Binary Output

Property Type Description
Active Text Character Describes the active (On) state of the present value (i.e., On, Enable, Occupy, etc.).
Change of State Time Date/Time Numeric Displays the date and time that the binary output was last controlled by another application (i.e. TOD lighting start).
Control Event Class Numeric Contains the Alarm and Message Routing Class number (1–20) that is used to route messages when this object is controlled.
CPL Program ID Object Ref CPL program executed by the object’s change of state.
Inactive Text Character Describes the inactive (Off) state of the present value (i.e., Off, Disable, Unoccupy, etc.).
Last Control Date Time Date/Time Numeric This indicates the date and time when the present value property of this object was last controlled.
Minimum Off Time Numeric Defines the minimum time the binary output must be in the Off state before it can be turned On again.
Minimum On Time Numeric Defines the minimum time the binary output must be in the On state before it can be turned Off.
Minimum Time Remaining Numeric Defines the time left until the minimum off or minimum on time (whichever is in effect) expires.
Object Identifier Object ID Unique hexadecimal ID of this object. This ID is used internally to identify the object.
Object Type Multi-State Designates object’s type (i.e., analog input, binary output, TCM, PCM, etc.).
Present Value Multi-State Current value of the binary output
Reference Object/Prop. Ref Object and property which this binary output is writing its value to.
Update Tag Numeric Value indicating last edit change of this object.