When you go to the advanced overrides page for a Intellipack Rooftop Unit in addition to Present Value, the following fields can be overridden:
Use this referencer edit control to disable all the heating on the IntelliPak. When this control is set to Disable, the unit is prevented from actively heating. When the control is set to Auto, the unit operates normally.
A system binary property can be referenced to control this field to Disable or Auto. If the referencer is in the Off state, Disable will appear in the field. If the referencer is in the On state, Auto will appear in the field.
Use this referencer edit control to disable all cooling (DX and Chilled Water) on the IntelliPak. When this control is set to Disable, cooling on the IntelliPak will not be allowed to operate. When this control is set to Auto mechanical cooling at the IntelliPak will be functional and will cool when requested by the IntelliPak’s cooling control algorithms.
A system binary property can be referenced to control this field to Disable or Auto. If the referencer is in the Off state, Disable will appear in the field. If the referencer is in the On state, Auto will appear in the field.
Use these referencer edit controls to initiate a Tracer Summit Ventilation Override. These are five modes of ventilation override (A, B, C, D and E) that Tracer Summit can initiate. A referencer edit control exists for each one of these modes. The specifics of how the IntelliPak will function for each override is handled at the IntelliPak's human interface panel. If Auto is selected, Tracer Summit is not requesting a VOM (The VOM modes can still be activated locally at the IntelliPak UCM). If On is selected, Tracer Summit is requesting a VOM to be activated.
A system binary property can be referenced to control this field to On or Off. The On state generates the On value. The Off state generates the Auto value.