Alarm Priorities: Mapping

Notification classes must be defined to enable Tracer Ensemble to notify the intended recipients of building alarms in the most efficient manner possible. Tracer Ensemble supports as many alarm notification classes as needed for each panel type.

Notes: To receive alarms from Tracker panels, the Tracer Ensemble system must be configured in the building control panel as a recipient of alarms with the Tracker service tool. The workstation ID of the Tracer Ensemble system must match the workstation ID used in the programming of the Tracker alarm event receiver for the Tracer Ensemble system to receive Tracker alarms.  See table below. To receive alarms from Tracker Version 12 or higher panels, Tracer Ensemble will "register foreign" with the building control panel during the building discovery process.

 

Workstation number

Workstation ID

1

82

2

83

3

84

4

85

5

86

6

87

7

88

8

89

9

90

10

91

 

To map alarm priority levels to notification classes:

  1. In the header, select Actions and Settings |  Priority Mappings.
  2. Select the Panel Type and click Next.
  3. Using the drop down boxes, select an alarm category for each priority.
  4. Click Finish. The new priority levels will be applied immediately to existing and new panels of the type specified, but alarms received before the change will not be affected.