value of Thermistor sensor (-20 F to 250 F) connected to Universal Input 1 on the BCU.

 

Analog Input 1[3]

 

Numeric

 

Value of Platinum RTD sensor (-90 F to 250 F) connected to Universal Input 1 on the BCU.

 

Analog Input 1[4]

 

Numeric

 

Value of Balco RTD sensor (-64 F to 250 F) connected to Universal Input 1 on the BCU.

 

Analog Input 2[1]

 

Numeric

 

Value of linear input (0–10 VDC, 0–20 mA, or 100 to 100,000 ohms) connected to Universal Input 2 on the BCU.

 

Analog Input 2[2]

 

Numeric

 

Value of Thermistor sensor (-20 F to 250 F) connected to Universal Input 2 on the BCU.

 

Analog Input 2[3]

 

Numeric

 

Value of Platinum RTD sensor (-90 F to 250 F) connected to Universal Input 2 on the BCU.

 

Analog Input 2[4]

 

Numeric

 

Value of Balco RTD sensor (-64 F to 250 F) connected to Universal Input 2 on the BCU.

 

APDU Segment Timeout

 

Binary

 

Application Layer Protocol Data Units (APDUs) represent requests and results of applications communicating over BACnet. Some APDUs are so large they must be broken into multiple "segments." This property indicates the status of the timeout.

 

APDU Timeout

 

Numeric

 

This property indicates the number of milliseconds for an APDU timeout. A timed out APDU is a failed APDU and is retried by the number of times defined by the "Number of APDU Retries" property.

 

Application Software Revision

 

Character

 

Not applicable.

 

BACnet Vendor ID

 

Numeric

 

This property indicates the vendor ID assigned by ASHRAE (used in BACnet communications).

 

BCU Database Status

 

Multi-State

 

Indicates whether BCU’s database is Normal, Under Construction, or Cleared.

 

BCU System Diagnostics[01]

 

Numeric

 

Number of BCU restarts since RAM was last cleared.

 

BCU System Diagnostics[02]

 

Numeric

 

Number of interrupted Power Critical Regions.

 

BCU System Diagnostics[03]

 

Numeric

 

ARCNET: Number of reconfigurations. A high or increasing number may indicate cable problems, or two nodes at the same address.

 

BCU System Diagnostics[04]

 

Numeric

 

Number of ARCNET/Ethernet aborted transmissions.

 

BCU System Diagnostics[05]

 

Numeric

 

Number of ARCNET/Ethernet receive out of buffers.

 

BCU System Diagnostics[06]

 

Numeric

 

Number of ARCNET/Ethernet messages retransmitted.

 

BCU System Diagnostics[07]

 

Numeric

 

Number of ARCNET/Ethernet good transmissions, low 16 bits.

 

BCU System Diagnostics[08]

 

Numeric

 

Number of ARCNET/Ethernet good transmissions, high 16 bits.

 

BCU System Diagnostics[09]

 

Numeric

 

Number of ARCNET/Ethernet good receives, low 16 bits

 

BCU System Diagnostics[10]

 

Numeric

 

Number of ARCNET/Ethernet good receives, high 16 bits. 

 

BCU System Diagnostics[11]

 

Numeric

 

Number of EEPROM re-tried writes. A non-zero value may indicate a bad or failing EEPROM.

 

BCU System Diagnostics[12]

 

Numeric

 

Number of unexpected BACnet replies. A high or increasing value may indicate problems with a Workstation or remote BACnet device.

 

BCU System Diagnostics[13]

 

Numeric

 

Number of BACnet Reject PDUs sent. A high or increasing value may indicate problems with a Workstation or remote BACnet device.

 

BCU System Diagnostics[14]

 

Numeric

 

Number of UCM channel 1 reinits. A high or increasing value may indicate problems with the UCM plugin card.

 

BCU System Diagnostics[15]

 

Numeric

 

Number of UCM channel 2 reinits. A high or increasing value may indicate problems with the UCM plugin card.

 

BCU System Diagnostics[16]

 

Numeric

 

Number of UCM channel 3 reinits. A high or increasing value may indicate problems with the UCM plugin card.

 

BCU System Diagnostics[17]

 

Numeric

 

Number of memory blocks outstanding.

 

BCU System Diagnostics[18]

 

Numeric

 

Paragraphs of memory remaining.

 

BCU System Diagnostics[19]

 

Numeric

 

Minimum paragraphs of memory encountered.

 

BCU System Diagnostics[20]

 

Numeric

 

Number of failing memory requests. A non-zero value is a warning of memory problems.

 

BCU System Diagnostics[21]

 

Numeric

 

Maximum number of paragraphs.

 

BCU System Diagnostics[22]

 

Numeric

 

Number of VM (database RAM) memory blocks outstanding.

 

BCU System Diagnostics[23]

 

Numeric

 

Paragraphs of VM (database RAM) memory remaining.

 

BCU System Diagnostics[24]

 

Numeric

 

Minimum paragraphs of VM (database RAM) memory encountered.

 

BCU System Diagnostics[25]

 

Numeric

 

Number of failing VM (database RAM) memory requests. A non-zero value is a warning of memory problems.

 

BCU System Diagnostics[26]

 

Numeric

 

Maximum number of VM (database RAM) memory paragraphs.

 

BCU System Diagnostics[27]

 

Numeric

 

Analog channel 0 (raw value of Universal input 1)

 

BCU System Diagnostics[28]

 

Numeric

 

Analog channel 1 (raw value of Universal input 2)

 

BCU System Diagnostics[29]

 

Numeric

 

Analog channel 2 (+5 ANAVCC, 2504 to 3064, nominal 2784)

 

BCU System Diagnostics[30]

 

Numeric

 

Analog channel 3 (+5 VCC, 2504 to 3064, nominal 2784)

 

BCU System Diagnostics[31]

 

Numeric

 

Analog channel 4 (Vunreg+, 2636 to 3164, nominal 2644)

 

BCU System Diagnostics[32]

 

Numeric

 

Analog channel 5 (Vunreg+, 2636 to 3164, nominal 2644)

 

BCU System Diagnostics[33]

 

Numeric

 

Analog channel 6 (-5, 2104 to 2432, nominal 3892)

 

BCU System Diagnostics[34]

 

Numeric

 

Analog channel 7 (-12, 3100 to 3240, nominal 3532)

 

BCU System Diagnostics[35]

 

Numeric

 

Analog channel 8 (Vunreg-, 3576 to 3908, nominal 3800)

 

BCU System Diagnostics[36]

 

Numeric

 

Analog channel 9 (+12, 3132 to 3404, nominal 3265)

 

BCU System Diagnostics[37]

 

Numeric

 

Analog channel 10 (VPP, 0000 to 1496, nominal 136)

 

BCU System Diagnostics[38]

 

Numeric

 

Analog channel 11 (ref/2, 2028 to 2068, nominal 2048)

 

BCU System Diagnostics[39]

 

Numeric

 

Number of UCM channel 1 NAKs. A high or increasing value may indicate problems with the UCM plugin card

 

BCU System Diagnostics[40]

 

Numeric

 

Number of UCM channel 2 NAKs. A high or increasing value may indicate problems with the UCM plugin card.

 

BCU System Diagnostics[41]

 

Numeric

 

Number of UCM channel 3 NAKS. A high or increasing value may indicate problems with the UCM plugin card.

 

BCU System Diagnostics[42]

 

Numeric

 

Number of COM1 false interrupts. A high value may indicate a faulty IBM-bus serial card or modem.

 

BCU System Diagnostics[43]

 

Numeric

 

Number of COM1 bytes in FIFO.

 

BCU System Diagnostics[44]

 

Numeric

 

Number of DCD transitions. A high or increasing value may indicate an incorrect serial cable.

 

BCU System Diagnostics[45]

 

Numeric

 

Number of NO DCD transitions. A high or increasing value may indicate an incorrect serial cable.

 

BCU System Diagnostics[46]

 

Numeric

 

Any other Async related errors from Rx handler. A high or increasing value may indicate an incorrect serial cable.

 

Binary Input 1[1]

 

Binary

 

Status of analog timed override switch if an analog input is connected to Universal Input 1 on the BCU.

 

Binary Input 1[2]

 

Binary

 

Status of analog input failure if an analog input is connected to Universal Input 1 on the BCU.

 

Binary Input 1[3]

 

Binary

 

Status of a normally open momentary binary input connected to Universal Input 1 on the BCU.

 

Binary Input 1[4]

 

Binary

 

Status of a continuous binary input connected to Universal Input 1 on the BCU.

 

Binary Input 2[1]

 

Binary

 

Status of analog timed override switch if an analog input is connected to Universal Input 2 on the BCU.

 

Binary Input 2[2]

 

Binary

 

Status of analog input failure if an analog input is connected to Universal Input 2 on the BCU.

 

Binary Input 2[3]

 

Binary

 

Status of a normally open momentary binary input connected to Universal Input 2 on the BCU.

 

Binary Input 2[4]

 

Binary

 

Status of a continuous binary input connected to Universal Input 2 on the BCU.

 

Firmware Revision

 

Character

 

Version number and date of factory software in the BCU.

 

Local Date

 

Date/Time Numeric

 

Current Date in the BCU.

 

Local Time

 

Date/Time Numeric

 

Current Time in the BCU.

 

Max Message Length Supported

 

Numeric

 

Longest message the BCU can transmit or receive over the ARCNET LAN.

 

Mode: System Status

 

Character

 

This property indicates the BACnet defined device status. OPERATIONAL, OPERATIONAL READ ONLY, DOWNLOAD REQUIRED, DOWNLOAD IN PROGRESS, NON OPERATIONAL.

 

Model Name

 

Character

 

Tracer Building Control Unit.

 

Network Number

 

Numeric

 

The property indicates the unique numeric value of the comfort system (for example, network) or grouping to which the current BCU is connected.

 

Number of APDU Retries

 

Numeric

 

This property indicates the number of times an APDU segment communication attempt will be made.

 

Object Identifier

 

Object ID

 

Unique hexadecimal ID of this object. This ID is used internally to identify the object.

 

Object List [1]

 

Character

 

Not Applicable.

 

Object Type

 

Multi-State

 

Designates object’s type (i.e., analog input, binary output, TCM, PCM, etc.).

 

Percent BCU NVM Available

 

Numeric

 

This property indicates the percent of nonvolatile memory storage left for database use.

 

Percent BCU VM Available

 

Numeric

 

This property indicates the percent of volatile memory storage left for database use.

 

Percent Processor Idle Time

 

Numeric

 

Indicates the average idle time (%) of the processor for the first 5 minutes.

 

Protocol Conformance Class

 

Numeric

 

Protocol class to which the BCU conforms.

 

Protocol Version

 

Character

 

Protocol version the BCU is using.

 

Segmentation Supported

 

Binary

 

Some APDUs are so large they must be broken into multiple "segments." This property indicates the whether segmentation is supported.

 

Update Tag

 

Numeric

 

Value indicating last edit change of this object.

 

Vendor Name

 

Character

Trane Global Controls and Contracting

 

Window Size

 

Numeric

 

Not applicable.