Property | Type | Description |
Acknowledged |
Binary |
Indicates whether the input’s current alarm state is acknowledged or not. |
Change of State Time |
Date/Time Numeric |
Displays the date and time that the property reference last changed state. |
CPL Program ID |
Object Ref |
CPL program executed by the object’s change of state. |
Enabled |
Binary |
Indicates whether alarming is enabled for this input. |
Event Deadband |
Numeric |
Value of deadband when transitioning from alarm to normal. |
Event Minimum On Time |
Numeric |
Amount of time input must be in alarm before system notification. |
Event State |
Multi-State |
When alarming is enabled, this property displays the current condition for the analog input. If alarming is disabled, this field displays Normal. Valid Range: High Alarm, High Warning, Normal, Low Warning, Low Alarm |
Last Event Class |
Numeric |
Value of the alarm class to which this input is assigned. |
Multiplier |
Numeric |
Value used to convert the actual input value to the displayed input value. |
Object Identifier |
Object ID |
Unique hexadecimal ID of this object. This ID is used internally to identify the object. |
Object Type |
Multi-State |
Designates object’s type (i.e., analog input, binary output, TCM, PCM, etc.). |
Offset |
Numeric |
Value used to offset the actual input value to the displayed input value. |
Present Value |
Numeric |
Current value of the analog input. |
Reference |
Object/Prop. Ref |
Object and property from which this analog input is getting its present value. |
Switch Delay |
Numeric |
Amount of time switch reference must be on before allowing analog input to alarm. |
Switch Reference |
Binary |
This property indicates the active status of the enable/disable reference for the analog input alarm function. |
Units |
Multi-State |
Indicates current units (i.e., degrees, percent, etc.) used for analog input. |
Update Tag |
Numeric |
Value indicating last edit change of this object. |