When you go to the advanced overrides page for a Commercial Self-Contained Unit in addition to Present Value, the following fields can be overridden:
Use this referencer edit control to lock out all mechanical cooling at the unit. When this control is set to Disable, the operations of the unit’s compressors are stopped. When the control is set to Auto, the unit operates normally.
Use this referencer edit control to override the current operating mode of the UCM. When this control is set to Disable, the unit is prevented from actively heating. When the control is set to Auto, the unit operates normally.
Use this referencer edit control to override the ventilation output of the UCM. When this control is set to Auto, the CSC is allowed to decide when to turn its ventilation output on. When the control is set to Disable, the CSC unit is forced to turn off its ventilation output.
Use this referencer edit control to override the maximum ventilation mode of the CSC unit. When this control is set to Auto, the CSC operates normally. When the control is set to Forced, the CSC is put in Forced Max Vent mode. In this mode, all mechanical heating and cooling is off, and the supply fan is on. Static pressure control is also active in the Forced Max Vent mode.